1 |
Enhancement of cooling tower performance by manipulation of rain zone drop sizeOosthuizen, Henry Randolph 03 1900 (has links)
Thesis (MEng)--University of Stellenbosch, 1995. / AFRIKAANSE OPSOMMING: Die moontlikheid om die warmteoordrag in die reensone van 'n natuurlike trek nat koeltoring
te vcrbeter deur die gemiddelde druppel diameter van die sproei te verminder is ondersoek.
Eksperimentele wcrk was daarop gerig om tipiese druppelgrootte verspreidings onder
druppakking te bepaal, asook die verkryging van werklike verrigtings-data vir verskiJlende
pakking en reensone kombinasies in 'n koeltoring toetsfasiliteit. 'n Fotografiese metode wat
gebruik maak van beeldverwerkingstegniekc is ontwikkel om die druppelgrootte verspreidings
wat in die )meltoring toetsfasiliteit gevind word te bepaal. 'n Rekenaar simulasieprogram wat
ontwikkel is deur Dreyer [940Rl] is verder gebruik om reensone verrigtingsdata
( oordragskarakteristieke en druppelgrootte verspreidings) teoreties te vcorspel, vir vergelyking
met en evalusie van die eksperimentele resultate.
Dit is bewys dat die plasing van 'n laag spatroosters reg onder druppakking die gerniddelde
druppeldiameter in die reensone verrninder het, wat gelei het tot 'n ooreenstemmende toename
in oordragskarakteristiek. Met die gebruik van 'n rekenaar simulasie program is bereken dat
hierdie opstelling die termiese kapasiteit van 'n koeltoring met tot 5 % kan verbeter. / ENGLISH ABSTRACT: The possibility of improving the heat transfer in the rain zone of large natural draft wet cooling
towers, by decreasing the mean drop diameter in this region, has been investigated.
Experimental studies were aimed at determining typical drop size distributions under trickle
packs and obtaining actual performance data for packing and rain zone combinations in a
cooling tower test facility. A photography-based method, which utilizes image processing
techniques, was develo!Jed t() determine the drop size distributions found in the test facility. A
computer simulation program developed by Dreyer [94DRI] was used to theoretically predict
rain zone performance data (i.e., transfer coefficients and drop size distribution data) for
comparison with and evaluation of the experimental data.
I: was found that by placing a layer of splash grids beneath a trickle pack the mean drop
diameter in the rain zone was decreased, resulting in corresponding increases in transfer
characteristic. Using a computer simulation program it was calculated that this arrangement
could increase the thermal capacity of a large natural draft cooling tower by up to 5 %.
|
2 |
Performance optimization of engineering systems with particular reference to dry-cooled power plantsConradie, Antonie Eduard 03 1900 (has links)
Thesis (PhD (Mechanical and Mechatronic Engineering))--University of Stellenbosch, 1995. / Computer simulation programs were developed for the analysis of dry-cooling systems for power
plant applications. Both forced draft direct condensing air"cooled condensers and hyperbolic natural
draft indirect dry-cooling towers are considered.
The results of a considerable amount of theoretical and experimental work are taken into account to
model all the physical phenomena ofthese systems, to formu1ate the problems in formal mathematical
terms and to design and apply suitable computational algorithms to solve these problems effectively
and reliably.
The dry-cooling systems are characterized by equation-based models. These equations are
simultaneously solved by a specially designed constrained nonlinear least squares algorithm to
determine the performance characteristics of the dry-cooling systems under fixed prescnoed
operating conditions, or under varying operating conditions when coupled to a turbo-generator set.
The solution procedure is very fast and effective.
A capital and operating cost estimation procedure, based on information obtained from dry-cooling
system component manufacturers and the literature, is proposed. Analytical functions express the
annual cost in terms ofthe various geometrical and operating parameters ofthe dry-cooling systems.
The simu1ation and the cost estimation procedures were coupled to a constrained nonlinear
programming code which enable the design of minimum cost dry-cooling systems at fixed prescribed
operating conditions, or dry-cooling systems which minimize the ratio of total annual cost to the
annual net power output of the corresponding turbo-generator set. Since prevailing atmospheric
conditions, especially the ambient temperature, influence the performance of dry-cooling systems,
wide fluctuations in turbine back pressure occur. Therefore, in the latter case the optimal design is
based on the annual mean hourly frequency ofambient temperatures, rather than a fixed value.
The equation-based models and the optimization problems are simultaneously solved along an
infeasible path (infeasible path integrated approach). The optimization model takes into
consideration all the parameters that may affect the capital and operating cost of the dry-cooling
systems and does not prescribe any limits, other than those absolutely essential due to practical
limitations and to simulate the systems effectively. The influence that changes ofthe constraint limits
and some problem parameters have on the optinmm solution, are evaluated (sensitivity analysis). The Sequential Quadratic Programming (SQP) method is used as the basis in implementing nonlinear
optimization techniques to solve the cost minimirnti~n problems. A stable dual active set algorithm
for convex quadratic programming (QP) problems is implemented that makes use of the special
features ofthe QP subproblems associated with the SQP methods. TIrls QP algorithm is also used as
part of the algorithm that solves the constrained nonlinear least squares problem This particular
implementation of the SQP method proved to be very reliable and efficient when applied to the
optimization problems based on the infeasible path integrated approach.
However, as the nonlinear optimization problems become large, storage requirements for the Hessian
matrix and computational expense of solving large quadratic programming (QP) subproblems
become prohibitive. To overcome these difficulties, a reduced Hessian SQP decomposition strategy
with coordinate bases was implemented. This method exploits the low dimensionality of the
subspace of independent decision variables. The performance of this SQP decomposition is further
improved by exploiting the mathematical structure of the engineering model, for example the block
diagonal structure ofthe Jacobian matrix. Reductions ofbetween 50-90% in the total CPU time are
obtained compared to conventional SQP optimization methods. However, more function and
gradient evaluations are used by this decomposition strategy.
The computer programs were extensively tested on various optimization problems and provide fast
and effective means to determine practical trends in the manufacturing and construction of costoptimal
dry-cooling systems, as well as their optimal performance and operating conditions in power
plant applications.
The dissertation shows that, through the proper application of powerful optimization strategies and
careful tailoring of the well constructed optimization model, direct optimization of complex models
does not need to be time consuming and difficult.
Reconnnendations for further research are made. / Imported from http://etd.sun.ac.za April 2010.
|
Page generated in 0.1199 seconds