Effektbegränsning värme : Analys och energieffektivisering av värmesystem på Umeå campus / Power limitation of heat : Analysis and energy efficiency improvements of the heating systems at Umeå campus

Eriksson, Mattias January 2024 (has links)
För majoriteten av Umeå universitetscampus finns en anslutningspunkt för fjärrvärme från Umeå Energi. Under januari 2024 uppstod problem när fjärrvärmeeffekten överskred den abonnerade nivån under några extremt kalla dagar, vilket resulterade i straffavgifter från leverantören. Projektets syfte är att analysera och lösa överbelastningsproblemen genom att hitta och jämföra olika förbättringar för värmesystemen på campus. Effektsignaturer analyserades för utvärdering av variationen i den inköpta fjärrvärmen på Umeå universitetscampus, för drift under och utanför verksamhetstid. Resultaten visar en maximal potentiell effektreduktion på 29,4% vid DVUT (dimensionerande vinterutetemperatur). En strategisk driftstrategi kan tillämpas genom att ändra styrsystemets globala tidsschema till röd dag för att uppnå effektreduktion i byggnader utan närvaro. Detta motsvarar en maximal potentiell ekonomisk besparing på 1,7 miljoner kronor för den totala effektreduktionen. Effektkartläggning av Fysikhusets värmesystem utfördes. Resultatet vid DVUT visade att radiatorerna endast stod för 30% av fjärrvärmeeffekten, LA001 (ventilationsaggregat i Fysikhuset, laborationssalar) 64% och LA002 (ventilationsaggregat i Fysikhuset, kontor) 6%. Fysikhusets variation i fjärrvärmebehov under och utanför verksamhetstid vid DVUT visar en minimal skillnad på endast 0,3%, vilket främst beror på värmesystemens utformning och verksamheten som bedrivs. Radiatorernas effektbehov i Fysikhuset vid DVUT analyserades vid sänkning av inomhustemperatur från 21°C till 18°C. Resultaten visar en effektreduktion på 8,7kW och en ekonomisk besparing på 5 746kr, jämfört med radiatorernas normala effektbehov på 43,5kW. Sänkning av ventilationsflöde i Fysikhuset enligt BBR (Boverkets byggregler) visar potential för betydande effektreduktion, med möjlighet att minska ventilationen upp till 61,8% under närvaro och 89,1% utanför närvaro, vilket kan leda till en ekonomisk besparing på mellan 4 700 - 59 500kr. Beräkningar visar att för varje grad (°C) sänkning av tilluftstemperaturen i Fysikhusets ventilation kan en effektreduktion på LA001 och LA002 uppnå 4kW och 3,7kW per grad respektive, vid DVUT. / For most of the buildings on Umeå University campus there is one main connection point for district heating from Umeå Energi. In January 2024 problems occurred when the district heating output exceeded the subscribed level during some extremely cold days, resulting in penalty charges from the supplier. The purpose of the project is to analyse and solve the overload problems by finding and comparing different improvements for the heating systems on campus. Power signatures were analysed for evaluation of the variation in the purchased district heating at Umeå University campus, for operation during and outside business hours. The results show a maximum potential power reduction of 29,4% at DVUT (dimensioned winter outdoor temperature). An operating strategy can be applied by changing the control system's global time schedule to public holiday to achieve a power reduction in unoccupied buildings. This corresponds to a maximum potential financial saving of SEK 1,7 million for the total effect reduction. Power mapping of the building “Fysikhusets” heating system was carried out. The results at DVUT showed that the radiators accounted for only 30% of the district heating power, LA001 (ventilation unit in Fysikhuset, laboratory rooms) 64% and LA002 (ventilation unit in Fysikhuset, offices) 6%. The district heating demand variation in Fysikhuset during and outside of operating hours at DVUT shows a minimal difference of only 0,3%, which is mainly due to the design of the heating systems and the operations that are carried out in the building. A power reduction on the radiators in Fysikhuset was analysed by lowering the indoor temperatures from 21°C to 18°C, the results showed a power reduction of 8,7 kW and a financial saving of SEK 5 746. Compared to the radiators normal power requirement of 43,5kW. Reduction of ventilation flow in Fysikhuset according to BBR (Boverket´s building regulations) shows potential for significant power reduction, with the possibility of reducing ventilation up to 61,8% during attendance and 89,1% without attendance, which can lead to a financial saving of between SEK 4,700 - 59,500. Calculations show that for each degree (°C) lowering of the supply air temperature in Fysikhusets ventilation, a power reduction on LA001 and LA002 can reach 4kW and 3,7kW for each degree respectively, at DVUT.

Page generated in 0.0773 seconds