The objective of this project was to evaluate methods to remediate a wood I-joist with a single, circular hole in the web while leaving utilities in place. The methods were experimentally evaluated with a full-scale bending test using four equally spaced point loads. There were three depths of joists with varying flange widths and two span lengths (4.88 m & 2.44 m). Failure modes for the long span joists without holes were in the flanges in either tension, compression or lateral buckling; but once a hole was introduced the majority were classified as shear failures. Effectiveness of the remediation was evaluated based on three criteria: strength, stiffness, and ease of installation/cost. The OSB collar patch was effective for 8 out of the 12 series tested. A maximum reduction of load from a joist with no hole to one with a hole was 49% for the long span and 58% for the short span. The OSB collar was not as effective in returning stiffness to the joists, but was easier to install and less expensive than the LSL patch. / Graduation date: 2013