Return to search

Métodos determinísticos para detecção e localização por área de faltas monofásicas de alta impedância sustentadas nos circuitos primários de sistemas de distribuição desequilibrados

Submitted by Renata Lopes (renatasil82@gmail.com) on 2017-04-11T15:15:34Z
No. of bitstreams: 1
joaotitoalmeidavianna.pdf: 4307092 bytes, checksum: 061d2a47a7e37bf6c1a1875c27f352ad (MD5) / Approved for entry into archive by Adriana Oliveira (adriana.oliveira@ufjf.edu.br) on 2017-04-18T12:47:46Z (GMT) No. of bitstreams: 1
joaotitoalmeidavianna.pdf: 4307092 bytes, checksum: 061d2a47a7e37bf6c1a1875c27f352ad (MD5) / Made available in DSpace on 2017-04-18T12:47:46Z (GMT). No. of bitstreams: 1
joaotitoalmeidavianna.pdf: 4307092 bytes, checksum: 061d2a47a7e37bf6c1a1875c27f352ad (MD5)
Previous issue date: 2016-09-05 / O presente trabalho tem por objetivo o desenvolvimento de alternativas para detecção de faltas de alta impedância (HIFs) sustentadas em sistemas de distribuição. Como a maioria destas faltas é monofásica, enfoque foi dado para este tipo de falta no desenvolvimento do trabalho. Devido ao desequilíbrio e a variação da carga dos sistemas de distribuição, a proteção tradicional dos mesmos apresenta dificuldades na detecção destas faltas, que acabam se sustentando no sistema. Isso acarreta um risco de segurança pública, na medida em que estruturas externas ao sistema elétrico são mantidas energizadas representando risco a vidas que entrem em contato com elas. Características da topologia típica de sistemas de distribuição brasileiros (conhecida como do “tipo europeu”) foram exploradas de forma a se elaborar duas propostas de métodos de detecção e localização de HIFs. Ambos os métodos se baseiam na alocação de medidores alocados ao longo do sistema de distribuição, cujas medidas são integradas a uma central de dados via rede de comunicação. Nesta central, as medidas recebidas são analisadas de forma a diagnosticar a presença e localização de faltas monofásicas de alta impedância no sistema e emitir alarmes que descrevam a situação atual do mesmo. O primeiro método, o PDSZ, baseia-se em medições fasoriais sincronizadas e, além da detecção e localização, conta com um algoritmo de classificação das fases envolvidas na falta. Já o segundo (PQDSZ) baseia-se em medições não fasoriais e não possui esta última funcionalidade. Ambos os métodos são implementados em laboratório e simulados com o uso de um Simulador Digital de Tempo Real (RTDS), o que permite uma validação bem próxima da aplicação dos métodos em um sistema real. Tais simulações comprovam a aplicabilidade dos métodos propostos e todos os resultados são analisados de forma a confirmar este fato. / This work aims to develop alternatives for the detection of sustained high impedance faults (HIFs) on distribution power systems. As the majority of these faults are single phase ones, the development was focused on this kind of fault. Due to load unbalance and variation of the distribution systems, the traditional protectiontechniques presents problems on detecting these faults, which are kept sustained on the system. This situation represents a serious public hazard, because the external electrical system structure remains energized, representing a risk to lives that eventually get in touch with it. There is also the risk of starting a fire from this fault point. Topologycal features of Brasilian distribution systems (known as “european type”) were exploited in order to elaborate two methods for detection and localization of HIFs. Both methods are based on the use of meters alocated along the distribution system, whose measurements are sent to a central data concentrator, through a network communication. Then, the received measurements are analysed in order to diagnose the ocurrence of single phase high impedance faults on the system and send alarms that describe the current system situation. The first method, named PDSZ, is based on Phasor Measurement Units (PMUs) and besides detecting and locating the fault, can also classify it, showing which phaseis involved. The second one, the PQDSZ, is based on non-synchronized measurements and can not classify the fault. Both methods were implemented on laboratory and tested using real equipament and a Real Time Digital Simulator (RTDS), which allows a very precise evaluation of the proposed methods, emulating conditions very similar the real ones. The simulations prove the aplicability of the proposed methods and the results are analysed in order to show the effectiveness of the proposed methods.

Identiferoai:union.ndltd.org:IBICT/oai:hermes.cpd.ufjf.br:ufjf/4039
Date05 September 2016
CreatorsVianna, João Tito Almeida
ContributorsAraujo, Leandro Ramos de, Araujo, Débora Rosana Ribeiro Penido de, Pereira, Jose Luiz Rezende, Silva, Kleber Melo e
PublisherUniversidade Federal de Juiz de Fora (UFJF), Programa de Pós-graduação em Engenharia Elétrica, UFJF, Brasil, Faculdade de Engenharia
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguagePortuguese
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Sourcereponame:Repositório Institucional da UFJF, instname:Universidade Federal de Juiz de Fora, instacron:UFJF
Rightsinfo:eu-repo/semantics/openAccess

Page generated in 0.003 seconds