Controle de vazÃo de biogÃs com baixa pressÃo para produÃÃo descentralizada de eletricidade / Low pressure biogas flow control for decentralized electricity production

Banco do Nordeste do Brasil / A presente dissertaÃÃo propÃe a implementaÃÃo de um sistema de aquisiÃÃo de dados, controle e monitoramento de uma planta de geraÃÃo de energia elÃtrica acionada por biogÃs. Foi realizado o estudo experimental das estratÃgias de modelagem, identificaÃÃo e controle aplicado ao controle de vazÃo da planta de biogÃs do LaboratÃrio de Energias Alternativas - LEA da Universidade Federal do Cearà - UFC. Foi utilizado e testado para o controle de vazÃo de biogÃs o controlador PI paralelo, alÃm de realizar a comparaÃÃo com o controle existente (controle centrÃfugo) do conjunto motor/gerador. Para vericar a resposta do gerador movido a biogÃs, foi inserido uma carga correspondente a 60% da potÃncia nominal. O sistema proposto reduziu a intervenÃÃo humana no ajuste de vazÃo da vÃlvula de expansÃo. Os resultados demonstraram que o tempo de resposta para estabilidade apÃs a introduÃÃo do contolador PI ao controlador original permitiu a reduÃÃo do tempo de resposta para estabilidade em no mÃnimo 20% mostrando uma resposta
satisfatÃria e boa estabilidade para a transiÃÃo da gasolina para o biogÃs, com amplitude de 10 Hz e 8 segundos para estabilizaÃÃo do sistema sem carga. A aÃÃo foi considerada viÃvel para automatizar o processo de partida do conjunto motor/gerador. / The present dissertation proposes the implementation of a data acquisition system, control and monitoring of a electricity generation plant powered by biogas. The experimental study of the modelling strategies, identication
and control was done applied to ow control of the biogas plant of the Renewable Energy Laboratory - LEA at the Federal University of Cearà - UFC. To control the biogas ow a parallel PI controller was used and tested, and
the controller was used to perform the comparison with the existing control (centrifugal control) of the gen-set. To check the response of the gen-set powered by biogas, a load corresponding of 60% of the nominal power was used. The proposed system reduced the human intervention in ow setting
of the expansion valve. The results showed that the stability response time after the introduction of the PI controller to the original controller allowed the reduction of the response time for at least 20% showing a satisfactory
response and a stability for the transition from gasoline to biogas, with 10 Hz amplitude and 8 seconds for the system stabilization with load. This action was considered feasible to automate the process of starting up of the gen-set.

Identiferoai:union.ndltd.org:IBICT/oai:www.teses.ufc.br:4835
Date27 October 2011
CreatorsAndrà Pimentel Moreira
ContributorsPaulo CÃsar Marques de Carvalho
PublisherUniversidade Federal do CearÃ, Programa de PÃs-GraduaÃÃo em Engenharia ElÃtrica, UFC, BR
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguageEnglish
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis