Previous issue date: 2016-02-22 / Com a atual escassez de energia, alta demanda e aumento do custo da energia elétrica,
verifica-se que uma questão importante é a melhoria da eficiência dos sistemas de
climatização dentro de um padrão de eficiência certificado possibilita-se, assim, para uma
comparação real de qual é a melhor opção de layout e operação dos sistemas, já que os
sistemas de climatização são responsáveis por uma alta parcela do consumo energético.
O presente trabalho se propõe a comparar dois sistemas de refrigeração diferentes, usando
chiller de compressão de vapor, para a climatização de ambientes. Foram propostas
diferentes modalidades para a comparação em operações isoladas e ações combinadas.
Essas operações são avaliadas nos conceitos de edifícios verdes. Foi desenvolvido um
modelo matemático baseado nos princípios de conservação de massa e energia,
complementado por várias funções, de modo a determinar as propriedades termofísicas e
eficiências dos compressores. O modelo avalia a influência dos parâmetros operacionais
principais do sistema de refrigeração a água gelada operando em três configurações
diferentes. As equações do modelo foram resolvidas pelo programa EES (Engineering
Equation Solver). Os resultados mostraram que o sistema com compressão diferenciada
apresenta COP igual ao do sistema com chiller parafuso na faixa de 0 a 300 TRs, e um
COP superior em média de 9% na faixa de 400 a 800 TRs. / With the current energy shortages, high demand and rising cost of electricity, it turns out
that an important issue is the improvement of the air conditioning efficiency within a
standard of efficiency certificate for a real comparison of what is the better layout option
and operation of systems, as the HVAC systems account for a high share of energy
consumption. This study aims to compare two different cooling systems using vapor
compression chiller for air conditioning environments. They were different proposals
modalities for comparison in isolated and combined action operations. These transactions
are valued on the concepts of green buildings. A mathematical model was developed
based on the principles of conservation of mass and energy, supplemented with various
functions in order to determine the thermophysical properties and efficiencies of the
compressors. The model evaluates the influence of the main operating parameters of the
cold water cooling system operating in three different configurations. The model
equations were solved by EES program (Engineering Equation Solver). The results
showed that the system presents differentiated compression COP equal to the screw
chiller systems in the range from 0 to 300 RTs and a higher COP (average of 9%) in the
range of 400 to 800 TR.

Identiferoai:union.ndltd.org:IBICT/oai:repositorio.ufpe.br:123456789/19556
Date22 February 2016
CreatorsPEREIRA, Gutenberg da Silva
Contributorshttp://lattes.cnpq.br/9143770208338263, PRIMO, Ana Rosa Mendes, MOREIRA, José Roberto Simões
PublisherUniversidade Federal de Pernambuco, Programa de Pos Graduacao em Engenharia Mecanica, UFPE, Brasil
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguagePortuguese
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/doctoralThesis
Sourcereponame:Repositório Institucional da UFPE, instname:Universidade Federal de Pernambuco, instacron:UFPE
RightsAttribution-NonCommercial-NoDerivs 3.0 Brazil, http://creativecommons.org/licenses/by-nc-nd/3.0/br/, info:eu-repo/semantics/openAccess

Page generated in 0.0021 seconds