Psychrometric Testing Facility Restoration and Cooling Capacity Testing

The Psychrometric Testing Facility at the Riverside Energy Efficiency Laboratory at Texas AandM University has not been operational for several years. The goal of this project was to restore the testing facility to a fully operational condition for the purpose of supporting research and cooling capacity testing, with the latter following the appropriate standards.
Numerous changes were made to the coolant piping system, the data acquisition system, instrumentation, and temperature and humidity control to update and improve the facility. In addition, a computer program was developed and implemented that allows for flexible control of the facility’s conditions and collection of data while showing real time performance and refrigerant and psychrometric calculations. The current program flexibility, along with the proper combination of instrumentation, allows the Psychrometric Facility to operate with separate steady state environmental conditions in each room, according to, and meeting, the AHRI 210/240 standard.
Cooling capacity testing done on a split system residential unit was compared to the published AHRI rating to benchmark the state of the facility. Tested cooling capacity was about 3 percent below the published cooling capacity; tested EER was about 7 percent below the published EER; and finally, the calculated SEER based on the default degradation coefficient was about 10 percent below the published SEER. The difference in the calculated performance parameters to the published are expected due to unknown testing conditions used to calculate the published rating.

Identiferoai:union.ndltd.org:tamu.edu/oai:repository.tamu.edu:1969.1/ETD-TAMU-2010-08-8272
Date2010 August 1900
CreatorsCline, Vincent E.
Source SetsTexas A and M University
Languageen_US
Detected LanguageEnglish
TypeBook, Thesis, Electronic Thesis, text
Formatapplication/pdf

Page generated in 0.0018 seconds