Return to search

Estimação computacional dos esforços eletromecânicos em transformadores de potência no sistema CHESF.

Submitted by Gustavo Nascimento (gustavo.diniz@ufcg.edu.br) on 2018-02-06T14:28:39Z
No. of bitstreams: 1
EDUARDO JORGE CALHEIROS JUNIOR - DISSERTACAO PPGEE 2014.pdf: 3431884 bytes, checksum: 5d6e954510b9e7405666b81ef4f13f30 (MD5) / Made available in DSpace on 2018-02-06T14:28:39Z (GMT). No. of bitstreams: 1
EDUARDO JORGE CALHEIROS JUNIOR - DISSERTACAO PPGEE 2014.pdf: 3431884 bytes, checksum: 5d6e954510b9e7405666b81ef4f13f30 (MD5)
Previous issue date: 2014-06 / As análises de adequabilidade de equipamentos são indispensáveis para permitir que as
empresas do setor elétrico conheçam as condições em que os mesmos operam,
garantindo assim o desempenho dos ativos da empresa e sua disponibilidade no Sistema
Interligado Nacional. Dentre os equipamentos analisados, destacam-se os
transformadores de potência pelo seu alto custo e a sua importância para o sistema
elétrico. Grande parte das falhas em transformadores de potência é de origem dielétrica,
relacionadas com a danificação da isolação dos condutores devido às deformações
mecânicas ocasionadas pelas altas correntes de curto-circuito passantes nos
enrolamentos, reduzindo a vida útil do equipamento. A partir destas considerações,
propôs-se avaliar os esforços eletromecânicos internos a alguns transformadores de
potência presentes no sistema CHESF, por intermédio de simulações computacionais,
quando da ocorrência de curto-circuito trifásico. A metodologia para as simulações
consistiu em selecionar os transformadores a serem analisados e coletar as informações
técnicas necessárias fornecidas pelos fabricantes. Posteriormente foram determinadas as
condições sistêmicas às quais os transformadores estariam submetidos e obtidos os
níveis de curto-circuito resultantes, para então efetuar as simulações propriamente ditas.
Os resultados das simulações computacionais mostraram os esforços eletromecânicos
estimados em quatro transformadores de potência em operação no sistema elétrico da
CHESF, resultantes do efeito dinâmico da corrente de curto-circuito trifásico que
percorrem os enrolamentos do transformador, considerando diferentes configurações
sistêmicas. As conclusões das análises dos resultados indicaram possíveis casos de
superações de limites admissíveis e revelou a importância dos aspectos construtivos dos
transformadores na sua capacidade de suportar os esforços mecânicos causados por
curtos-circuitos. / Analysis of suitability of equipment are indispensable for the electric sector companies
meet the conditions in which they operate, thus ensuring the performance of the
company's assets and its availability in the National Interconnected System (Sistema
Interligado Nacional). The power transformers are included among the analyzed
equipment due to its high cost and importance for the electrical system. Most faults in
power transformers is of dielectric origin, related to insulation damage due to
mechanical deformations, caused by the high short-circuit currents in the windings,
reducing the life of the equipment. Then, it was proposed to evaluate the internal
electromechanical efforts to some power transformers present in the CHESF system,
through computer simulations, in the event of a three-phase short circuit. The
methodology for the simulations consisted to select the transformers to parse and collect
the necessary technical information provided by the manufacturers. Later, certain
systemic conditions in which the transformers would be subjected were defined, it was
obtained the resulting short circuit levels and then was performed the simulations
themselves. The results of the computer simulations showed the electromechanical
efforts estimated at four power transformers in operation in the CHESF electrical
system, resulting from the dynamic effect of three-phase short-circuit current that run
through the windings of the transformer, considering different systemic configurations.
The conclusions of the analysis results indicated possible cases of overruns of
permissible limits and reveal the importance of the transformers constructive aspects in
their ability to withstand the mechanical stress caused by short circuits.

Identiferoai:union.ndltd.org:IBICT/oai:localhost:riufcg/257
Date06 February 2018
CreatorsCALHEIROS JUNIOR, Eduardo Jorge.
ContributorsFERREIRA, Tarso Vilela., COSTA, Edson Guedes da.
PublisherUniversidade Federal de Campina Grande, PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA, UFCG, Brasil, Centro de Engenharia Elétrica e Informática - CEEI
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguageEnglish
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Sourcereponame:Biblioteca de Teses e Dissertações da UFCG, instname:Universidade Federal de Campina Grande, instacron:UFCG
Rightsinfo:eu-repo/semantics/openAccess

Page generated in 0.0029 seconds