Return to search

Field implementation of a transient voltage measurement facility using HV current transformers

Thesis (MScEng)--University of Stellenbosch, 2003. / ENGLISH ABSTRACT: The bandwidth of standard HV measurement devices such as capacitive voltage
transformers is too limited in order to measure wideband phenomena. This thesis is
concerned with the investigation into a non- intrusive HV transient voltage
measurement facility using standard substation HV current transformers (CI's)
configured in a transconductance topology. The sensing, summation and integration
of the CT capacitive earth currents are investigated. This thesis also reports on the
development of a optically isolated link using optical fibre for signal transfer and a
computer based data acquisition system. / AFRIKAANSE OPSOMMING: Standaard hoogspannings (HS) meettoerusting soos kapasitiewe spannmgs
transformators het beperkte bandwydte vir die meet van wyeband verskynsels.
Hierdie tesis handel oor die implementering van 'n HS meetstelsel wat op meinbrekende
wyse oorgangsverskynsels meet deur middel van HS
stroomtransformators wat in 'n transkonduktansie topologie gekonfigureer is. Die
meet, sommasie en integrasie van kapasitoewe grondstrome word ondersoek. Hierdie
tesis doen ook verslag aangaande die ontwikkeling van 'n optiese geisoleerde
koppelvlak wat gebruik word vir seinoordrag en 'n rekenaar gebasseerde data
versamelaar. / pdv201406

Identiferoai:union.ndltd.org:netd.ac.za/oai:union.ndltd.org:sun/oai:scholar.sun.ac.za:10019.1/53426
Date12 1900
CreatorsSiebrits, F. B.(Francois Bart)
ContributorsVermeulen, H. J., Stellenbosch University. Faculty of Engineering. Dept. of Electrical and Electronic Engineering.
PublisherStellenbosch : Stellenbosch University
Source SetsSouth African National ETD Portal
Languageen_ZA
Detected LanguageEnglish
TypeThesis
Format160 leaves : ill.
RightsStellenbosch University

Page generated in 0.0017 seconds