Return to search

Direct digital control algorithm for low power nuclear reactors

A direct digital control algorithm for low power reactors is proposed using logarithmic power level as input. The logarithmic power levels allow the use of fixed point arithmic resulting in faster calculation speeds than are obtainable with algorithms using floating point arithmetic. A stability analysis for various sampled data hold types is shown to have a 25% safety margin. A time optimal control sequence for power increases is derived using switch points. The switch points are determined using simulation techniques, eliminating the use of complex and approximate calculations. A practical demand level controller is developed using machine language programming to minimize the delay from the sampling of the neutron power to the output of control action. The controller is tested with digital and analog simulations of a thermal reactor showing that a successful, near time-optimal, control algorithm with general applications to low power reactors has been developed. / Applied Science, Faculty of / Electrical and Computer Engineering, Department of / Graduate

Identiferoai:union.ndltd.org:UBC/oai:circle.library.ubc.ca:2429/33068
Date January 1973
CreatorsHarvey, Geoffrey Alan
PublisherUniversity of British Columbia
Source SetsUniversity of British Columbia
LanguageEnglish
Detected LanguageEnglish
TypeText, Thesis/Dissertation
RightsFor non-commercial purposes only, such as research, private study and education. Additional conditions apply, see Terms of Use https://open.library.ubc.ca/terms_of_use.

Page generated in 0.0022 seconds