Return to search

Non-destructive testing of capless porcelain line post insulators to detect internal defects

Thesis (MScEng)--University of Stellenbosch, 2003. / ENGLISH ABSTRACT: This project relates to the unexplained failure of 33kV porcelain line post insulators in
ESKOM's Southern Region. An initial investigation suggested that the failures could
probably be due to a combination of internal manufacturing flaws and the effects of
lightning. The failures all occurred in insulators based on a new design that uses a
metal spindle for mechanical attachment to a power line structure embedded in the
insulator base.
This thesis investigates the non-destructive detection of internal flaws in porcelain
line post insulators. The research was structured as follows:
• The examination of the manufacturing process and materials used to determine
the cause, location and nature of internal flaws.
• An electrical field simulation study to verify whether a void in the sulphur
cement will experience discharge activity when exposed to systeni nominal
voltage or lightning potential.
• The identification of non-destructive techniques (NDT) that are potentially
viable for determining the presence of insulator internal flaws.
• The design of NDT experiments for X-ray, partial discharge (PD) detection
and ultrasonic testing. These experiments were evaluated for their
effectiveness in determining the presence of internal flaws and their usefulness
as a quality control measure in the insulator manufacturing process.
The main findings are:
The major cause of insulator internal flaws is the fast setting sulphur cement used
for cementing the metal spindle (mechanical attachment) to the porcelain body of
the insulator.
The field simulation study shows that a discharge in a 3mm diameter spherical
void on the insulator's axis of symmetry will occur if the insulator is exposed to
lightning potential.
High energy X-raying is an effective technique for exposing the location, nature,
size and number of flaws in the insulator, but is impractical due to the high Xraying
cost and over-utilisation of the only high energy X-ray facility in the
RSA. The PD experiment was effective in revealing the presence of internal flaws, but
the location, nature, size and number of flaws cannot be determined. The
experiment is time consuming and is therefore not suitable for quality control
in the insulator manufacturing process.
A preliminary investigation into the suitability of ultrasonic testing techniques
encountered major technical difficulties. Further investigation into the use of
ultrasonic 3D imaging techniques is recommended. / AFRIKAANSE OPSOMMING: Hierdie projek hou verband met die onverklaarbare faling van 33kV porselein staaftipe
isolators in ESKOM se Suidelike Streek. 'n Aanvanklike ondersoek het daarop
gedui dat die falings veroorsaak is deur 'n kombinasie van interne vervaardigingsfoute
en die effek van weerlig. Die falings het almal plaasgeving op isolators waarvan
die vashegtingsbout direk in die porselein versink is.
Die doel van hierdie navorsingsprojek is om nie-vernietigende toetsmetodes (NVT) te
ondersoek, teneinde interne foute in die tipe isolators op te spoor. Die tesis is soos
volg gestruktureer:
• Die ondersoek van die vervaardigingsproses en die materiale wat gebruik
word, ten einde die oorsaak, posisie en aard van hierdie foute vas te stel.
• 'n Simulasie van die elektriese veld om vas te stelof 'n holte in die swaelsement
ontladings salondervind onder die invloed van nominale spanning en
weerlig.
• Die indentifisering van nie-vernietignde toetsmetodes wat gebruik kan word
om die teenwoordigheid van interne foute te bepaal.
• Die ontwerp van NVT eksperimente vir X-straal, gedeeltelike ontlading
("PD") deteksie en ultrasoniese toetsing. Hierdie eksperimente is geëvalueer
om hul effektiwiteit om die teenwoordigheid van interne foute vas te stel,
asook hul nuttigheid as 'n kwaliteitsbeheermaatreël in die
iso latorvervaardigingsproses.
Die hoofbevindinge is:
Die hoofoorsaak van die interne foute is die vinnig-stollende swael-sement
wat gebruik word om die metaalinsetsel aan die porselein te heg.
Die veldsimulasies het getoon dat 'n ontlading in 'n 3mm sferiese holte op die
isolator se simmetrie-as sal plaasvind as die isolator aan weerligpotensiaal
onderwerp word.
Hoë-energie-X-strale is 'n effektiewe tegniek om die posisie, aard, grootte en
aantal foute in die isolator vas te stel. Dit is egter onprakties as gevolg van die hoë koste en oorbenutting van die enigste hoë-energie-X-straal-fasiliteit in die
RSA.
Die ontladingsdeteksie eksperiment was effektief om die teenwoordigheid van
interne foute aan te dui, maar die posisie, aard; grootte en getal foute kan nie
bepaal word nie. Die eksperiment is tydrowend en is daarom nie geskik vir
kwaliteitsbeheer van die isolatorvervaardigingsproses nie.
'n Voorlopige ondersoek na die geskiktheid van ultrasoniese toetsmetodes het
groot tegniese stuikelblokke opgelewer. Verdere ondersoek van die gebruik
van ultrasoniese 3D-beeldtegnieke word aanbeveel.

Identiferoai:union.ndltd.org:netd.ac.za/oai:union.ndltd.org:sun/oai:scholar.sun.ac.za:10019.1/53525
Date12 1900
CreatorsBorrill, Leslie (Leslie David)
ContributorsHoltzhausen, J. P., Vosloo, W. L., Stellenbosch University. Faculty of Engineering. Dept. of Electrical and Electronic Engineering.
PublisherStellenbosch : Stellenbosch University
Source SetsSouth African National ETD Portal
Languageen_ZA
Detected LanguageUnknown
TypeThesis
Format114 p. : ill.
RightsStellenbosch University

Page generated in 0.0149 seconds