Return to search

Religamento monopolar adaptativo rapido baseado na assinatura harmonica da tensão de arco secundario / Fast adaptive single-phase autoreclosing based on secondary arc voltage harmonic signature

Orientador: Maria Cristina Dias Tavares / Dissertação (mestrado) - Universidade Estadual de Campinas, Faculdade de Engenharia Eletrica e de Computação / Made available in DSpace on 2018-08-13T12:17:57Z (GMT). No. of bitstreams: 1
Montanari_AllanAlves_M.pdf: 7585929 bytes, checksum: 4c00ba94f40e488cc4da50c4089e8630 (MD5)
Previous issue date: 2009 / Resumo: Este trabalho apresenta um esquema de religamento monopolar adaptativo rápido para
otimizar o tempo compreendido entre a abertura e o religamento da fase sob falta. A proteção
adaptativa recompõe rapidamente o sistema de transmissão de energia elétrica, minimizando a
probabilidade de propagação de perturbações severas no sistema. O método é fundamentado na análise de dados de ensaios de arco secundário gerados e monitorados numa estrutura de testes construída em campo, composta por um trecho real de linha de transmissão (três torres e dois vãos). Analisou-se o conteúdo harmônico da tensão e da corrente de arco secundário através da aplicação da Transformada de Fourier Janelada. Tais análises viabilizaram a realização de um tratamento estatístico para a caracterização da assinatura harmônica de arco secundário.
Simulações de faltas monofásicas foram realizadas utilizando dados provenientes dos
Ensaios de arco secundário. Desenvolveu-se um algoritmo baseado nas características
Harmônicas da tensão da fase sob falta, calculadas através do deslocamento de uma janela de
tempo sobre os sinais analisados (Transformada de Fourier Janelada). O algoritmo determina
a existência do arco secundário e fornece informações a respeito do instante no qual o
religamento pode ser realizado com sucesso. O método apresenta também um mecanismo
para a detecção da característica permanente ou transitória da falta. / Abstract: This work presents a fast adaptive single-phase autorec1osingseheme to optimize the
period between the tripping operation and the rec10sure of the faulted phase breakers. The
adaptive proteetion quiekly reeomposes the eleetric power transmission, minimizing the
probability of severe damages propagation in the system.
The method is based on the analysis of secondary are field tests data that were
generated and monitored in an infra-structure which consists of a real transmission line
section (three towers and two spans). The harmonic content of the secondary are voltage and
eurrent was analyzed by the application of Short Time Discrete Fourier Transform. Such
analysis made it possible to implement a statistical approach in order to obtain the secondary
are harmonic signature.
Single-phase faults computer simulations were performed using the data obtained from
the secondary are tests. It was developed an algorithm based on the voltage harmonic content
of the faulted phase, which was ea1culated by shifting a window on the analyzed signals
(Short Time Discrete Fourier Transform). The algorithm determines the secondary are
existence and provides information in order to suceessfully rec10se the circuit breaker. The
method also presents a control mechanism responsible for identifying whether the fault is a
permanent one or a transient fault. / Mestrado / Energia Eletrica / Mestre em Engenharia Elétrica

Identiferoai:union.ndltd.org:IBICT/oai:repositorio.unicamp.br:REPOSIP/259603
Date13 August 2018
CreatorsMontanari, Allan Alves
ContributorsUNIVERSIDADE ESTADUAL DE CAMPINAS, Tavares, Maria Cristina Dias, 1962-, Moreira, Fernando Augusto, Violaro, Fabio
Publisher[s.n.], Universidade Estadual de Campinas. Faculdade de Engenharia Elétrica e de Computação, Programa de Pós-Graduação em Engenharia Elétrica
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguagePortuguese
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Format144 p. : il., application/pdf
Sourcereponame:Repositório Institucional da Unicamp, instname:Universidade Estadual de Campinas, instacron:UNICAMP
Rightsinfo:eu-repo/semantics/openAccess

Page generated in 0.0026 seconds