Development of A Heat Pump Heater System with Fuzzy Logic Control

With the continued development of economy, the energy demand increases continually . The industry is interested in evaluating the technology of heat pump, with applications mostly for water heater. This thesis analyzes and compares the heating efficiency of electric heater, gas heater and heat pump heater . A fuzzy theory is employed to the developed heating algorithm to raise the efficiency of the heat pump heater and suppress the unnecessary heating at the high temperature.
According to the experiment, the heat pump heater could reach 60% energy saving while gas heater could attain 23% in comparison with the electric heater under the same temperature, The system could work all year around and can provide users with water at a proper temperature. In the winter, COP of heat pump heater could reache 2.1~2.5 while in the summer around 2.61~2.95. The energy saving is obvious.