This thesis introduces a novel online set-point modulation (SPM) technique that employs fuzzy logic to adjust the timing and magnitude of control system set-points. After first applying fuzzy logic-enabled SPM to underdamped second order systems for testing purposes, the new scheme is then applied to an electromagnetic transient simulation model of Manitoba Hydro’s existing Ponton SVC system, and the results are then compared to the original SVC system that uses traditional control approaches. Conclusions show that fuzzy logic-based SPM improves the controlled voltage’s transient overshoot response to changes in the voltage set-point.
Identifer | oai:union.ndltd.org:LACETR/oai:collectionscanada.gc.ca:MWU.1993/18343 |
Date | 04 April 2013 |
Creators | Howell, Steven |
Contributors | Filizadeh, Shaahin (Electrical and Computer Engineering), Gole, Ani (Electrical and Computer Engineering) Ormiston, Scott (Mechanical and Manufacturing Engineering) |
Source Sets | Library and Archives Canada ETDs Repository / Centre d'archives des thèses électroniques de Bibliothèque et Archives Canada |
Detected Language | English |