Return to search

Mathematical Model and Performance Analysis of a Liquid Desiccant Dehumidification Tower

A finite difference model simulating a liquid desiccant dehumidification tower with lithium chloride as the desiccant solution has been developed. The model determines the packing height needed for a condensation rate. Comparisons with experimental data illustrates that the model produces valid results. Air and desiccant solution temperatures within the dehumidification tower show that a temperature increase is experienced for both the air and desiccant solution from their respective entrances and exits from the tower. Increasing the air mass velocity or the amount of moisture removed from the air supply causes an increase in packing height. Increasing the desiccant mass velocity decreases the packing height.

Identiferoai:union.ndltd.org:MSSTATE/oai:scholarsjunction.msstate.edu:td-6316
Date06 August 2005
CreatorsLong, Mark Alan
PublisherScholars Junction
Source SetsMississippi State University
Detected LanguageEnglish
Typetext
Formatapplication/pdf
SourceTheses and Dissertations

Page generated in 0.0013 seconds