Return to search

Saturated Reluctance Identification of high voltage Induction Motor and Estimation of Induction Motor/Generator Effect

Saturated reluctance identification of induction motor can be implemented by additional sensor, finite-element method, spectrum analysis, or step voltage test in the research accounts. But it is not easy to implement in the field evaluation when we need to build up the power system model, because of the factory parameter absent, expansive cost, extra sensor installation, or variable voltage and frequency.
To be concerned with practicality, it is always inconvenient to build up simulation for the end user. The linear model of motor can¡¦t provide the simulation answer accurately when models run into saturated during power system transient. Accordingly, this thesis discuss two paragraphs as following:
First, This thesis introduces a simple and practical method base on the manufacturer instruction manual to estimate the saturated reluctance of high / medium voltage induction motor in modeling. And we can analyze the motor dynamic characteristic by using the induction motor d-q-0 model directly, in place of traditional mathematical power equations.
Moreover, we can evaluate the motor-generation reaction because of the rotor inertia due to loss of voltage. To identify the discrepancy between numeral situations what the line capacitor existed or not. Besides, we can explain the existing voltage after power system break down by comparing the simulation result with recorder chart.

Identiferoai:union.ndltd.org:NSYSU/oai:NSYSU:etd-0610103-224614
Date10 June 2003
CreatorsLee, Ching-Lin
ContributorsCHWEN CHYN, Whei-Min Lin, Ta-Peng Tsao
PublisherNSYSU
Source SetsNSYSU Electronic Thesis and Dissertation Archive
LanguageCholon