Return to search

Ochrany při zemních spojeních / Earth Faults Protections

The thesis deals with wattmetric and conductance principle of faulted feeder detection in medium voltage compensated distribution networks. These principles are analysed and tested with particular emphasis on high impedance earth faults. The first part of testing utilizes data about state of the system with earth fault, which was determined by designed static model of earth fault. The testing in the second part utilizes real records of high impedance earth faults. In both parts the wattmetric and conductance protections was presented on protective relays ABB REF 615, ABB REM 543 and Protection&Consulting RYo by means of unit OMICRON CMC 256plus. As a major result of performed tests are records of detection of particular earth faults. Based on these records it could be concluded, that functionality of protections is substantially dependent on magnitude of zero sequence voltage. Furthermore the wattmetric protections are dependent on fault resistance as well.

Identiferoai:union.ndltd.org:nusl.cz/oai:invenio.nusl.cz:221169
Date January 2015
CreatorsOstruška, Jan
ContributorsTopolánek, David, Orságová, Jaroslava
PublisherVysoké učení technické v Brně. Fakulta elektrotechniky a komunikačních technologií
Source SetsCzech ETDs
LanguageCzech
Detected LanguageEnglish
Typeinfo:eu-repo/semantics/masterThesis
Rightsinfo:eu-repo/semantics/restrictedAccess