Comportamento da fadiga de um condutor de linha aérea / Fatigue behavior of an overhead line conductor

Dissertação (mestrado)—Universidade de Brasília, Faculdade de Tecnologia, Departamento de Engenharia Civil e Ambiental, 2018. / Submitted by Fabiana Santos (fabianacamargo@bce.unb.br) on 2018-11-07T18:55:11Z
No. of bitstreams: 1
2018_JohnGibbonsPrahl.pdf: 4233145 bytes, checksum: 91365913d5bf7cac24c5c88031a443fa (MD5) / Approved for entry into archive by Fabiana Santos (fabianacamargo@bce.unb.br) on 2018-11-12T17:47:24Z (GMT) No. of bitstreams: 1
2018_JohnGibbonsPrahl.pdf: 4233145 bytes, checksum: 91365913d5bf7cac24c5c88031a443fa (MD5) / Made available in DSpace on 2018-11-12T17:47:24Z (GMT). No. of bitstreams: 1
2018_JohnGibbonsPrahl.pdf: 4233145 bytes, checksum: 91365913d5bf7cac24c5c88031a443fa (MD5)
Previous issue date: 2018-11-12 / As linhas de transmissão de eletricidade estão sujeitas a vibrações eólicas, que podem levar à fadiga dos condutores nas regiões próximas aos grampos de suspensão ou de ancoragem ou mesmo nas regiões próximas aos amortecedores de vibrações. Com o propósito de obter uma melhor compreensão dos mecanismos das falhas desses condutores pela fadiga, a empresa Ontario Hydro desenvolveu um método para a determinação dos limites das vibrações, realizado no campo para vários tipos de condutores e utilizado com sucesso por mais de sessenta anos. O presente trabalho consiste em apresentar a pesquisa realizada pela empresa Manaus Transmissora de Energia, que utilizou o método desenvolvido pela empresa Ontario Hydro para a determinação da vida útil do cabo condutor CAL em liga de alumínio de 1055 kcmil montado em um espaçador amortecedor para quatro feixes utilizado na linha de transmissão em 500 kV entre as cidades de Oriximiná (PA) e Lechuga (AM). Os procedimentos para o teste foram desenvolvidos pela empresa Ontario Hydro e normatizados por EPRI (2009), IEEE (1966) e CIGRÉ (1995). / Electrical transmission lines are always subject to aeolian vibrations that may lead to the failure of overhead conductors by fatigue in regions close to suspension or anchoring clamps or even in regions close to vibration dampers. In order to obtain a better understanding of the mechanism of fatigue failure of several conductors, the Company Ontario Hydro has developed a method for determining the vibration limits, performed in the field and used for more than sixty years. The present work consists in presenting the research carried out by the Company Manaus Transmissora de Energia, which used the method developed by Ontario Hydro for the determination of the useful life of the conductor CAL in aluminum alloy of 1055 kcmil. The conductor was mounted on a four-bundle spacer-damper used in the 500 kV transmission line between the cities of Oriximiná (PA) and Lechuga (AM). The test procedures were developed by Ontario Hydro and standardized by EPRI (2009), IEEE (1966) and CIGRÉ (1995).

Identiferoai:union.ndltd.org:IBICT/oai:repositorio.unb.br:10482/33032
Date27 April 2018
CreatorsPrahl, John Gibbons
ContributorsBrito, José Luís Vital de
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguagePortuguese
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Sourcereponame:Repositório Institucional da UnB, instname:Universidade de Brasília, instacron:UNB
RightsA concessão da licença deste item refere-se ao termo de autorização impresso assinado pelo autor com as seguintes condições: Na qualidade de titular dos direitos de autor da publicação, autorizo a Universidade de Brasília e o IBICT a disponibilizar por meio dos sites www.bce.unb.br, www.ibict.br, http://hercules.vtls.com/cgi-bin/ndltd/chameleon?lng=pt&skin=ndltd sem ressarcimento dos direitos autorais, de acordo com a Lei nº 9610/98, o texto integral da obra disponibilizada, conforme permissões assinaladas, para fins de leitura, impressão e/ou download, a título de divulgação da produção científica brasileira, a partir desta data., info:eu-repo/semantics/openAccess

Page generated in 0.0028 seconds