During the construction of a chemical processing plant, a polyphosphate product was selected for use as a corrosion inhibitor in the open recirculating cooling tower system. After several months of operation, problems in the system made evident the fact that polyphosphate as a corrosion inhibitor was not acceptable. An organic corrosion inhibitor was substituted for the phosphate, resulting in improved corrosion protection and the elimination of phosphate fouling.
Identifer | oai:union.ndltd.org:ucf.edu/oai:stars.library.ucf.edu:rtd-1480 |
Date | 01 July 1980 |
Creators | Everson, Lawrence P. |
Publisher | University of Central Florida |
Source Sets | University of Central Florida |
Language | English |
Detected Language | English |
Type | text |
Format | application/pdf |
Source | Retrospective Theses and Dissertations |
Rights | Public Domain |
Page generated in 0.0019 seconds