The purpose of this investigation is to find out suitability of the solar chimney natural ventilation system in a Zero Energy Lab located at the University of North Texas campus, to figure out performance of the solar chimney. Reduction in the heating and ventilation and air conditioning energy consumption of the house has been also analyzed. The parameters which are considered for investigation are volumetric flow rate of outlet of chimney, the absorber wall temperature and glass wall temperatures. ANSYS FLUENT 14.0 has been employed for the 3-D modeling of the solar chimney. The dimensions of the solar chimney are 14’2” X 7’4” X 6’11”. The flow inside solar chimney is found to be laminar and the simulation results show that maximum outlet volumetric flow rate of about 0.12m3/s or 432 cfm is possible from chimney. The experimental velocity of chimney was found to be 0.21 m/s. Density Boussinesq approximation is considered for the modeling. Velocity and temperature sensors have been installed at inlet and outlet of the chimney in order to validate the modeling results. It is found that based on simulated volumetric flow rate that cooling load of 9.29 kwh can be saved and fan power of 7.85 Watts can be saved.
Identifer | oai:union.ndltd.org:unt.edu/info:ark/67531/metadc499996 |
Date | 08 1900 |
Creators | Talele, Suraj H. |
Contributors | Tao, Yong, Rayeganr, Rambod, Burzo, Mihai |
Publisher | University of North Texas |
Source Sets | University of North Texas |
Language | English |
Detected Language | English |
Type | Thesis or Dissertation |
Format | Text |
Rights | Public, Talele, Suraj H., Copyright, Copyright is held by the author, unless otherwise noted. All rights Reserved. |
Page generated in 0.0024 seconds