Return to search

Air distribution from ventilation ducts

A wooden, perforated, uniform cross-section duct was examined to determine the optimum levels of aperture ratio and fan speed with respect to uniformity of discharge. The optimum aperture ratio for the 8.54 m long duct was 1.0 with a uniformity coefficient of 90.28%. The fan speed had little effect on the uniformity of discharge. The friction factor was experimentally determined to be 0.048 for a non-perforated duct and this value was assumed to be the same for a perforated duct of similar construction. A kinetic energy correction factor was used to analyze the flow in the duct. Values for this correction factor were determined from experimental data. Values of the coefficient of discharge and the total duct energy were calculated. A mathematical model was proposed based on the conservation of momentum and the Bernoulli's equation. The model responded favourably and predicted the duct velocity nearly perfectly and slightly underestimated the total duct energy.

Identiferoai:union.ndltd.org:LACETR/oai:collectionscanada.gc.ca:QMM.59655
Date January 1990
CreatorsMacKinnon, Ian R. (Ian Roderick), 1964-
PublisherMcGill University
Source SetsLibrary and Archives Canada ETDs Repository / Centre d'archives des thèses électroniques de Bibliothèque et Archives Canada
LanguageEnglish
Detected LanguageEnglish
TypeElectronic Thesis or Dissertation
Formatapplication/pdf
CoverageMaster of Science (Department of Agricultural Engineering.)
RightsAll items in eScholarship@McGill are protected by copyright with all rights reserved unless otherwise indicated.
Relationalephsysno: 001116852, proquestno: AAIMM66402, Theses scanned by UMI/ProQuest.

Page generated in 0.0022 seconds