Previous issue date: 2015-05-15 / Eletronorte - Centrais Elétricas do Norte do Brasil S/A / Convencionalmente a monitoração das condições de funcionamento de uma linha de
transmissão de energia e' realizada através de inspeções periódicas ao longo desta linha. Esta
monitoração permite a manutenção corretiva pela constatação de falhas durante a inspeção.
Uma manutenção mais eficiente deve empregar técnicas preditivas que se caracterizam pela
monitoração em tempo real. As técnicas preditivas verificam o estado de funcionamento
empregando modelos de funcionamento normal para a detecção de falhas e modelos de falha
para a determinação e o diagnóstico a ser empregado no PDI (Fault Detection and Isolation).
Por isso foi desenvolvido um modelo matemático adequado para ser aplicado em manutenção
preditiva de trechos de linhas de transmissão a baixo custo, sem necessidade de sensores
distribuídos ao longo da linha. Este modelo permite o emprego da metodologia de detecção de
falhas (PDI) através do acompanhamento da corrente de fuga de linhas de transmissão. 0
emprego do modelo permite também a obtenção de um novo indicador da condição normal e
anormal de funcionamento de uma linha de transmissão que e' a capacitância das freqüências
harmônicas. A metodologia foi validada através de medidas obtidas em um trecho de linha de
transmissão, e a utilização de uma rede neural artificial desenvolvida para a classificação do
estado de funcionamento da Linha de Transmissão. / Conventionally monitoring operating conditions of a power transmission line is accomplished by periodic inspections along this line. This monitoring allows corrective maintenance by
finding faults during the inspection. But in more efficient maintenance, predictive techniques
that are characterized by real-time monitoring should be employed. The predictive techniques
verify the operating status using normal function models for fault detection and fault models
for the diagnosis to be employed in PDI (Fault Detection and Isolation). So, we developed a
mathematical model appropriate for application to predictive maintenance of transmission line
segments at low cost, without the need for sensors distributed along the line. This model allows
the use of the methodology for detecting faults (PDI) by monitoring the leaka ge current of
transmission lines. The use of the model also allows obtaining a new indicator of the condition
of normal and abnormal functioning of a transmission line, which is the capacitance of
harmonic frequencies. The model was validated through measurements obtained on a section
of transmission line, by means of an artificial neural network.
Identifer | oai:union.ndltd.org:IBICT/oai:repositorio.ufpa.br:2011/7413 |
Date | 15 May 2015 |
Creators | NEGRÃO, Martin Max Luis de Castro |
Contributors | VIEIRA JÚNIOR, Petrônio, BARREIROS, José Augusto Lima |
Publisher | Universidade Federal do Pará, Programa de Pós-Graduação em Engenharia Elétrica, UFPA, Brasil, Instituto de Tecnologia |
Source Sets | IBICT Brazilian ETDs |
Language | Portuguese |
Detected Language | Portuguese |
Type | info:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/doctoralThesis |
Source | reponame:Repositório Institucional da UFPA, instname:Universidade Federal do Pará, instacron:UFPA |
Rights | info:eu-repo/semantics/openAccess |
Page generated in 0.0024 seconds