This thesis studies the operating characteristics of lead acid batteries with the intermittent discharging current. Rest time is added periodically on purpose during the battery discharging to observe its impact on the releasable capacity. From the experimental results that take the frequency and the duty-ratio as two variables, batteries with the intermittent discharging at high frequencies or low duty ratios can release more capacity. The results also indicate that the depth of discharge (DOD) affects the intermittent discharging. More capacity is released while approaching the end of the discharging, whereas no clear difference is found in the beginning. Last but not least, the average current is proved experimentally to play a significant role in current discharging. With the same average current, the maximum capacity obtained from the intermittent current discharging is close to that from the constant current discharging.
Identifer | oai:union.ndltd.org:NSYSU/oai:NSYSU:etd-0708107-221427 |
Date | 08 July 2007 |
Creators | Lin, Yu-Chao |
Contributors | Jiann-Fuh Chen, Ming-Tsung Tsai, Chih-Chiang Hua, Chin-Sien Moo, Jia-You Lee |
Publisher | NSYSU |
Source Sets | NSYSU Electronic Thesis and Dissertation Archive |
Language | Cholon |
Detected Language | English |
Type | text |
Format | application/pdf |
Source | http://etd.lib.nsysu.edu.tw/ETD-db/ETD-search/view_etd?URN=etd-0708107-221427 |
Rights | unrestricted, Copyright information available at source archive |