Return to search

The prediction and control of transients in thyristor valves

This thesis describes an investigation of methods by which both repetitive and non-repetitive electrical transients in an HVDC converter station may be controlled for minimum overall cost. Several methods of inrush control are proposed and studied. The preferred method, whose development is reported in this thesis, would utilize two magnetic materials, one of which is assumed to be lossless and the other has controlled eddy-current losses. Mathematical studies are performed to assess the optimum characteristics of these materials, such that inrush current is suitably controlled for a minimum saturation flux requirement. Subsequent evaluation of the cost of hardware and capitalized losses of the proposed inrush control, indicate that a cost reduction of approximately 50% is achieved, in comparison with the inrush control hardware for the Sellindge converter station. Further mathematical studies are carried out to prove the adequacy of the proposed inrush control characteristics for controlling voltage and current transients during both repetitive and non-repetitive operating conditions. The results of these proving studies indicate that no change in the proposed characteristics is required to ensure that integrity of the thyristors is maintained.

Identiferoai:union.ndltd.org:bl.uk/oai:ethos.bl.uk:545252
Date January 1985
CreatorsBarnes, M. J.
PublisherAston University
Source SetsEthos UK
Detected LanguageEnglish
TypeElectronic Thesis or Dissertation
Sourcehttp://publications.aston.ac.uk/15140/

Page generated in 0.0013 seconds