Return to search

Contribuições ao estudo de recomposição fluente de sistemas elétricos de potência / Contributions to study of electrical power systems fluent restoration

Submitted by Renata Lopes (renatasil82@gmail.com) on 2016-06-09T11:56:03Z
No. of bitstreams: 1
wesleyperes.pdf: 1629298 bytes, checksum: 979f44672c05a9876154ebaff4efaf74 (MD5) / Approved for entry into archive by Adriana Oliveira (adriana.oliveira@ufjf.edu.br) on 2016-07-13T13:30:59Z (GMT) No. of bitstreams: 1
wesleyperes.pdf: 1629298 bytes, checksum: 979f44672c05a9876154ebaff4efaf74 (MD5) / Made available in DSpace on 2016-07-13T13:30:59Z (GMT). No. of bitstreams: 1
wesleyperes.pdf: 1629298 bytes, checksum: 979f44672c05a9876154ebaff4efaf74 (MD5)
Previous issue date: 2012-03-05 / Este trabalho apresenta uma metodologia baseada em Fluxo de Potência Ótimo (FPO) e Análise de Sensibilidade para a definição da configuração mínima de rede necessária para garantir, com segurança, o processo de recomposição fluente de corredores radiais de transmissão. Nos instantes iniciais de recomposição, devido à baixa capacidade de geração que o sistema se encontra, uma estratégia importante consiste em elevar a Capacidade de Curto Circuito das barras. Neste sentido, a metodologia proposta baseia-se na incorporação, na função objetivo do FPO, da maximização da potência de curto circuito das barras. Para tanto, uma Análise de Sensibilidade é realizada a cada iteração do processo iterativo para determinar os fatores de ponderação de alocação associados à impedância equivalente permitindo a inclusão no FPO da maximização da potência de curto circuito das barras. Na metodologia proposta os reatores que mais reduzirem a impedância receberão menores fatores de ponderação de alocação. Adicionalmente, o FPO contempla a modelagem das máquinas síncronas, curva de capabilidade e o estudo de cada cenário de recomposição em regime permanente, pré e pós rejeição de carga. O programa desenvolvido em MATLAB é utilizado para a simulação de corredores de recomposição fluente do sistema elétrico brasileiro. Os resultados obtidos apontam para uma ferramenta eficaz ao estudo de recomposição fluente. / This work presents a methodology based on Optimal Power Flow (OPF) and Sensitivity Analysis to define a minimum network configuration for a power system fluent restoration taking security issues into account. At this early restoration stage, the system has low Short-Circuit Capacity due to the low generation capacity. An important strategy is to increase the Short Circuit Capacity at this operation stage through search network configurations with low bus equivalent impedance. In this work, the Short-Circuit Capacity is incorporated in the objective function of the OPF formulation by using sensitivity analysis which yields lowest allocation factors for more suitable reactors to reduce the equivalents impedances. The proposed OPF takes into account the synchronous machine model, the capability curves and the set of overvoltage critical restoration scenarios following load rejection. The restoration scenarios are represented at steady state prior and after load rejection. The computational tool is developed in the MATLAB platform and it is used to conduct case studies for fluent restoration branches of Brazilian Electric System. The results show that the proposed methodology is effective.

Identiferoai:union.ndltd.org:IBICT/oai:hermes.cpd.ufjf.br:ufjf/1784
Date05 March 2012
CreatorsPeres, Wesley
ContributorsOliveira, Edimar José de, Martins, Nelson, Pereira, Jose Luiz Rezende, Passos Filho, João Alberto, Oliveira, Leonardo Willer de
PublisherUniversidade Federal de Juiz de Fora, Programa de Pós-graduação em Engenharia Elétrica, UFJF, Brasil, Faculdade de Engenharia
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguagePortuguese
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Sourcereponame:Repositório Institucional da UFJF, instname:Universidade Federal de Juiz de Fora, instacron:UFJF
Rightsinfo:eu-repo/semantics/openAccess

Page generated in 0.0022 seconds