Structural mechanics and resistance of concrete structures in the event of a hydrogen explosion in nuclear powerplants

This thesis deals with the problem of hydrogen explosions in nuclear power plants, and evaluates if the reactor hall is to be seen as a safety barrier for such events. Today, the reactor hall is not seen as a safety barrier that is able to withstand an internal explosion. In the analysis Abaqus was used for the FEM calculations, where a main scenario of a wall subjected to a hydrogen explosion was used. In conclusion, the results showed that a reactor hall with the assumed dimensions cannot be seen as a safety barrier, since the deformation after a hydrogen explosion near the LEL was too great. However, it is also concluded that with increased wall and rebar dimensions it is possible to construct a wall of this kind that fulfills the requirements of a safety barrier.

Identiferoai:union.ndltd.org:UPSALLA1/oai:DiVA.org:ltu-69823
Date January 2018
CreatorsBjälke, Victor
PublisherLuleå tekniska universitet, Byggkonstruktion och brand
Source SetsDiVA Archive at Upsalla University
LanguageEnglish
Detected LanguageEnglish
TypeStudent thesis, info:eu-repo/semantics/bachelorThesis, text
Formatapplication/pdf
Rightsinfo:eu-repo/semantics/openAccess