The performance of a combined vapor-compression cycle/ORC is evaluated using waste-heat from a diesel generator. A flat plate microchannel heat exchanger is employed to provide energy exchange between the diesel exhaust stream and an oil loop, which provides energy to a boiler. This study finds an increased diesel duty corresponds with an increased cooling capacity, for a maximum of 5 kW of cooling (with 13.5 kWe diesel load). System COP is reduced with a higher input power due to limitations in the cooling cycle. A number of solutions are identified to increase the COP and cooling capacity. A new microchannel heat exchanger to recovery heat is designed to increase performance compared to the previous version. / Graduation date: 2012
Identifer | oai:union.ndltd.org:ORGSU/oai:ir.library.oregonstate.edu:1957/28445 |
Date | 09 March 2012 |
Creators | Seward, Ryan |
Contributors | Wang, Hailei |
Source Sets | Oregon State University |
Language | en_US |
Detected Language | English |
Type | Thesis/Dissertation |
Page generated in 0.0023 seconds