Return to search

Improving Energy Efficiency of School Buildings with Solar-Assisted Cooling for the Maldives

Anthropogenic activities are responsible for the impact of global climate change because of burning fossil fuels releasing harmful gases into the environment. As a result, the global temperature has risen about 1.18 °C since 1880, causing the global sea level to rise by 178 mm over the past century. This is a threat to countries that are closer to the ocean, especially the low-lying countries such as the Maldives. It is predicted if the sea level keeps rising, most of these islands could be below sea level by 2030.
The Maldives has a tropical climate requiring cooling to achieve thermal comfort. Electricity is used to provide cooling which is generated by burning fossil fuels. Due to the need for more buildings and the effects of global warming, the demand for cooling has increased, ultimately increasing the emissions.
Therefore, this paper investigated the methods to minimize the building cooling demand by creating a building model of a school in Feydhoo, Addu City, Maldives using DesignBuilder software. Also, to analyze the potential of using solar technology in providing cooling for the building, a clean energy source reducing emissions. The base model of the building showed that annual electricity consumption for cooling would be about 200.14 MWh. Based on the base model, multiple building models were created to understand the best option that can lower the cooling demand of the building. The results showed that having a super-insulated timber construction could be a better option by using improved double-glazed low-E windows and an improved cooling system with a COP of 3.2. This lowered the cooling energy demand to about 103.71 MWh.
Based on these results, a solar thermal cooling system was simulated using Polysun software which shows that solar thermal collectors were not able to provide the required cooling to run the chiller system. Hence, another option was explored where DesignBuilder software was used to model a solar PV array system to provide cooling for the building. But by using a better air conditioning system (VRF system coupled with a DOAS) to provide fresh conditioned air into the building, improving the indoor air quality. The results showed that the new PV array system was able to provide the electricity required not for cooling but for other electrical requirements (total of 163.31 MWh). It also resulted in a surplus of 1 MWh of electricity exported to the utility grid, achieving a net-positive energy building.

Identiferoai:union.ndltd.org:UMASS/oai:scholarworks.umass.edu:masters_theses_2-2354
Date09 August 2023
CreatorsFathhee, Ahmed
PublisherScholarWorks@UMass Amherst
Source SetsUniversity of Massachusetts, Amherst
Detected LanguageEnglish
Typetext
Formatapplication/pdf
SourceMasters Theses
Rightshttp://creativecommons.org/licenses/by/4.0/

Page generated in 0.0023 seconds