Critical analysis of voltage regulation on mismatched parallel-connected transformers.

M. Tech. Electrical Engineering. / Voltage control is an essential part of the electricity transmission and distribution network system for maintaining voltage within statutory limits at the substation bus and at the consumer's point of supply. The most popular voltage control method on the transmission and distribution network system uses the on-load tap changer (OLTC) transformer. This study proposes the use of Fuzzy Logic Control (FLC) systems on the on-load tap changers when two or more mismatched transformers are connected in parallel in order to control the voltage supply to local customers. The actual voltage recordings and on-load tap change operations for each of the paralleled transformers have been analyzed and modelled on MATLAB/Simulink in order to develop an improved control algorithm using Fuzzy Logic Control. With the two-input, one-output FLC system with seven linguistic values giving 49 control rules, the number of tap change operations are minimized and the bus voltage is maintained within the statutory limits.