Identificação de faltas de alta impedância em sistemas de distribuição.

Submitted by Emanuel Varela Cardoso (emanuel.varela@ufcg.edu.br) on 2018-05-07T20:46:33Z
No. of bitstreams: 1
WELLINSÍLVIO COSTA DOS SANTOS – TESE (PPGEE) 2016.pdf: 10591682 bytes, checksum: 97299060f7fb8f9c7f837b25352da777 (MD5) / Made available in DSpace on 2018-05-07T20:46:33Z (GMT). No. of bitstreams: 1
WELLINSÍLVIO COSTA DOS SANTOS – TESE (PPGEE) 2016.pdf: 10591682 bytes, checksum: 97299060f7fb8f9c7f837b25352da777 (MD5)
Previous issue date: 2016-08-15 / Capes / Uma técnica baseada em análise de transitórios eletromagnéticos é proposta para identificar faltas de alta impedância (FAI) em redes de distribuição. O algoritmo dispensa conhecimento dos parâmetros dos alimentadores e faz uso da transformada wavelet discreta (TWD) para monitorizar fenômenos transitórios associados a distúrbios no sistema de distribuição. A metodologia proposta é avaliada através de simulações em um programa de transitórios eletromagnéticos (EMTP) em um sistema de 13,8 kV, que foi modelado a partir de dados de uma rede de distribuição brasileira real. Além de FAI, foram simulados outros tipos de distúrbios, tais como faltas de baixa impedância, chaveamentos de novas linhas e bancos de capacitores. Os resultados obtidos demonstraram que o método é capaz de detectar a perturbação logo após o seu
início e distingui-la de outros distúrbios, além de proporcionar uma redução significativa da região de localização da FAI. / An electromagnetic transient analysis-based technique is proposed to identify high impedance faults (HIF) in distribution networks. The algorithm dispenses knowledge of the feeder parameters and makes use of discrete wavelet transform (TWD) to monitor transient phenomena associated with disturbances in the distribution system. The proposed methodology is evaluated through simulations in an electromagnetic transient program (EMTP) in a 13.8 kV system, which was modeled from actual Brazilian distribution network data. Besides HIF, other types of disturbances were simulated, such as low impedance fault, and switching of lines and capacitor banks. Obtained results have shown that the method is able to detect the disturbance soon after its inception and distinguish it from other disorders, as well as providing a significant reduction in the region of its location for maintenance crews.

Identiferoai:union.ndltd.org:IBICT/oai:localhost:riufcg/602
Date07 May 2018
CreatorsSANTOS, Wellinsílvio Costa dos.
ContributorsSOUZA, Benemar Alencar de., BRITO, Núbia Silva Dantas., NEVES, Washington Luiz Araújo., AQUINO, Ronaldo Ribeiro Barbosa de., MEDEIROS JÚNIOR, Manoel Firmino de., ASSIS, Francisco Marcos de.
PublisherUniversidade Federal de Campina Grande, PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA, UFCG, Brasil, Centro de Engenharia Elétrica e Informática - CEEI
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguageEnglish
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/doctoralThesis
Sourcereponame:Biblioteca de Teses e Dissertações da UFCG, instname:Universidade Federal de Campina Grande, instacron:UFCG
Rightsinfo:eu-repo/semantics/openAccess