Previous issue date: 2012 / Falhas inesperadas em transformadores levaram a identificação da formação de
sulfeto de cobre, depositado sobre os condutores, avaliando-se da presença
qualitativa de enxofre corrosivo resultando na alteração da norma brasileira ABNT
NBR 10505, que avalia a presença de enxofre corrosivo em óleo mineral, alterando-se
o tempo e a temperatura de ensaio para 150 °C por 48 horas. Realizando-se a
especiação química de compostos organosulfurados via cromatografia gasosa
acoplada a espectrometria de massas, onde foram encontrados 13 compostos
sulfurados no óleo Nynas e 9 compostos no óleo da Petrobras, sendo o dibenzil
dissulfeto (DBDS) o de maior concentração, encontrado apenas no óleo Nynas. Para
realizar a determinação da presença do DBDS em óleo mineral isolante foi
desenvolvido um método através de cromatografia gasosa acoplada a
espectrometria de massas, e por este método foi possível quantificar o teor de
DBDS em amostras de OMI oriundas de transformadores de potência. Foi avaliado o
processo de passivação do cobre por benzotriazol e tolutriazol, utilizados como
aditivos anticorrosivos no núcleo dos equipamentos elétricos, verificando-se que o
efeito da adição agente de passivação torna-se ineficaz com o passar do tempo. A
solução para a remoção de DBDS em óleo mineral foi a utilização de nanotubo de
carbono baseado em matriz metálica (NTC/Al) como agente de remoção do DBDS.
Verificou-se que o agente de adsorção foi capaz de efetuar a remoção total do
DBDS do OMI até um volume de 4000 mL de óleo contaminado com DBDS. / Unexpected failures in transformers led to the identification of copper sulphide
formation, deposited on the conductors. The qualitative presence evaluation of
corrosive sulfur in insulating mineral oil, led to a change in the Brazilian standards
ABNT NBR 10505, which assesses the presence of corrosive sulfur in mineral oil,
change in the time and test temperature to 150 °C / 48 hours. Performing the
chemical speciation of organosulfur compounds (by gas chromatography coupled to
mass spectrometry), were found 13 compounds in the Nynas oil and 9 compounds in
the Petrobras oil. DBDS, which was found only in the Nynas oil, and it was the
compound with the highest concentration. To perform the determination of the
presence of DBDS in insulating mineral oil, a method by gas chromatography
coupled to mass spectrometry was developed, and it was possible to quantify the
amount of DBDS in insulating mineral oil samples derived from the power
transformer. The passivation process by tolutriazol and benzotriazol, used as
anticorrosive additives in the core of electrical equipament, was evaluated; after a
while the effect of the addition of passivating agent becomes ineffective with time.
The solution for the remotionl of DBDS from mineral oil was realized by using carbon
nanotube reinforced by metallic matrix as agent to remove the DBDS. It was found
that the adsorption agent was able to realize the complete DBDS remotion from
insulating mineral oil up to a volume of 4000 mL (oil contaminated with DBD).
Identifer | oai:union.ndltd.org:IBICT/oai:repositorio.ufpa.br:2011/4597 |
Date | 07 May 2012 |
Creators | SARAIVA, Augusto Cesar Fonseca |
Contributors | DEL NERO, Jordan |
Publisher | Universidade Federal do Pará, Programa de Pós-Graduação em Engenharia Elétrica, UFPA, Brasil, Instituto de Tecnologia |
Source Sets | IBICT Brazilian ETDs |
Language | Portuguese |
Detected Language | English |
Type | info:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/doctoralThesis |
Source | reponame:Repositório Institucional da UFPA, instname:Universidade Federal do Pará, instacron:UFPA |
Rights | info:eu-repo/semantics/openAccess |
Page generated in 0.0125 seconds