Análise de estabilidade transitória na otimização de sistemas elétricos de potência / Transitory stability analysis in the electric power system optimization

Dissertação (mestrado)—Universidade de Brasília, Faculdade de Tecnologia, Departamento de Engenharia Elétrica, 2009. / Submitted by Camila Duarte (camiladias@bce.unb.br) on 2017-01-26T17:10:30Z
No. of bitstreams: 1
2009_RobervalMadeiraDaSilva.pdf: 1848670 bytes, checksum: 0aad4f72191abc216c7f7112596179ac (MD5) / Approved for entry into archive by Patrícia Nunes da Silva(patricia@bce.unb.br) on 2017-01-29T10:43:00Z (GMT) No. of bitstreams: 1
2009_RobervalMadeiraDaSilva.pdf: 1848670 bytes, checksum: 0aad4f72191abc216c7f7112596179ac (MD5) / Made available in DSpace on 2017-01-29T10:43:00Z (GMT). No. of bitstreams: 1
2009_RobervalMadeiraDaSilva.pdf: 1848670 bytes, checksum: 0aad4f72191abc216c7f7112596179ac (MD5) / Esta dissertação apresenta uma metodologia para associação de estudos de estabilidade
transitória de ângulo de rotor com estudos de otimização de sistemas elétricos de potência.
Nesta metodologia, são alterados, nas restrições do Fluxo de Potência Ótimo (FPO), os
limites de potência ativa do(s) gerador(es) previamente identificado(s) através do cálculo
da diferença angular entre cada gerador e o Centro de Inércia (Cl), na condição préperturbação.
O FPO é utilizado para calcular o despacho que resulte no menor valor de perdas
elétricas na transmissão, do ponto de vista estático. Em seguida, são realizadas diversas
simulações de estabilidade transitória, avaliando o comportamento dos ângulos de rotor
frente aos critérios de segurança dinâmica estabelecidos. Caso os critérios de segurança
sejam violados, será necessário repetir a execução do FPO até que seja encontrado um
ponto de operação que atenda aos critérios do FPO e aos critérios de segurança dinâmica.
Com o cálculo da diferença angular entre os geradores e o Cl, a repetição do FPO deixa
de utilizar o método de “tentativa e erro”, uma vez que é possível estabelecer o sentido da
variação na potência ativa do(s) gerador(es) mais crítico(s). Os geradores que possuem
maior defasagem angular em relação ao Cl terão seu despacho de potência ativa restringido
a valores próximos ao seu limite inferior, nas situações em que o ângulo do gerador for
maior que o ângulo do Cl, ou ao seu limite superior (ângulo do gerador menor que o
ângulo do Cl). Esta metodologia foi testada em uma rede de 9 barras e em um sistema real
de 41 barras. / This dissertation presents a methodology to associate angle transitory stability analysis
with electric power system optimization studies. Whenever dynamic security criteria are
violated in a pre-disturbance condition, the active power generation capacity constraints
are modified in the optimal power flow (OPF) for generators previously selected. The
selection is based on the calculation of the angular displacement between each generator
and the Inertial Center (IC).
The OPF is used for dispatch calculation which results in lowest transmission losses,
concerning the static point of view. Then, several transitory stability simulations are
accomplished to evaluate the rotor's angle behavior in relation to established dynamic
security criteria. In the occurrence of security criteria violations, a new optimal dispatch is
calculated, and the process is repeated until reaching an operation point with no violations.
Once the presented methodology makes use of angular displacement calculations to
select which generators are candidates to solve the security problem, the usual empiric
check-and-bound methods are not utilized. The method presented in this work allows to
identifying the generators with greater angular displacements, choosing them and changing
their active power constraint. The constraint is changed to a value close to the generator’s
lower limit of generation capacity if the generator's angle is larger than the IC's angle. On
the contrary, the generator's active power constraint is changed to its upper generation
capacity limit. The methodology was tested with a 9-bus network and a real 41-bus
system.

Identiferoai:union.ndltd.org:IBICT/oai:repositorio.unb.br:10482/22295
Date07 December 2009
CreatorsSilva, Roberval Madeira da
ContributorsSouza, Alessandra Macedo de, Camargo, Ivan Marques de Toledo
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguagePortuguese
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Sourcereponame:Repositório Institucional da UnB, instname:Universidade de Brasília, instacron:UNB
RightsA concessão da licença deste item refere-se ao termo de autorização impresso assinado pelo autor com as seguintes condições: Na qualidade de titular dos direitos de autor da publicação, autorizo a Universidade de Brasília e o IBICT a disponibilizar por meio dos sites www.bce.unb.br, www.ibict.br, http://hercules.vtls.com/cgi-bin/ndltd/chameleon?lng=pt&skin=ndltd sem ressarcimento dos direitos autorais, de acordo com a Lei nº 9610/98, o texto integral da obra disponibilizada, conforme permissões assinaladas, para fins de leitura, impressão e/ou download, a título de divulgação da produção científica brasileira, a partir desta data., info:eu-repo/semantics/openAccess

Page generated in 0.0028 seconds