Return to search

Ajuste ótimo da potência inserida por unidades de geração distribuída em alimentadores de média tensão / Optimum sizing of units of generations distributed in radial systems of distribution through techniques of nonlinear programming

Dissertação (mestrado)—Universidade de Brasília, Faculdade de Tecnologia, Departamento de Engenharia Elétrica, 2006. / Submitted by wesley oliveira leite (leite.wesley@yahoo.com.br) on 2009-11-12T22:10:36Z
No. of bitstreams: 1
dissertacao KENNETH ROSSEVELT SAMPAIO MENDONÇA.pdf: 857605 bytes, checksum: 765b37e60be197f934ae8f3fc6737469 (MD5) / Approved for entry into archive by Lucila Saraiva(lucilasaraiva1@gmail.com) on 2010-03-01T21:57:54Z (GMT) No. of bitstreams: 1
dissertacao KENNETH ROSSEVELT SAMPAIO MENDONÇA.pdf: 857605 bytes, checksum: 765b37e60be197f934ae8f3fc6737469 (MD5) / Made available in DSpace on 2010-03-01T21:57:54Z (GMT). No. of bitstreams: 1
dissertacao KENNETH ROSSEVELT SAMPAIO MENDONÇA.pdf: 857605 bytes, checksum: 765b37e60be197f934ae8f3fc6737469 (MD5)
Previous issue date: 2006-05 / O dimensionamento ótimo de unidades de Geração Distribuída é um problema à qual a
formulação leva em consideração a redução de perdas nas linhas de distribuição, o controle de
tensão, a capacidade (em MW) das unidades respeitando os limites operacionais do sistema. O
principal objetivo do processo de dimensionamento é determinar os níveis de potência ativa e
reativa a serem inseridas em um sistema de distribuição radial de forma a reduzir suas perdas
totais e realizar controle de tensão. Para isto, duas técnicas de programação não linear são
implementadas: Método da Aproximação Quadrática e Método de Newton.
Primeiramente, são apresentadas as soluções encontradas para redução de perdas em sistemas
de distribuição da literatura, trabalhando em carga média. Os testes são realizados em barras
escolhidas no início, meio e fim dos sistemas, de forma a observar o comportamento das
técnicas de programação não linear utilizadas. A segunda abordagem, leva em consideração
novamente os dados da literatura, mas com um enfoque diferente: o controle de tensão. Neste
teste é utilizado, junto às técnicas de programação matemática, o Método das Penalidades que
penaliza à função objetivo caso as tensões não estejam dentro dos limites determinados. A
última abordagem é realizada com sistemas de distribuição criados no intuito de simular
situações reais como redes sem ramificações e trabalhando em três níveis de carga: leve,
médio e pesado.
Os resultados das simulações mostram reduções maciças das perdas para a primeira
abordagem, e para a segunda abordagem tem-se o controle de tensão, observanso-se um
aumento das perdas totais do sistema para que seja realizado o controle de tensão nos sistemas testados. A principal vantagem da abordagem sugerida é a sua simplicidade de implementação e a sua velocidade de processamento. __________________________________________________________________________________________ ABSTRACT / The optimum sizing of units of Distributed Generation is a problem to which this formulation takes in consideration the reduction of losses in the distribution lines, the voltage control, the
capacity (in MW) of the units respecting the operational limits of the system. The main
objective of the sizing process is to determine the active and reactive power levels to be inserted in a system of radial distribution in order to reduce its total losses and to carry through voltage control. For this, two techniques of nonlinear programming are implemented:
Quadratic Fit Method and Newton’s Method.
First, the solutions found for the reduction of losses in distribution systems in the literature are presented, working with medium load. The tests are carried out at chosen bars in the beginning, middle and end of the systems, in order to observe the response behavior of the used techniques with nonlinear programming. The second approach, takes in consideration
again the literature data, but with one difference: the voltage control. In this test it is used, together to the techniques of mathematical programming, the Method of the Penalties that penalizes the objective function in the case the voltage is not inside of the defined limits. The
last approach is carried with distribution systems created to simulate real situations like
feeders without ramifications and working within three load levels: low, medium and high.
The results of the simulations show massive reductions of the losses in the first approach, and
for the second one when the voltage control is exerted, it is observed an increase of the total
losses of the system so that the control of voltage in the tested systems is carried out. The main advantage of the suggested approach is its simplicity implementation and its high processing speed.

Identiferoai:union.ndltd.org:IBICT/oai:repositorio.unb.br:10482/3792
Date05 1900
CreatorsMendonça, Kenneth Roosevelt Sampaio
ContributorsCoelho, Marco Antônio Freitas do Egito
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguagePortuguese
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Sourcereponame:Repositório Institucional da UnB, instname:Universidade de Brasília, instacron:UNB
Rightsinfo:eu-repo/semantics/openAccess

Page generated in 0.011 seconds