Análise da proteção antiilhamento de geradores de indução conectados em redes de distribuição de energia elétrica / Analysis of the anti-islanding protection of induction generators connected to electric power distribution systems

Orientador: Walmir de Freitas Filho / Dissertação (mestrado) - Universidade Estadual de Campinas, Faculdade de Engenharia Eletrica e de Computação / Made available in DSpace on 2018-08-15T23:24:26Z (GMT). No. of bitstreams: 1
Meira_PauloCesarMagalhaes_M.pdf: 4399317 bytes, checksum: abd35262b6780f553e52831e63c6947c (MD5)
Previous issue date: 2010 / Resumo: Em redes de distribuição, ilhamento ocorre quando parte da rede elétrica é desconectada do restante do sistema da concessionária, mas continua a ser energizada por um ou mais geradores distribuídos conectados a ela. Esta ocorrência deve ser evitada porque coloca em risco a segurança de pessoas e equipamentos. Diversos trabalhos têm sido desenvolvidos na análise do comportamento ilhado e da proteção antiilhamento de geradores síncronos e de geradores não-rotativos conectados via conversores eletrônicos. No entanto, pouca atenção tem sido dada aos casos envolvendo geradores de indução, sejam eles geradores duplamente alimentados ou com rotor tipo gaiola de esquilo. Portanto, o objetivo desta dissertação de mestrado é investigar o comportamento destes geradores durante ilhamentos, bem como analisar a eficiência dos relés baseados em medidas de freqüência e tensão para a realização de proteção antiilhamento. A ferramenta empregada para análise da proteção antiilhamento é a zona de não-detecção, a qual é definida como a região no espaço de desbalanço de potência reativa versus desbalanço de potência ativa em que o sistema de proteção antiilhamento não consegue detectar a situação de ilhamento dentro do tempo especificado. Tais zonas foram obtidas através de numerosas simulações de transitórios eletromagnéticos utilizando o programa PSCAD/EMTDC / Abstract: In distribution systems, islanding occurs when part of the electric system is disconnected from the remaining utility system, but continues to be fed by one or more distributed generators operating in the island. This occurrence should be avoided as it represents a safety risk to equipment and customers. There have been several research papers which analyze the islanding behavior and the anti-islanding protection of synchronous generators and non-rotating generators connected to the grid using electronic converters. Nonetheless, little attention has been spent to analyze the situations involving induction generators, either doubly-fed generators or squirrel-cage generators. Therefore, the objective of this dissertation is to investigate the behavior of these generators during islanded operation, as well as analyze the efficiency of anti-islanding protection schemes based on frequency and voltage relays. The analysis is conducted by using the non-detection zone, which is defined in the active versus reactive power imbalance space where the anti-islanding protection fails. These zones were determined by numerous electromagnetic transient simulations by using the software PSCAD/EMTDC / Mestrado / Energia Eletrica / Mestre em Engenharia Elétrica

Identiferoai:union.ndltd.org:IBICT/oai:repositorio.unicamp.br:REPOSIP/259993
Date15 August 2018
CreatorsMeira, Paulo César Magalhães, 1985-
ContributorsUNIVERSIDADE ESTADUAL DE CAMPINAS, Freitas Filho, Walmir de, 1971-, Filho, Walmir de Freitas, Haffner, Sergio Luis, Rider Flores, Marcos Julio
Publisher[s.n.], Universidade Estadual de Campinas. Faculdade de Engenharia Elétrica e de Computação, Programa de Pós-Graduação em Engenharia Elétrica
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguagePortuguese
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/masterThesis
Format138 p. : il., application/pdf
Sourcereponame:Repositório Institucional da Unicamp, instname:Universidade Estadual de Campinas, instacron:UNICAMP
Rightsinfo:eu-repo/semantics/openAccess

Page generated in 0.0029 seconds