Metodologias para ajuste e avaliação do desempenho de reles de proteção anti-ilhamento de geradores sincronos distribuidos / Methods for setting and evaluating the performance of anti-islanding protection relays of distributed synchronous generators

Orientadores: Andre Luiz Morelato França, Walmir de Freitas Filho / Tese (doutorado) - Universidade Estadual de Campinas, Faculdade de Engenharia Eletrica e de Computação / Made available in DSpace on 2018-08-06T02:54:55Z (GMT). No. of bitstreams: 1
VieiraJunior_JoseCarlosdeMelo_D.pdf: 1983649 bytes, checksum: 2abfcaa471b650a7138b798950c476a7 (MD5)
Previous issue date: 2006 / Resumo: Uma das principais funções dos sistemas de proteção de geradores distribuídos conectados em redes de subtransmissão ou de distribuição de energia elétrica é desconectá-los tão logo uma situação de ilhamento seja detectada. O ilhamento ocorre quando parte da rede elétrica é desconectada do restante do sistema da concessionária, mas continua a ser energizada por um ou mais geradores distribuídos conectados a ela, formando um subsistema isolado da concessionária. Esta ocorrência deve ser evitada porque coloca em risco a segurança de pessoas e equipamentos e pode deteriorar a qualidade da energia suprida aos consumidores locais. Neste contexto, esta tese de doutorado propõe novas metodologias para avaliar de forma sistemática e ajustar alguns dos principais relés de proteção anti-ilhamento de geradores síncronos. As técnicas analisadas compreendem os relés de deslocamento de fase ou ¿salto de vetor¿, relés de taxa de variação de freqüência, relés de sub/sobrefreqüência convencionais e os relés de sub/sobretensão convencionais. A aplicação das metodologias desenvolvidas mostrou que elas são ferramentas eficientes para avaliar e determinar o desempenho desses relés quanto à detecção de ilhamentos, auxiliando na seleção dos esquemas de proteção e ajustes mais adequados / Abstract: One of the main functions of distributed generators¿ protection systems is the capability to disconnect the generators immediately after an islanding occurrence is detected. Islanding occurs when a portion of the distribution system is disconnected from the utility grid, yet remains energized by one or more distributed generators connected to it. This operating condition should be avoided because it poses safety risks to utility personnel and equipments as well as it can cause power quality problems to the local costumers. In this context, this thesis proposes new methodologies to systematically evaluate and adjust some anti-islanding techniques applied to synchronous generators. The techniques analyzed are the under/over frequency relays, the rate of change of frequency (ROCOF) relays, the vector surge or vector jump relays and the under/overvoltage relays. The results have shown that the proposed methodologies can be efficient tools to evaluate and to determine the performance of these anti-islanding relays, consequently, they can help protection engineers to select the most proper protection devices and their settings / Doutorado / Energia Eletrica / Doutor em Engenharia Elétrica

Identiferoai:union.ndltd.org:IBICT/oai:repositorio.unicamp.br:REPOSIP/260506
Date03 October 2006
CreatorsVieira Junior, Jose Carlos de Melo
ContributorsUNIVERSIDADE ESTADUAL DE CAMPINAS, Freitas Filho, Walmir de, 1971-, França, Andre Luiz Morelato, 1946-, Coury, Denis Vinicius, Junior, Sandoval Carneiro, Sato, Fujio, Tavares, Maria Cristina Dias, Deckmann, Sigmar Maurer
Publisher[s.n.], Universidade Estadual de Campinas. Faculdade de Engenharia Elétrica e de Computação
Source SetsIBICT Brazilian ETDs
LanguagePortuguese
Detected LanguagePortuguese
Typeinfo:eu-repo/semantics/publishedVersion, info:eu-repo/semantics/doctoralThesis
Format197p. : il., application/pdf
Sourcereponame:Repositório Institucional da Unicamp, instname:Universidade Estadual de Campinas, instacron:UNICAMP
Rightsinfo:eu-repo/semantics/openAccess

Page generated in 0.0024 seconds