Return to search

Modeling of High Voltage Pollution Discharge to Investigate Hot Stick Flashover

Electric “flashover” or insulation breakdown has occurred on “hot stick” safety tools used on live AC transmission lines at Manitoba Hydro in 1997 and 2002. Investigations showed pollution flashover as the cause, whereby leakage currents cascade into flashover. Prior to reinstating live-line work with mitigation procedures, DC voltage experiments suggested an atypical flashover uncharacteristic of pollution flashover without leakage currents, which may require a different mitigation strategy. In this thesis, statistical analysis shows that relative humidity has a greater correlation than voltage with the type of flashover. Labeled a “fast flashover”, it seems to be distinct from pollution flashover, although not statistically significant. A time-stepping computer model was developed to calculate a critical voltage for flashover as a function of relative humidity. However, lack of data prevents the model from making firm
conclusions. A list of recommended research is proposed to remedy these deficiencies to allow future model refinement.

Identiferoai:union.ndltd.org:LACETR/oai:collectionscanada.gc.ca:MWU.1993/18487
Date04 April 2013
CreatorsReske, Dean
ContributorsKordi, Behzad (Electrical and Computer Engineering) Swatek, David (Electrical and Computer Engineering), Oliver, Derek (Electrical and Computer Engineering) Major, Arkady (Electrical and Computer Engineering) Jafari Jozani, Mohammad (Statistics)
Source SetsLibrary and Archives Canada ETDs Repository / Centre d'archives des thèses électroniques de Bibliothèque et Archives Canada
Detected LanguageEnglish

Page generated in 0.0054 seconds