A study of convective boiling heat transfer of a micro-fin chip cooler in a confined space / 微鰭片晶片散熱器之限制空間對流沸騰熱傳研究

碩士 / 國立臺北科技大學 / 能源與冷凍空調工程系碩士班 / 105 / In this study, flow boiling experiment is tested with di-electric fluid, FC-72, which flow through a 14 mm by 14 mm square heated area in a square channel having variable space. Cubic fins of 0.2 mm in both height and width were made on the copper plate with 0.2 mm fin gap. The internal space of the test section is either 1/4, 1/2, or 3/4 covered. The experimental results showed that the single phase convetion heat transfer performane increased the ratio of covered area as a result of increased flow velocity above the heated surface under a confined space of 1.0mm channel height. For two phase convection with boiling, the heat transfer coefficient increased with the cover-ratio at 500 and 800 ml/min. However,insignificant effect on cover-ratio was found at 200 ml/min because the dominat heat transfer mechanism is boiling. Observation of flow phenomena showed that the bubble size reduced as the flow velocity increased with increasing cover- ratio.