Lokalizace místa zemního spojení v kompenzované distribuční síti / Ground Fault Location in Compensated Distribution Network

The most widespread system of an earthing neutral point of a supply transformer in a MV network is an earthing through an arc-suppression coil. In this case of a resonant-earthed power system a fault current is compensated by the suppression coil and only residual current flows through a fault point. A value of the residual current is much smaller then a value of an original capacitive current of the network and is not dependent on the fault location. According to that reasons it is really complicated to fast and accurately determine the fault point location. Since nowadays used methods for the ground fault location inside wide distribution networks have a lot of disadvantages, the thesis is focused on a proposal of a new method for the ground fault location especially inside of a compensated network. The main reasons for a consecutive installation of power quality meters into distribution transformer substations are a power quality monitoring and a global evolution of an electrical network onto the “SmartGrids”. In case that all results from the meters are properly synchronized and centralized, new possibilities of control or of an evaluation of a network are enabled. This doctoral thesis proposes the possibility for the ground fault detection with an aid of synchronized records recorded on the low-voltage side of the distribution transformers 22/0.4 kV into the network equipped with automatics for short-time increasing of an active part of a faulty current. The described method uses a voltage drop evoked by connecting of the auxiliary resistor for location of the faulty section. The proposed method is tested with help of numerical model which presents a part of the distribution network Series of simulation are executed and correct function and force function of the method is reviewed. Finally the thesis describes real experiment and also a confrontation between simulation and real measuring, and also possibilities of method usage are commented.

Identiferoai:union.ndltd.org:nusl.cz/oai:invenio.nusl.cz:233549
Date January 2011
CreatorsTopolánek, David
ContributorsJaníček,, František, Mišák,, Stanislav, Toman, Petr
PublisherVysoké učení technické v Brně. Fakulta elektrotechniky a komunikačních technologií
Source SetsCzech ETDs
LanguageCzech
Detected LanguageEnglish
Typeinfo:eu-repo/semantics/doctoralThesis
Rightsinfo:eu-repo/semantics/restrictedAccess

Page generated in 0.0026 seconds