Return to search

REDESIGN OF HVAC SYSTEM TO IMPROVE ENERGY EFFICIENCY OF EDUCATIONAL BUILDING

An energy modeling software was used to analyze the current building configuration and simulations were performed in an attempt to redesign the current HVAC system of an educational building to improve the energy efficiency of the building, exceed current building code requirements, and meet the building's cooling and heating load. The different HVAC systems simulated were: Dual Air Duct, Variable-Air Volume (VAV), and Dedicated Outdoor Air Systems (DOAS). Each system was modeled in four operation schedules including: current system operation, fan control, lighting control, and lighting and fan control. These operation schedules are to represent how efficient the building would be in different controlled settings. Results were obtained regarding the energy requirements of the different HVAC systems. For the educational building both VAV and DOAS systems offer 48.8% and 57.9%, respectively, in annual savings in energy use, achieved by adding controls to the lights and fans of both systems reducing energy consumed by ventilation fans. The time of a simple payback period for a new VAV and DOAS system is 10.2 and 9.35 years, respectively, and may remove any considerations to implement a new HVAC system. Based on these findings, educational buildings using Dual Duct should consider using DOAS systems.

Identiferoai:union.ndltd.org:siu.edu/oai:opensiuc.lib.siu.edu:theses-1834
Date01 May 2012
CreatorsHagene, Brian Matthew
PublisherOpenSIUC
Source SetsSouthern Illinois University Carbondale
Detected LanguageEnglish
Typetext
Formatapplication/pdf
SourceTheses

Page generated in 0.0025 seconds