Return to search

Thermodynamic modeling and optimization of a screw compressor chiller and cooling tower system

This thesis presents a thermodynamic model for a screw chiller and cooling tower system for the purpose of developing an optimized control algorithm for the chiller plant. The thermodynamic chiller model is drawn from the thermodynamic models developed by Gordon and Ng (1996). However, the entropy production in the compressor is empirically related to the pressure difference measured across the compressor. The thermodynamic cooling tower model is the Baker & Shryock cooling tower model that is presented in ASHRAE Handbook - HVAC Systems and Equipment (1992). The models are coupled to form a chiller plant model which can be used to determine the optimal performance. Two correlations are then required to optimize the system: a wet-bulb/setpoint correlation and a fan speed/pump speed correlation. Using these correlations, a "quasi-optimal" operation can be achieved which will save 17% of the energy consumed by the chiller plant.

Identiferoai:union.ndltd.org:tamu.edu/oai:repository.tamu.edu:1969.1/427
Date30 September 2004
CreatorsGraves, Rhett David
ContributorsCulp, Charles H.
PublisherTexas A&M University
Source SetsTexas A and M University
Languageen_US
Detected LanguageEnglish
TypeBook, Thesis, Electronic Thesis, text
Format2358950 bytes, 89357 bytes, electronic, application/pdf, text/plain, born digital

Page generated in 0.0013 seconds