The hardware validation of a novel average-value model (AVM) for the simulation of a synchronous-generator/controlled rectifier system is presented herein. The generator is characterized using genetic algorithm techniques to fit standstill frequency response (SSFR) measurements to q and d-axis equivalent circuits representing the generator in the rotor reference frame. The generator parameters form the basis of a detailed model of the system, from which algebraic functions defining the parametric AVM are derived. The average-value model is compared to the physical system for a variety of loading and operating conditions including step load change, change in delay angle, and external closed-loop control, validating the model accuracy for steady-state and transient operation.