{"id":{"repo_id":"bu","oai_identifier":"oai:open.bu.edu:2144/46654"},"canonical_url":"https://search.ndltd.org/etd/bu/oai:open.bu.edu:2144/46654","repository":{"repo_id":"bu","name":"Boston University","base_url":"https://open.bu.edu/oai/request"},"display":{"title":"Performance-aware site-wide data center power management","abstract":"Top high performance computing (HPC) data centers recently entered the era of exascale computing, requiring up to tens of megawatts for a computing facility to meet its users’ computing needs. The massive capacity for power at a single site comes with challenges in power management. Poorly managed power may result in unnecessarily high demand on costly energy or may cause the system to under-perform. An HPC data center may have many types of users and workloads with non-trivial power requirements, making it difficult to select a one-size-fits-all policy. But the high power capacity also offers opportunities for data centers to be key players enabling greater adoption of renewable energy across a power grid. Data centers can adjust their demand through software power management policies to help smart grids balance against nature’s time-varying green energy supply. This thesis claims that multi-tiered power management methods are essential for data centers to implement site-wide power management policies that accurately respond to changing power constraints at a higher cluster-level tier while reacting to application-specific performance impacts at a lower job-level tier. Through investigations over site, cluster, job, and server characteristics, we demonstrate that a feedback-driven multi-tiered power management approach meets power management objectives more effectively than siloed solutions. We design a cluster power management policy that distributes power across jobs using knowledge about job power-performance properties, demonstrating up to 7% reduction in system time dedicated to jobs and up to 11% savings in energy, compared to a policy without job awareness. We provide a power management framework that enables accurate, dynamic cluster power control while reacting to incomplete or inaccurate prior knowledge about job power and performance properties. We add a site-wide power model to a cluster power management policy that offers regulation services in a smart grid, showing 1.3x cost savings compared to a policy that is unaware of site-wide power consumption. We introduce a job power management policy that integrates job performance awareness with knowledge of hardware power-performance trade-offs, demonstrating up to 40% energy reduction and 17% execution time reduction in an imbalanced, compute-bound benchmark compared to a policy without frequency throttling.","abstract_html":"Top high performance computing (HPC) data centers recently entered the era of exascale computing, requiring up to tens of megawatts for a computing facility to meet its users’ computing needs. The massive capacity for power at a single site comes with challenges in power management. Poorly managed power may result in unnecessarily high demand on costly energy or may cause the system to under-perform. An HPC data center may have many types of users and workloads with non-trivial power requirements, making it difficult to select a one-size-fits-all policy. But the high power capacity also offers opportunities for data centers to be key players enabling greater adoption of renewable energy across a power grid. Data centers can adjust their demand through software power management policies to help smart grids balance against nature’s time-varying green energy supply. This thesis claims that multi-tiered power management methods are essential for data centers to implement site-wide power management policies that accurately respond to changing power constraints at a higher cluster-level tier while reacting to application-specific performance impacts at a lower job-level tier. Through investigations over site, cluster, job, and server characteristics, we demonstrate that a feedback-driven multi-tiered power management approach meets power management objectives more effectively than siloed solutions. We design a cluster power management policy that distributes power across jobs using knowledge about job power-performance properties, demonstrating up to 7% reduction in system time dedicated to jobs and up to 11% savings in energy, compared to a policy without job awareness. We provide a power management framework that enables accurate, dynamic cluster power control while reacting to incomplete or inaccurate prior knowledge about job power and performance properties. We add a site-wide power model to a cluster power management policy that offers regulation services in a smart grid, showing 1.3x cost savings compared to a policy that is unaware of site-wide power consumption. We introduce a job power management policy that integrates job performance awareness with knowledge of hardware power-performance trade-offs, demonstrating up to 40% energy reduction and 17% execution time reduction in an imbalanced, compute-bound benchmark compared to a policy without frequency throttling.","abstract_has_math":false,"creators":["Wilson, Daniel C."],"institution":"Boston University","degree_name":"Doctor of Philosophy","degree_level":"doctoral","degree_discipline":"Electrical & Computer Engineering","degree_department":null,"school":null,"contributors":[],"advisors":["Coskun, Ayse K."],"committee_chairs":[],"committee_members":[],"year":2023,"date_issued":"2023","date_published":"2023","updated_at":"2026-11-19T02:41:40Z","subjects":["Computer engineering"],"languages":["en_US"],"rights":[],"rights_urls":[],"identifier_entries":[],"person_identifier_entries":[{"key":"dc:identifier.orcid","label":"ORCID","values":["0000-0001-5101-9471"],"render_values":[{"text":"0000-0001-5101-9471","href":"https://orcid.org/0000-0001-5101-9471","code":true}]}]},"links":{"outbound_url":"https://hdl.handle.net/2144/46654","outbound_label":"Handle","outbound_source":"dc:identifier.uri","record_url":"https://hdl.handle.net/2144/46654","record_label":"Repository record","record_kind":"handle","record_source":"dc:identifier.uri","download_url":null,"download_label":null,"download_source":null,"access_status":null,"embargo_until":null,"access_note":null},"source_record":{"url":"https://open.bu.edu/oai/request?verb=GetRecord&metadataPrefix=dim&identifier=oai%3Aopen.bu.edu%3A2144%2F46654","prefix":"dim"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor.advisor","label":"Advisor","values":["Coskun, Ayse K."]},{"key":"dc:creator","label":"Author","values":["Wilson, Daniel C."]},{"key":"dc:identifier.orcid","label":"ORCID","values":["0000-0001-5101-9471"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date.accessioned","label":"Dc Date Accessioned","values":["2023-09-06T13:59:27Z"]},{"key":"dc:date.embargo","label":"Dc Date Embargo","values":["2024-02-29T00:00:00Z"]},{"key":"dc:date.issued","label":"Date","values":["2023"]},{"key":"dc:date.updated","label":"Dc Date Updated","values":["2023-08-30T04:05:09Z"]},{"key":"dc:type","label":"Dc Type","values":["Thesis/Dissertation"]},{"key":"thesis:degree_discipline","label":"Discipline","values":["Electrical & Computer Engineering"]},{"key":"thesis:degree_level","label":"Degree Level","values":["doctoral"]},{"key":"thesis:degree_name","label":"Degree Name","values":["Doctor of Philosophy"]},{"key":"thesis:institution_name","label":"Thesis Institution Name","values":["Boston University"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject","label":"Dc Subject","values":["Computer engineering"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:language.iso","label":"Language (ISO)","values":["en_US"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier.uri","label":"Identifier URI","values":["https://hdl.handle.net/2144/46654"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description.abstract","label":"Abstract","values":["Top high performance computing (HPC) data centers recently entered the era of exascale computing, requiring up to tens of megawatts for a computing facility to meet its users’ computing needs. The massive capacity for power at a single site comes with challenges in power management. Poorly managed power may result in unnecessarily high demand on costly energy or may cause the system to under-perform. An HPC data center may have many types of users and workloads with non-trivial power requirements, making it difficult to select a one-size-fits-all policy. But the high power capacity also offers opportunities for data centers to be key players enabling greater adoption of renewable energy across a power grid. Data centers can adjust their demand through software power management policies to help smart grids balance against nature’s time-varying green energy supply. This thesis claims that multi-tiered power management methods are essential for data centers to implement site-wide power management policies that accurately respond to changing power constraints at a higher cluster-level tier while reacting to application-specific performance impacts at a lower job-level tier. Through investigations over site, cluster, job, and server characteristics, we demonstrate that a feedback-driven multi-tiered power management approach meets power management objectives more effectively than siloed solutions. We design a cluster power management policy that distributes power across jobs using knowledge about job power-performance properties, demonstrating up to 7% reduction in system time dedicated to jobs and up to 11% savings in energy, compared to a policy without job awareness. We provide a power management framework that enables accurate, dynamic cluster power control while reacting to incomplete or inaccurate prior knowledge about job power and performance properties. We add a site-wide power model to a cluster power management policy that offers regulation services in a smart grid, showing 1.3x cost savings compared to a policy that is unaware of site-wide power consumption. We introduce a job power management policy that integrates job performance awareness with knowledge of hardware power-performance trade-offs, demonstrating up to 40% energy reduction and 17% execution time reduction in an imbalanced, compute-bound benchmark compared to a policy without frequency throttling."]},{"key":"dc:title","label":"Title","values":["Performance-aware site-wide data center power management"]}]}],"canonical_facts":{"dc:contributor.advisor":["Coskun, Ayse K."],"dc:creator":["Wilson, Daniel C."],"dc:date.accessioned":["2023-09-06T13:59:27Z"],"dc:date.embargo":["2024-02-29T00:00:00Z"],"dc:date.issued":["2023"],"dc:date.updated":["2023-08-30T04:05:09Z"],"dc:description.abstract":["Top high performance computing (HPC) data centers recently entered the era of exascale computing, requiring up to tens of megawatts for a computing facility to meet its users’ computing needs. The massive capacity for power at a single site comes with challenges in power management. Poorly managed power may result in unnecessarily high demand on costly energy or may cause the system to under-perform. An HPC data center may have many types of users and workloads with non-trivial power requirements, making it difficult to select a one-size-fits-all policy. But the high power capacity also offers opportunities for data centers to be key players enabling greater adoption of renewable energy across a power grid. Data centers can adjust their demand through software power management policies to help smart grids balance against nature’s time-varying green energy supply. This thesis claims that multi-tiered power management methods are essential for data centers to implement site-wide power management policies that accurately respond to changing power constraints at a higher cluster-level tier while reacting to application-specific performance impacts at a lower job-level tier. Through investigations over site, cluster, job, and server characteristics, we demonstrate that a feedback-driven multi-tiered power management approach meets power management objectives more effectively than siloed solutions. We design a cluster power management policy that distributes power across jobs using knowledge about job power-performance properties, demonstrating up to 7% reduction in system time dedicated to jobs and up to 11% savings in energy, compared to a policy without job awareness. We provide a power management framework that enables accurate, dynamic cluster power control while reacting to incomplete or inaccurate prior knowledge about job power and performance properties. We add a site-wide power model to a cluster power management policy that offers regulation services in a smart grid, showing 1.3x cost savings compared to a policy that is unaware of site-wide power consumption. We introduce a job power management policy that integrates job performance awareness with knowledge of hardware power-performance trade-offs, demonstrating up to 40% energy reduction and 17% execution time reduction in an imbalanced, compute-bound benchmark compared to a policy without frequency throttling."],"dc:identifier.orcid":["0000-0001-5101-9471"],"dc:identifier.uri":["https://hdl.handle.net/2144/46654"],"dc:language.iso":["en_US"],"dc:subject":["Computer engineering"],"dc:title":["Performance-aware site-wide data center power management"],"dc:type":["Thesis/Dissertation"],"thesis:degree_discipline":["Electrical & Computer Engineering"],"thesis:degree_level":["doctoral"],"thesis:degree_name":["Doctor of Philosophy"],"thesis:institution_name":["Boston University"]},"updated_at":"2026-11-19T02:41:40Z"}