{"id":{"repo_id":"calgary","oai_identifier":"oai:ucalgary.scholaris.ca:11023/181"},"canonical_url":"https://search.ndltd.org/etd/calgary/oai:ucalgary.scholaris.ca:11023/181","repository":{"repo_id":"calgary","name":"University of Calgary","base_url":"https://ucalgary.scholaris.ca/server/oai/request"},"display":{"title":"Demand Controlled Ventilation: Use in Calgary and Impact of Sensor Location","abstract":"Demand controlled ventilation (DCV) is used to reduce the amount of energy required to condition outdoor air introduced into a building based by monitoring occupancy. This thesis reports the hours DCV is used in an existing building in Calgary. Results showed DCV was used approximately 20% of annual fan operating hours when paired with an air-side economizer and just over 60% when a heat recovery wheel was part of the system. A Simulink model was built to compare the performance of two currently used DCV approaches based on carbon dioxide readings (CO2-DCV). The model showed positioning a sensor in the supply air duct (SACO2-DCV) to serve multiple zones of a re-circulating system maintained lower CO2 levels when occupancy varied between rooms than if the sensor were in the return-air duct (RACO2-DCV). The model showed these lower CO2 levels were due to SACO2-DCV over-ventilating spaces relative to typical requirements.","abstract_html":"Demand controlled ventilation (DCV) is used to reduce the amount of energy required to condition outdoor air introduced into a building based by monitoring occupancy. This thesis reports the hours DCV is used in an existing building in Calgary. Results showed DCV was used approximately 20% of annual fan operating hours when paired with an air-side economizer and just over 60% when a heat recovery wheel was part of the system. A Simulink model was built to compare the performance of two currently used DCV approaches based on carbon dioxide readings (CO2-DCV). The model showed positioning a sensor in the supply air duct (SACO2-DCV) to serve multiple zones of a re-circulating system maintained lower CO2 levels when occupancy varied between rooms than if the sensor were in the return-air duct (RACO2-DCV). The model showed these lower CO2 levels were due to SACO2-DCV over-ventilating spaces relative to typical requirements.","abstract_has_math":false,"creators":["Lachapelle, Annie-Claude"],"institution":"Environmental Design","degree_name":"Master of Environmental Design (MEDes)","degree_level":null,"degree_discipline":null,"degree_department":null,"school":null,"contributors":[],"advisors":["Love, James A."],"committee_chairs":[],"committee_members":[],"year":2012,"date_issued":"2012-09-06","date_published":"2012-09-06","updated_at":"2026-11-19T07:36:41Z","subjects":["Energy"],"languages":["eng"],"rights":["University of Calgary graduate students retain copyright ownership and moral rights for their thesis. You may use this material in any way that is permitted by the Copyright Act or through licensing that has been assigned to the document. For uses that are not allowable under copyright legislation or licensing, you are required to seek permission."],"rights_urls":[],"identifier_entries":[{"key":"dc:identifier.uri","label":"Identifier URI","values":["http://hdl.handle.net/11023/181"],"render_values":[{"text":"http://hdl.handle.net/11023/181","href":"https://hdl.handle.net/11023/181","code":true}]}],"person_identifier_entries":[]},"links":{"outbound_url":"https://doi.org/10.11575/PRISM/25548","outbound_label":"DOI","outbound_source":"dc:identifier.doi","record_url":"https://doi.org/10.11575/PRISM/25548","record_label":"Repository record","record_kind":"doi","record_source":"dc:identifier.doi","access_status":null,"embargo_until":null,"access_note":null},"source_record":{"url":"https://ucalgary.scholaris.ca/server/oai/request?verb=GetRecord&metadataPrefix=dim&identifier=oai%3Aucalgary.scholaris.ca%3A11023%2F181","prefix":"dim"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor.advisor","label":"Advisor","values":["Love, James A."]},{"key":"dc:creator","label":"Author","values":["Lachapelle, Annie-Claude"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date.accessioned","label":"Dc Date Accessioned","values":["2012-09-07T00:30:33Z"]},{"key":"dc:date.available","label":"Dc Date Available","values":["2012-11-13T08:01:33Z"]},{"key":"dc:date.issued","label":"Date","values":["2012-09-06"]},{"key":"dc:date.submitted","label":"Dc Date Submitted","values":["2012"]},{"key":"dc:publisher.faculty","label":"Dc Publisher Faculty","values":["Environmental Design","Graduate Studies"]},{"key":"dc:publisher.institution","label":"Dc Publisher Institution","values":["University of Calgary"]},{"key":"dc:publisher.place","label":"Dc Publisher Place","values":["Calgary"]},{"key":"dc:type","label":"Dc Type","values":["master thesis"]},{"key":"thesis:degree_name","label":"Degree Name","values":["Master of Environmental Design (MEDes)"]},{"key":"thesis:institution_name","label":"Thesis Institution Name","values":["University of Calgary"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject","label":"Dc Subject","values":["Energy"]},{"key":"dc:subject.classification","label":"Dc Subject Classification","values":["Demand Controlled Ventilation","CO2 sensor","DOE2","Indoor Air Quality","Multiple zones"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:language.iso","label":"Language (ISO)","values":["eng"]},{"key":"dc:rights","label":"Dc Rights","values":["University of Calgary graduate students retain copyright ownership and moral rights for their thesis. You may use this material in any way that is permitted by the Copyright Act or through licensing that has been assigned to the document. For uses that are not allowable under copyright legislation or licensing, you are required to seek permission."]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier.citation","label":"Dc Identifier Citation","values":["Lachapelle, A. (2012). Demand Controlled Ventilation: Use in Calgary and Impact of Sensor Location (Master's thesis, University of Calgary, Calgary, Canada). Retrieved from https://prism.ucalgary.ca. doi:10.11575/PRISM/25548"]},{"key":"dc:identifier.doi","label":"DOI","values":["http://dx.doi.org/10.11575/PRISM/25548"]},{"key":"dc:identifier.uri","label":"Identifier URI","values":["http://hdl.handle.net/11023/181"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"atmire:migration.oldid","label":"Atmire Migration Oldid","values":["256"]},{"key":"dc:description.abstract","label":"Abstract","values":["Demand controlled ventilation (DCV) is used to reduce the amount of energy required to condition outdoor air introduced into a building based by monitoring occupancy. This thesis reports the hours DCV is used in an existing building in Calgary. Results showed DCV was used approximately 20% of annual fan operating hours when paired with an air-side economizer and just over 60% when a heat recovery wheel was part of the system. A Simulink model was built to compare the performance of two currently used DCV approaches based on carbon dioxide readings (CO2-DCV). The model showed positioning a sensor in the supply air duct (SACO2-DCV) to serve multiple zones of a re-circulating system maintained lower CO2 levels when occupancy varied between rooms than if the sensor were in the return-air duct (RACO2-DCV). The model showed these lower CO2 levels were due to SACO2-DCV over-ventilating spaces relative to typical requirements."]},{"key":"dc:title","label":"Title","values":["Demand Controlled Ventilation: Use in Calgary and Impact of Sensor Location"]},{"key":"dspace:entity.type","label":"Dspace Entity Type","values":["Publication"]},{"key":"local:request.copy","label":"Local Request Copy","values":["true"]},{"key":"others:access_status","label":"Others Access Status","values":["open.access"]}]}],"canonical_facts":{"atmire:migration.oldid":["256"],"dc:contributor.advisor":["Love, James A."],"dc:creator":["Lachapelle, Annie-Claude"],"dc:date.accessioned":["2012-09-07T00:30:33Z"],"dc:date.available":["2012-11-13T08:01:33Z"],"dc:date.issued":["2012-09-06"],"dc:date.submitted":["2012"],"dc:description.abstract":["Demand controlled ventilation (DCV) is used to reduce the amount of energy required to condition outdoor air introduced into a building based by monitoring occupancy. This thesis reports the hours DCV is used in an existing building in Calgary. Results showed DCV was used approximately 20% of annual fan operating hours when paired with an air-side economizer and just over 60% when a heat recovery wheel was part of the system. A Simulink model was built to compare the performance of two currently used DCV approaches based on carbon dioxide readings (CO2-DCV). The model showed positioning a sensor in the supply air duct (SACO2-DCV) to serve multiple zones of a re-circulating system maintained lower CO2 levels when occupancy varied between rooms than if the sensor were in the return-air duct (RACO2-DCV). The model showed these lower CO2 levels were due to SACO2-DCV over-ventilating spaces relative to typical requirements."],"dc:identifier.citation":["Lachapelle, A. (2012). Demand Controlled Ventilation: Use in Calgary and Impact of Sensor Location (Master's thesis, University of Calgary, Calgary, Canada). Retrieved from https://prism.ucalgary.ca. doi:10.11575/PRISM/25548"],"dc:identifier.doi":["http://dx.doi.org/10.11575/PRISM/25548"],"dc:identifier.uri":["http://hdl.handle.net/11023/181"],"dc:language.iso":["eng"],"dc:publisher.faculty":["Environmental Design","Graduate Studies"],"dc:publisher.institution":["University of Calgary"],"dc:publisher.place":["Calgary"],"dc:rights":["University of Calgary graduate students retain copyright ownership and moral rights for their thesis. You may use this material in any way that is permitted by the Copyright Act or through licensing that has been assigned to the document. For uses that are not allowable under copyright legislation or licensing, you are required to seek permission."],"dc:subject":["Energy"],"dc:subject.classification":["Demand Controlled Ventilation","CO2 sensor","DOE2","Indoor Air Quality","Multiple zones"],"dc:title":["Demand Controlled Ventilation: Use in Calgary and Impact of Sensor Location"],"dc:type":["master thesis"],"dspace:entity.type":["Publication"],"local:request.copy":["true"],"others:access_status":["open.access"],"thesis:degree_name":["Master of Environmental Design (MEDes)"],"thesis:institution_name":["University of Calgary"]},"updated_at":"2026-11-19T07:36:41Z"}