{"id":{"repo_id":"gatech","oai_identifier":"oai:repository.gatech.edu:1853/50282"},"canonical_url":"https://search.ndltd.org/etd/gatech/oai:repository.gatech.edu:1853/50282","repository":{"repo_id":"gatech","name":"Georgia Tech","base_url":"https://repository.gatech.edu/server/oai/request"},"display":{"title":"Two-phase flow and heat transfer in pin-fin enhanced micro-gaps","abstract":"In modern microprocessors, thermal management has become one of the main hurdles in continued performance enhancement. Cooling schemes utilizing single phase microfluidics have been investigated extensively for enhanced heat dissipation from microprocessors. However, two-phase fluidic cooling devices are becoming a promising approach, and are less understood. This study aims to examine two-phase flow and heat transfer within a pin-fin enhanced micro-gap. The pin-fin array covered an area of 1cm x 1cm and had a pin diameter, height and pitch of 150μm, 200μm and 225μm, respectively, (aspect ratio of 1.33). This study covers both uniformly and partially heated scenarios. The working fluid used was R245fa. The average heat transfer coefficient and high speed flow visualization results indicated a rapid transition to the annular flow regime with a strong dependence on heat flux. Also, unique, conically-shaped two-phase wakes were observed, demonstrating the lateral spreading capability of the pin-fin array geometry.","abstract_html":"In modern microprocessors, thermal management has become one of the main hurdles in continued performance enhancement. Cooling schemes utilizing single phase microfluidics have been investigated extensively for enhanced heat dissipation from microprocessors. However, two-phase fluidic cooling devices are becoming a promising approach, and are less understood. This study aims to examine two-phase flow and heat transfer within a pin-fin enhanced micro-gap. The pin-fin array covered an area of 1cm x 1cm and had a pin diameter, height and pitch of 150μm, 200μm and 225μm, respectively, (aspect ratio of 1.33). This study covers both uniformly and partially heated scenarios. The working fluid used was R245fa. The average heat transfer coefficient and high speed flow visualization results indicated a rapid transition to the annular flow regime with a strong dependence on heat flux. Also, unique, conically-shaped two-phase wakes were observed, demonstrating the lateral spreading capability of the pin-fin array geometry.","abstract_has_math":false,"creators":["Isaacs, Steven"],"institution":"Georgia Institute of Technology","degree_name":null,"degree_level":"Masters","degree_discipline":null,"degree_department":"Mechanical Engineering","school":null,"contributors":[],"advisors":["Joshi, Yogendra"],"committee_chairs":[],"committee_members":["Bakir, Muhannad","Fedorov, Andrei"],"year":2013,"date_issued":"2013-08-28","date_published":"2013-08-28","updated_at":"2026-11-19T04:13:46Z","subjects":["Two-phase","Micro-gap","Pin-fin","Heat Transmission","Three-dimensional integrated circuits","Microfluidics"],"languages":["en_US"],"rights":[],"rights_urls":[],"identifier_entries":[],"person_identifier_entries":[]},"links":{"outbound_url":"http://hdl.handle.net/1853/50282","outbound_label":"Handle","outbound_source":"dc:identifier.uri","record_url":"http://hdl.handle.net/1853/50282","record_label":"Repository record","record_kind":"handle","record_source":"dc:identifier.uri","download_url":null,"download_label":null,"download_source":null,"access_status":null,"embargo_until":null,"access_note":null},"source_record":{"url":"https://repository.gatech.edu/server/oai/request?verb=GetRecord&metadataPrefix=dim&identifier=oai%3Arepository.gatech.edu%3A1853%2F50282","prefix":"dim"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor.advisor","label":"Advisor","values":["Joshi, Yogendra"]},{"key":"dc:contributor.committeemember","label":"Committee Member","values":["Bakir, Muhannad","Fedorov, Andrei"]},{"key":"dc:contributor.department","label":"Department","values":["Mechanical Engineering"]},{"key":"dc:contributor.other","label":"Dc Contributor Other","values":["George W. Woodruff School of Mechanical Engineering","College of Engineering"]},{"key":"dc:creator","label":"Author","values":["Isaacs, Steven"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date.accessioned","label":"Dc Date Accessioned","values":["2014-01-13T16:21:57Z"]},{"key":"dc:date.available","label":"Dc Date Available","values":["2014-01-13T16:21:57Z"]},{"key":"dc:date.created","label":"Dc Date Created","values":["2013-12"]},{"key":"dc:date.issued","label":"Date","values":["2013-08-28"]},{"key":"dc:date.submitted","label":"Dc Date Submitted","values":["December 2013"]},{"key":"dc:date.updated","label":"Dc Date Updated","values":["2014-01-13T16:21:57Z"]},{"key":"dc:publisher","label":"Institution","values":["Georgia Institute of Technology"]},{"key":"dc:relation.advisorentity","label":"Dc Relation Advisorentity","values":["63ef328b-076b-44b7-92a9-0f7dd03fa1fa"]},{"key":"dc:relation.orgunit","label":"Dc Relation Orgunit","values":["c01ff908-c25f-439b-bf10-a074ed886bb7","7c022d60-21d5-497c-b552-95e489a06569"]},{"key":"dc:type","label":"Dc Type","values":["Text","Thesis"]},{"key":"thesis:degree_level","label":"Degree Level","values":["Masters"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject","label":"Dc Subject","values":["Two-phase","Micro-gap","Pin-fin"]},{"key":"dc:subject.lcsh","label":"Dc Subject Lcsh","values":["Heat Transmission","Three-dimensional integrated circuits","Microfluidics"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:language.iso","label":"Language (ISO)","values":["en_US"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier.uri","label":"Identifier URI","values":["http://hdl.handle.net/1853/50282"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description.abstract","label":"Abstract","values":["In modern microprocessors, thermal management has become one of the main hurdles in continued performance enhancement. Cooling schemes utilizing single phase microfluidics have been investigated extensively for enhanced heat dissipation from microprocessors. However, two-phase fluidic cooling devices are becoming a promising approach, and are less understood. This study aims to examine two-phase flow and heat transfer within a pin-fin enhanced micro-gap. The pin-fin array covered an area of 1cm x 1cm and had a pin diameter, height and pitch of 150μm, 200μm and 225μm, respectively, (aspect ratio of 1.33). This study covers both uniformly and partially heated scenarios. The working fluid used was R245fa. The average heat transfer coefficient and high speed flow visualization results indicated a rapid transition to the annular flow regime with a strong dependence on heat flux. Also, unique, conically-shaped two-phase wakes were observed, demonstrating the lateral spreading capability of the pin-fin array geometry."]},{"key":"dc:description.degree","label":"Dc Description Degree","values":["M.S."]},{"key":"dc:format.mimetype","label":"Dc Format Mimetype","values":["application/pdf"]},{"key":"dc:title","label":"Title","values":["Two-phase flow and heat transfer in pin-fin enhanced micro-gaps"]},{"key":"dspace:entity.type","label":"Dspace Entity Type","values":["Publication"]}]}],"canonical_facts":{"dc:contributor.advisor":["Joshi, Yogendra"],"dc:contributor.committeemember":["Bakir, Muhannad","Fedorov, Andrei"],"dc:contributor.department":["Mechanical Engineering"],"dc:contributor.other":["George W. Woodruff School of Mechanical Engineering","College of Engineering"],"dc:creator":["Isaacs, Steven"],"dc:date.accessioned":["2014-01-13T16:21:57Z"],"dc:date.available":["2014-01-13T16:21:57Z"],"dc:date.created":["2013-12"],"dc:date.issued":["2013-08-28"],"dc:date.submitted":["December 2013"],"dc:date.updated":["2014-01-13T16:21:57Z"],"dc:description.abstract":["In modern microprocessors, thermal management has become one of the main hurdles in continued performance enhancement. Cooling schemes utilizing single phase microfluidics have been investigated extensively for enhanced heat dissipation from microprocessors. However, two-phase fluidic cooling devices are becoming a promising approach, and are less understood. This study aims to examine two-phase flow and heat transfer within a pin-fin enhanced micro-gap. The pin-fin array covered an area of 1cm x 1cm and had a pin diameter, height and pitch of 150μm, 200μm and 225μm, respectively, (aspect ratio of 1.33). This study covers both uniformly and partially heated scenarios. The working fluid used was R245fa. The average heat transfer coefficient and high speed flow visualization results indicated a rapid transition to the annular flow regime with a strong dependence on heat flux. Also, unique, conically-shaped two-phase wakes were observed, demonstrating the lateral spreading capability of the pin-fin array geometry."],"dc:description.degree":["M.S."],"dc:format.mimetype":["application/pdf"],"dc:identifier.uri":["http://hdl.handle.net/1853/50282"],"dc:language.iso":["en_US"],"dc:publisher":["Georgia Institute of Technology"],"dc:relation.advisorentity":["63ef328b-076b-44b7-92a9-0f7dd03fa1fa"],"dc:relation.orgunit":["c01ff908-c25f-439b-bf10-a074ed886bb7","7c022d60-21d5-497c-b552-95e489a06569"],"dc:subject":["Two-phase","Micro-gap","Pin-fin"],"dc:subject.lcsh":["Heat Transmission","Three-dimensional integrated circuits","Microfluidics"],"dc:title":["Two-phase flow and heat transfer in pin-fin enhanced micro-gaps"],"dc:type":["Text","Thesis"],"dspace:entity.type":["Publication"],"thesis:degree_level":["Masters"]},"updated_at":"2026-11-19T04:13:46Z"}