{"id":{"repo_id":"gatech","oai_identifier":"oai:repository.gatech.edu:1853/67099"},"canonical_url":"https://search.ndltd.org/etd/gatech/oai:repository.gatech.edu:1853/67099","repository":{"repo_id":"gatech","name":"Georgia Tech","base_url":"https://repository.gatech.edu/server/oai/request"},"display":{"title":"Control Strategies for Piezoelectrically Actuated Fast Mechanical Disconnect Switches for Hybrid Circuit Breakers","abstract":"Piezoelectrically-actuated fast mechanical switches provide a low-loss conduction path in hybrid circuit breakers for medium-voltage, direct-current system protection. With the desired actuation performance being pushed towards the driving limit of the piezoelectric actuator, excessive vibration starts to dominate the underdamped travel curves of contact movements, which will lead to insulation failures and delayed operations in the fast mechanical switch. To improve underdamped responses into critically damped actuations, several switching motion control strategies have been proposed with active damping filters such as notch, lead and lag compensators in the closed-loop system. The switching motion controllers are built upon a vibrational dynamics model of a prestressed piezoelectric stack actuator with experimentally identified parameters. The controller tuning principles are derived to achieve optimized step responses with a minimized rising time down to 250 μs, a reduced undershoot around 10%, and a closed-loop control bandwidth up to 1760 Hz. The closed-loop simulation is performed to verify the performance of proposed switching motion controllers on both low-frequency external disturbance elimination and high-frequency internal vibration attenuation. According to the hardware implementation tests, the proposed control strategies have optimized the switching motions of a heavily loaded piezoelectric actuator with a 60% reduction in undershoot and a 45% reduction in settling time. At the same time, the sub-millisecond switching time has been preserved in the actively damped travel curves of this piezoelectric actuator. With optimized switching operations of the piezoelectric actuator, the overall fast mechanical switch can better serve the advanced hybrid circuit breakers to achieve reduced fault current and fault clearance time during circuit interruptions. Consequently, the overall medium-voltage direct-current systems can get better protected by the piezoelectrically-actuated fast mechanical switch.","abstract_html":"Piezoelectrically-actuated fast mechanical switches provide a low-loss conduction path in hybrid circuit breakers for medium-voltage, direct-current system protection. With the desired actuation performance being pushed towards the driving limit of the piezoelectric actuator, excessive vibration starts to dominate the underdamped travel curves of contact movements, which will lead to insulation failures and delayed operations in the fast mechanical switch. To improve underdamped responses into critically damped actuations, several switching motion control strategies have been proposed with active damping filters such as notch, lead and lag compensators in the closed-loop system. The switching motion controllers are built upon a vibrational dynamics model of a prestressed piezoelectric stack actuator with experimentally identified parameters. The controller tuning principles are derived to achieve optimized step responses with a minimized rising time down to 250 μs, a reduced undershoot around 10%, and a closed-loop control bandwidth up to 1760 Hz. The closed-loop simulation is performed to verify the performance of proposed switching motion controllers on both low-frequency external disturbance elimination and high-frequency internal vibration attenuation. According to the hardware implementation tests, the proposed control strategies have optimized the switching motions of a heavily loaded piezoelectric actuator with a 60% reduction in undershoot and a 45% reduction in settling time. At the same time, the sub-millisecond switching time has been preserved in the actively damped travel curves of this piezoelectric actuator. With optimized switching operations of the piezoelectric actuator, the overall fast mechanical switch can better serve the advanced hybrid circuit breakers to achieve reduced fault current and fault clearance time during circuit interruptions. Consequently, the overall medium-voltage direct-current systems can get better protected by the piezoelectrically-actuated fast mechanical switch.","abstract_has_math":false,"creators":["Xu, Chunmeng"],"institution":"Georgia Institute of Technology","degree_name":null,"degree_level":"Doctoral","degree_discipline":null,"degree_department":"Electrical and Computer Engineering","school":null,"contributors":[],"advisors":["Graber, Lukas"],"committee_chairs":[],"committee_members":["Saeedifard, Maryam","Grijalva, Santiago Carlos","Divan, Deepakraj M.","Steurer, Michael"],"year":2021,"date_issued":"2021-05-13","date_published":"2021-05-13","updated_at":"2026-11-19T05:00:43Z","subjects":["DC circuit breaker","hybrid circuit breaker","fast mechanical switch","piezoelectric actuator","Thomson coil actuator","motion control","active damping filter","travel curve"],"languages":["en_US"],"rights":[],"rights_urls":[],"identifier_entries":[],"person_identifier_entries":[]},"links":{"outbound_url":"http://hdl.handle.net/1853/67099","outbound_label":"Handle","outbound_source":"dc:identifier.uri","record_url":"http://hdl.handle.net/1853/67099","record_label":"Repository record","record_kind":"handle","record_source":"dc:identifier.uri","download_url":null,"download_label":null,"download_source":null,"access_status":null,"embargo_until":null,"access_note":null},"source_record":{"url":"https://repository.gatech.edu/server/oai/request?verb=GetRecord&metadataPrefix=dim&identifier=oai%3Arepository.gatech.edu%3A1853%2F67099","prefix":"dim"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor.advisor","label":"Advisor","values":["Graber, Lukas"]},{"key":"dc:contributor.committeemember","label":"Committee Member","values":["Saeedifard, Maryam","Grijalva, Santiago Carlos","Divan, Deepakraj M.","Steurer, Michael"]},{"key":"dc:contributor.department","label":"Department","values":["Electrical and Computer Engineering"]},{"key":"dc:contributor.other","label":"Dc Contributor Other","values":["School of Electrical and Computer Engineering","College of Engineering"]},{"key":"dc:creator","label":"Author","values":["Xu, Chunmeng"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date.accessioned","label":"Dc Date Accessioned","values":["2022-08-25T13:25:30Z"]},{"key":"dc:date.available","label":"Dc Date Available","values":["2022-08-25T13:25:30Z"]},{"key":"dc:date.created","label":"Dc Date Created","values":["2021-08"]},{"key":"dc:date.issued","label":"Date","values":["2021-05-13"]},{"key":"dc:date.submitted","label":"Dc Date Submitted","values":["August 2021"]},{"key":"dc:date.updated","label":"Dc Date Updated","values":["2022-08-25T13:25:30Z"]},{"key":"dc:publisher","label":"Institution","values":["Georgia Institute of Technology"]},{"key":"dc:relation.advisorentity","label":"Dc Relation Advisorentity","values":["ef92cc42-4de7-450b-a0a3-91822c1af6de"]},{"key":"dc:relation.ispartofseries","label":"Dc Relation Ispartofseries","values":["Doctor of Philosophy with a Major in Electrical and Computer Engineering"]},{"key":"dc:relation.orgunit","label":"Dc Relation Orgunit","values":["5b7adef2-447c-4270-b9fc-846bd76f80f2","7c022d60-21d5-497c-b552-95e489a06569"]},{"key":"dc:relation.seriesentity","label":"Dc Relation Seriesentity","values":["3890cd56-8ecf-424b-8074-8f5ebd8dbe15"]},{"key":"dc:type","label":"Dc Type","values":["Text","Dissertation"]},{"key":"thesis:degree_level","label":"Degree Level","values":["Doctoral"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject","label":"Dc Subject","values":["DC circuit breaker","hybrid circuit breaker","fast mechanical switch","piezoelectric actuator","Thomson coil actuator","motion control","active damping filter","travel curve"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:language.iso","label":"Language (ISO)","values":["en_US"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier.uri","label":"Identifier URI","values":["http://hdl.handle.net/1853/67099"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description.abstract","label":"Abstract","values":["Piezoelectrically-actuated fast mechanical switches provide a low-loss conduction path in hybrid circuit breakers for medium-voltage, direct-current system protection. With the desired actuation performance being pushed towards the driving limit of the piezoelectric actuator, excessive vibration starts to dominate the underdamped travel curves of contact movements, which will lead to insulation failures and delayed operations in the fast mechanical switch. To improve underdamped responses into critically damped actuations, several switching motion control strategies have been proposed with active damping filters such as notch, lead and lag compensators in the closed-loop system. The switching motion controllers are built upon a vibrational dynamics model of a prestressed piezoelectric stack actuator with experimentally identified parameters. The controller tuning principles are derived to achieve optimized step responses with a minimized rising time down to 250 μs, a reduced undershoot around 10%, and a closed-loop control bandwidth up to 1760 Hz. The closed-loop simulation is performed to verify the performance of proposed switching motion controllers on both low-frequency external disturbance elimination and high-frequency internal vibration attenuation. According to the hardware implementation tests, the proposed control strategies have optimized the switching motions of a heavily loaded piezoelectric actuator with a 60% reduction in undershoot and a 45% reduction in settling time. At the same time, the sub-millisecond switching time has been preserved in the actively damped travel curves of this piezoelectric actuator. With optimized switching operations of the piezoelectric actuator, the overall fast mechanical switch can better serve the advanced hybrid circuit breakers to achieve reduced fault current and fault clearance time during circuit interruptions. Consequently, the overall medium-voltage direct-current systems can get better protected by the piezoelectrically-actuated fast mechanical switch."]},{"key":"dc:description.degree","label":"Dc Description Degree","values":["Ph.D."]},{"key":"dc:format.mimetype","label":"Dc Format Mimetype","values":["application/pdf"]},{"key":"dc:title","label":"Title","values":["Control Strategies for Piezoelectrically Actuated Fast Mechanical Disconnect Switches for Hybrid Circuit Breakers"]},{"key":"dspace:entity.type","label":"Dspace Entity Type","values":["Publication"]}]}],"canonical_facts":{"dc:contributor.advisor":["Graber, Lukas"],"dc:contributor.committeemember":["Saeedifard, Maryam","Grijalva, Santiago Carlos","Divan, Deepakraj M.","Steurer, Michael"],"dc:contributor.department":["Electrical and Computer Engineering"],"dc:contributor.other":["School of Electrical and Computer Engineering","College of Engineering"],"dc:creator":["Xu, Chunmeng"],"dc:date.accessioned":["2022-08-25T13:25:30Z"],"dc:date.available":["2022-08-25T13:25:30Z"],"dc:date.created":["2021-08"],"dc:date.issued":["2021-05-13"],"dc:date.submitted":["August 2021"],"dc:date.updated":["2022-08-25T13:25:30Z"],"dc:description.abstract":["Piezoelectrically-actuated fast mechanical switches provide a low-loss conduction path in hybrid circuit breakers for medium-voltage, direct-current system protection. With the desired actuation performance being pushed towards the driving limit of the piezoelectric actuator, excessive vibration starts to dominate the underdamped travel curves of contact movements, which will lead to insulation failures and delayed operations in the fast mechanical switch. To improve underdamped responses into critically damped actuations, several switching motion control strategies have been proposed with active damping filters such as notch, lead and lag compensators in the closed-loop system. The switching motion controllers are built upon a vibrational dynamics model of a prestressed piezoelectric stack actuator with experimentally identified parameters. The controller tuning principles are derived to achieve optimized step responses with a minimized rising time down to 250 μs, a reduced undershoot around 10%, and a closed-loop control bandwidth up to 1760 Hz. The closed-loop simulation is performed to verify the performance of proposed switching motion controllers on both low-frequency external disturbance elimination and high-frequency internal vibration attenuation. According to the hardware implementation tests, the proposed control strategies have optimized the switching motions of a heavily loaded piezoelectric actuator with a 60% reduction in undershoot and a 45% reduction in settling time. At the same time, the sub-millisecond switching time has been preserved in the actively damped travel curves of this piezoelectric actuator. With optimized switching operations of the piezoelectric actuator, the overall fast mechanical switch can better serve the advanced hybrid circuit breakers to achieve reduced fault current and fault clearance time during circuit interruptions. Consequently, the overall medium-voltage direct-current systems can get better protected by the piezoelectrically-actuated fast mechanical switch."],"dc:description.degree":["Ph.D."],"dc:format.mimetype":["application/pdf"],"dc:identifier.uri":["http://hdl.handle.net/1853/67099"],"dc:language.iso":["en_US"],"dc:publisher":["Georgia Institute of Technology"],"dc:relation.advisorentity":["ef92cc42-4de7-450b-a0a3-91822c1af6de"],"dc:relation.ispartofseries":["Doctor of Philosophy with a Major in Electrical and Computer Engineering"],"dc:relation.orgunit":["5b7adef2-447c-4270-b9fc-846bd76f80f2","7c022d60-21d5-497c-b552-95e489a06569"],"dc:relation.seriesentity":["3890cd56-8ecf-424b-8074-8f5ebd8dbe15"],"dc:subject":["DC circuit breaker","hybrid circuit breaker","fast mechanical switch","piezoelectric actuator","Thomson coil actuator","motion control","active damping filter","travel curve"],"dc:title":["Control Strategies for Piezoelectrically Actuated Fast Mechanical Disconnect Switches for Hybrid Circuit Breakers"],"dc:type":["Text","Dissertation"],"dspace:entity.type":["Publication"],"thesis:degree_level":["Doctoral"]},"updated_at":"2026-11-19T05:00:43Z"}