{"id":{"repo_id":"iastate","oai_identifier":"oai:dr.lib.iastate.edu:20.500.12876/64555"},"canonical_url":"https://search.ndltd.org/etd/iastate/oai:dr.lib.iastate.edu:20.500.12876/64555","repository":{"repo_id":"iastate","name":"Iowa State University","base_url":"https://dr.lib.iastate.edu/server/oai/request"},"display":{"title":"The effect of liquid inundation, vapor shear, and non-condensible gases on the condensation of refrigerants HFC-134a and HCFC-123","abstract":"<p>Shell-side condensation heat transfer data were obtained for refrigerants HFC-134a and HCFC-123, the scheduled non-CFC replacements for CFC-12 and CFC-11, respectively, using tube bundles constructed from 19.1 mm o.d. 26-fpi, 40-fpi, Turbo C-II, and GEWA SC tubes. HCFC-123 bundle data were obtained for non-condensible gas concentrations of 0.5, 1.0, 2.0, and 5.0% at four heat fluxes between 18,000 W/m2 and 34,000 W/m2. HCFC-123 vapor shear and liquid inundation studies were also conducted to simulate bundle depths of 25 tube rows at heat fluxes ranging from 17,500-31,000 W/m2 and vapor velocities between 2.5 and 4.5 m/s. Liquid inundation tests with HFC-134a were conducted to simulate bundle depths up to 30 rows at heat fluxes between 26,000 and 56,000 W/m2. All tests were conducted at a refrigerant saturation temperature of 35∘C;The Turbo C-II generally performed the best at non-condensible gas concentrations up to 5.0%, followed by the 40-fpi, GEWA SC and 26-fpi geometries. The Turbo C-II was also found to be the most susceptible to even small gas concentrations (0.5%), with drops in average bundle heat transfer coefficients of 50% and 35% at the lowest heat flux (20 kW/m2) and highest heat flux (34 kW/m2) respectively. Row-by-row data showed that non-condensibles work to smooth out individual row performance, so that at the highest gas concentrations all rows within a bundle perform very similarly. High concentrations of nitrogen also cause the different bundles to perform similarly, within approximately 13% of each other. Vapor shearing effects in the non-condensible gas layer were found to have a large effect with all tube geometries, particularly at the highest heat fluxes;In inundation with HFC-134a, the Turbo C-II had the highest heat transfer coefficients, followed by the GEWA SC, the 40-fpi, and the 26-fpi tubes. At the lowest inundation rates the Turbo C-II heat transfer performance was approximately 2.5 times that of the GEWA SC and more than four times that of the 26-fpi. However, at the highest inundation rates the Turbo C-II performed almost equally to the GEWA SC and differed from the other tubes by less than 10%;Inundation with HFC-134a had very little effect on those tubes with continuous fins, particularly the 26-fpi and the GEWA SC. The Turbo C-II was most affected by HFC-134a inundation, with heat transfer coefficients dropping nearly 80% through a Reynolds number of 2900;The inundation effects are much more pronounced with HCFC-123 than with HFC-134a. The Turbo C-II performance dropped nearly 80% from the lowest to the highest condensate Reynolds numbers. Decreases of approximately 20%, 20%, and 45% were seen for the 26-fpi, 40-fpi, and GEWA SC tubes, respectively, over the same test range. (Abstract shortened by UMI.)</p>","abstract_html":"&lt;p&gt;Shell-side condensation heat transfer data were obtained for refrigerants HFC-134a and HCFC-123, the scheduled non-CFC replacements for CFC-12 and CFC-11, respectively, using tube bundles constructed from 19.1 mm o.d. 26-fpi, 40-fpi, Turbo C-II, and GEWA SC tubes. HCFC-123 bundle data were obtained for non-condensible gas concentrations of 0.5, 1.0, 2.0, and 5.0% at four heat fluxes between 18,000 W/m2 and 34,000 W/m2. HCFC-123 vapor shear and liquid inundation studies were also conducted to simulate bundle depths of 25 tube rows at heat fluxes ranging from 17,500-31,000 W/m2 and vapor velocities between 2.5 and 4.5 m/s. Liquid inundation tests with HFC-134a were conducted to simulate bundle depths up to 30 rows at heat fluxes between 26,000 and 56,000 W/m2. All tests were conducted at a refrigerant saturation temperature of 35∘C;The Turbo C-II generally performed the best at non-condensible gas concentrations up to 5.0%, followed by the 40-fpi, GEWA SC and 26-fpi geometries. The Turbo C-II was also found to be the most susceptible to even small gas concentrations (0.5%), with drops in average bundle heat transfer coefficients of 50% and 35% at the lowest heat flux (20 kW/m2) and highest heat flux (34 kW/m2) respectively. Row-by-row data showed that non-condensibles work to smooth out individual row performance, so that at the highest gas concentrations all rows within a bundle perform very similarly. High concentrations of nitrogen also cause the different bundles to perform similarly, within approximately 13% of each other. Vapor shearing effects in the non-condensible gas layer were found to have a large effect with all tube geometries, particularly at the highest heat fluxes;In inundation with HFC-134a, the Turbo C-II had the highest heat transfer coefficients, followed by the GEWA SC, the 40-fpi, and the 26-fpi tubes. At the lowest inundation rates the Turbo C-II heat transfer performance was approximately 2.5 times that of the GEWA SC and more than four times that of the 26-fpi. However, at the highest inundation rates the Turbo C-II performed almost equally to the GEWA SC and differed from the other tubes by less than 10%;Inundation with HFC-134a had very little effect on those tubes with continuous fins, particularly the 26-fpi and the GEWA SC. The Turbo C-II was most affected by HFC-134a inundation, with heat transfer coefficients dropping nearly 80% through a Reynolds number of 2900;The inundation effects are much more pronounced with HCFC-123 than with HFC-134a. The Turbo C-II performance dropped nearly 80% from the lowest to the highest condensate Reynolds numbers. Decreases of approximately 20%, 20%, and 45% were seen for the 26-fpi, 40-fpi, and GEWA SC tubes, respectively, over the same test range. (Abstract shortened by UMI.)&lt;/p&gt;","abstract_has_math":false,"creators":["Rewerts, Lance"],"institution":null,"degree_name":"Doctor of Philosophy","degree_level":"dissertation","degree_discipline":null,"degree_department":"Department of Mechanical Engineering","school":null,"contributors":[],"advisors":["Michael Pate"],"committee_chairs":[],"committee_members":[],"year":1994,"date_issued":"1994","date_published":"1994","updated_at":"2026-11-19T04:37:40Z","subjects":[],"languages":["en"],"rights":[],"rights_urls":[],"identifier_entries":[{"key":"dc:identifier.uri","label":"Identifier URI","values":["https://dr.lib.iastate.edu/handle/20.500.12876/64555"],"render_values":[{"text":"https://dr.lib.iastate.edu/handle/20.500.12876/64555","href":"https://dr.lib.iastate.edu/handle/20.500.12876/64555","code":true}]},{"key":"dc:identifier","label":"Identifier","values":["archive/lib.dr.iastate.edu/rtd/11311/"],"render_values":[{"text":"archive/lib.dr.iastate.edu/rtd/11311/","href":null,"code":true}]},{"key":"dc:identifier.other","label":"Dc Identifier Other","values":["12310","6453557"],"render_values":[{"text":"12310","href":null,"code":true},{"text":"6453557","href":null,"code":true}]},{"key":"mods:identifier.filename","label":"Mods Identifier Filename","values":["archive/lib.dr.iastate.edu/rtd/11311/r_9518434.pdf|||Fri Jan 14 18:47:33 UTC 2022"],"render_values":[{"text":"archive/lib.dr.iastate.edu/rtd/11311/r_9518434.pdf|||Fri Jan 14 18:47:33 UTC 2022","href":null,"code":true}]}],"person_identifier_entries":[]},"links":{"outbound_url":"https://doi.org/10.31274/rtd-180813-12923","outbound_label":"DOI","outbound_source":"dc:identifier.doi","record_url":"https://doi.org/10.31274/rtd-180813-12923","record_label":"Repository record","record_kind":"doi","record_source":"dc:identifier.doi","access_status":null,"embargo_until":null,"access_note":null},"oai_pmh_record":{"url":"https://union.ndltd.org/oai-pmh/?verb=GetRecord&metadataPrefix=oai_dc&identifier=oai%3Aunion.ndltd.org%3Arepo%3Aiastate%3Aoai%3Adr.lib.iastate.edu%3A20.500.12876%2F64555","prefix":"oai_dc"},"source_record":{"url":"https://dr.lib.iastate.edu/server/oai/request?verb=GetRecord&metadataPrefix=dim&identifier=oai%3Adr.lib.iastate.edu%3A20.500.12876%2F64555","prefix":"dim"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor.advisor","label":"Advisor","values":["Michael Pate"]},{"key":"dc:contributor.department","label":"Department","values":["Department of Mechanical Engineering"]},{"key":"dc:creator","label":"Author","values":["Rewerts, Lance"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date","label":"Dc Date","values":["2018-08-23T17:52:09.000"]},{"key":"dc:date.accessioned","label":"Dc Date Accessioned","values":["2020-06-30T07:11:54Z"]},{"key":"dc:date.available","label":"Dc Date Available","values":["2020-06-30T07:11:54Z"]},{"key":"dc:date.copyright","label":"Dc Date Copyright","values":["Sat Jan 01 00:00:00 UTC 1994"]},{"key":"dc:date.issued","label":"Date","values":["1994"]},{"key":"dc:relation.orgunit","label":"Dc Relation Orgunit","values":["6d38ab0f-8cc2-4ad3-90b1-67a60c5a6f59"]},{"key":"dc:type","label":"Dc Type","values":["dissertation"]},{"key":"thesis:degree_level","label":"Degree Level","values":["dissertation"]},{"key":"thesis:degree_name","label":"Degree Name","values":["Doctor of Philosophy"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject.discipline","label":"Dc Subject Discipline","values":["Mechanical Engineering"]},{"key":"dc:subject.keyword","label":"Dc Subject Keyword","values":["Mechanical engineering"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:language.iso","label":"Language (ISO)","values":["en"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier","label":"Identifier","values":["archive/lib.dr.iastate.edu/rtd/11311/"]},{"key":"dc:identifier.doi","label":"DOI","values":["https://doi.org/10.31274/rtd-180813-12923"]},{"key":"dc:identifier.other","label":"Dc Identifier Other","values":["12310","6453557"]},{"key":"dc:identifier.uri","label":"Identifier URI","values":["https://dr.lib.iastate.edu/handle/20.500.12876/64555"]},{"key":"mods:identifier.filename","label":"Mods Identifier Filename","values":["archive/lib.dr.iastate.edu/rtd/11311/r_9518434.pdf|||Fri Jan 14 18:47:33 UTC 2022"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description.abstract","label":"Abstract","values":["<p>Shell-side condensation heat transfer data were obtained for refrigerants HFC-134a and HCFC-123, the scheduled non-CFC replacements for CFC-12 and CFC-11, respectively, using tube bundles constructed from 19.1 mm o.d. 26-fpi, 40-fpi, Turbo C-II, and GEWA SC tubes. HCFC-123 bundle data were obtained for non-condensible gas concentrations of 0.5, 1.0, 2.0, and 5.0% at four heat fluxes between 18,000 W/m2 and 34,000 W/m2. HCFC-123 vapor shear and liquid inundation studies were also conducted to simulate bundle depths of 25 tube rows at heat fluxes ranging from 17,500-31,000 W/m2 and vapor velocities between 2.5 and 4.5 m/s. Liquid inundation tests with HFC-134a were conducted to simulate bundle depths up to 30 rows at heat fluxes between 26,000 and 56,000 W/m2. All tests were conducted at a refrigerant saturation temperature of 35∘C;The Turbo C-II generally performed the best at non-condensible gas concentrations up to 5.0%, followed by the 40-fpi, GEWA SC and 26-fpi geometries. The Turbo C-II was also found to be the most susceptible to even small gas concentrations (0.5%), with drops in average bundle heat transfer coefficients of 50% and 35% at the lowest heat flux (20 kW/m2) and highest heat flux (34 kW/m2) respectively. Row-by-row data showed that non-condensibles work to smooth out individual row performance, so that at the highest gas concentrations all rows within a bundle perform very similarly. High concentrations of nitrogen also cause the different bundles to perform similarly, within approximately 13% of each other. Vapor shearing effects in the non-condensible gas layer were found to have a large effect with all tube geometries, particularly at the highest heat fluxes;In inundation with HFC-134a, the Turbo C-II had the highest heat transfer coefficients, followed by the GEWA SC, the 40-fpi, and the 26-fpi tubes. At the lowest inundation rates the Turbo C-II heat transfer performance was approximately 2.5 times that of the GEWA SC and more than four times that of the 26-fpi. However, at the highest inundation rates the Turbo C-II performed almost equally to the GEWA SC and differed from the other tubes by less than 10%;Inundation with HFC-134a had very little effect on those tubes with continuous fins, particularly the 26-fpi and the GEWA SC. The Turbo C-II was most affected by HFC-134a inundation, with heat transfer coefficients dropping nearly 80% through a Reynolds number of 2900;The inundation effects are much more pronounced with HCFC-123 than with HFC-134a. The Turbo C-II performance dropped nearly 80% from the lowest to the highest condensate Reynolds numbers. Decreases of approximately 20%, 20%, and 45% were seen for the 26-fpi, 40-fpi, and GEWA SC tubes, respectively, over the same test range. (Abstract shortened by UMI.)</p>"]},{"key":"dc:format.mimetype","label":"Dc Format Mimetype","values":["application/pdf"]},{"key":"dc:title","label":"Title","values":["The effect of liquid inundation, vapor shear, and non-condensible gases on the condensation of refrigerants HFC-134a and HCFC-123"]},{"key":"dspace:entity.type","label":"Dspace Entity Type","values":["Publication"]},{"key":"local:admin","label":"Local Admin","values":["isulib-bepress-aws-west","rtd/11311"]}]}],"canonical_facts":{"dc:contributor.advisor":["Michael Pate"],"dc:contributor.department":["Department of Mechanical Engineering"],"dc:creator":["Rewerts, Lance"],"dc:date":["2018-08-23T17:52:09.000"],"dc:date.accessioned":["2020-06-30T07:11:54Z"],"dc:date.available":["2020-06-30T07:11:54Z"],"dc:date.copyright":["Sat Jan 01 00:00:00 UTC 1994"],"dc:date.issued":["1994"],"dc:description.abstract":["<p>Shell-side condensation heat transfer data were obtained for refrigerants HFC-134a and HCFC-123, the scheduled non-CFC replacements for CFC-12 and CFC-11, respectively, using tube bundles constructed from 19.1 mm o.d. 26-fpi, 40-fpi, Turbo C-II, and GEWA SC tubes. HCFC-123 bundle data were obtained for non-condensible gas concentrations of 0.5, 1.0, 2.0, and 5.0% at four heat fluxes between 18,000 W/m2 and 34,000 W/m2. HCFC-123 vapor shear and liquid inundation studies were also conducted to simulate bundle depths of 25 tube rows at heat fluxes ranging from 17,500-31,000 W/m2 and vapor velocities between 2.5 and 4.5 m/s. Liquid inundation tests with HFC-134a were conducted to simulate bundle depths up to 30 rows at heat fluxes between 26,000 and 56,000 W/m2. All tests were conducted at a refrigerant saturation temperature of 35∘C;The Turbo C-II generally performed the best at non-condensible gas concentrations up to 5.0%, followed by the 40-fpi, GEWA SC and 26-fpi geometries. The Turbo C-II was also found to be the most susceptible to even small gas concentrations (0.5%), with drops in average bundle heat transfer coefficients of 50% and 35% at the lowest heat flux (20 kW/m2) and highest heat flux (34 kW/m2) respectively. Row-by-row data showed that non-condensibles work to smooth out individual row performance, so that at the highest gas concentrations all rows within a bundle perform very similarly. High concentrations of nitrogen also cause the different bundles to perform similarly, within approximately 13% of each other. Vapor shearing effects in the non-condensible gas layer were found to have a large effect with all tube geometries, particularly at the highest heat fluxes;In inundation with HFC-134a, the Turbo C-II had the highest heat transfer coefficients, followed by the GEWA SC, the 40-fpi, and the 26-fpi tubes. At the lowest inundation rates the Turbo C-II heat transfer performance was approximately 2.5 times that of the GEWA SC and more than four times that of the 26-fpi. However, at the highest inundation rates the Turbo C-II performed almost equally to the GEWA SC and differed from the other tubes by less than 10%;Inundation with HFC-134a had very little effect on those tubes with continuous fins, particularly the 26-fpi and the GEWA SC. The Turbo C-II was most affected by HFC-134a inundation, with heat transfer coefficients dropping nearly 80% through a Reynolds number of 2900;The inundation effects are much more pronounced with HCFC-123 than with HFC-134a. The Turbo C-II performance dropped nearly 80% from the lowest to the highest condensate Reynolds numbers. Decreases of approximately 20%, 20%, and 45% were seen for the 26-fpi, 40-fpi, and GEWA SC tubes, respectively, over the same test range. (Abstract shortened by UMI.)</p>"],"dc:format.mimetype":["application/pdf"],"dc:identifier":["archive/lib.dr.iastate.edu/rtd/11311/"],"dc:identifier.doi":["https://doi.org/10.31274/rtd-180813-12923"],"dc:identifier.other":["12310","6453557"],"dc:identifier.uri":["https://dr.lib.iastate.edu/handle/20.500.12876/64555"],"dc:language.iso":["en"],"dc:relation.orgunit":["6d38ab0f-8cc2-4ad3-90b1-67a60c5a6f59"],"dc:subject.discipline":["Mechanical Engineering"],"dc:subject.keyword":["Mechanical engineering"],"dc:title":["The effect of liquid inundation, vapor shear, and non-condensible gases on the condensation of refrigerants HFC-134a and HCFC-123"],"dc:type":["dissertation"],"dspace:entity.type":["Publication"],"local:admin":["isulib-bepress-aws-west","rtd/11311"],"mods:identifier.filename":["archive/lib.dr.iastate.edu/rtd/11311/r_9518434.pdf|||Fri Jan 14 18:47:33 UTC 2022"],"thesis:degree_level":["dissertation"],"thesis:degree_name":["Doctor of Philosophy"]},"updated_at":"2026-11-19T04:37:40Z"}