{"id":{"repo_id":"mit","oai_identifier":"oai:dspace.mit.edu:1721.1/77046"},"canonical_url":"https://search.ndltd.org/etd/mit/oai:dspace.mit.edu:1721.1/77046","repository":{"repo_id":"mit","name":"MIT","base_url":"https://dspace.mit.edu/oai/request"},"display":{"title":"Off peak cooling using an ice storage system","abstract":"The electric utilities in the United States have entered a period of slow growth due to a combination of increased capital costs and a staggering rise in the costs for fuel. In addition to this, the rise in peak power demand continues almost at historical levels resulting in lower plant utilization. Current rate schedules do little to improve the utilities' load factors and,in fact, encourage consumption. Time of day rate structures have been suggested as one load management device. This thesis investigates the impact of commercial cooling systems on the utilities supply picture and describes an off-peak cooling system which would enable a building operator to shift chiller operation to off-peak hours. The chillers draw heat from a water/glycol coolant, cooling it to 20°F. The coolant circulates through a series of coiled pipes inside a water filled storage tank. As heat is drawn from the water, ice forms around the pipe heat exchanger. With a cool ant temperature of 20°F the ice cylinder will form out to a diameter of 3.4\" in 10 hours. Optimum pipe spacing is 3.5\" on center. Polyethylene pipe is preferred to copper pipe for cost and fabrication reasons. The plastic pipes are grouped in discrete modules which allow flexibility in design. Building cooling loads are managed by circulating the remaining 32°F tank water through a heat exchanger coupled to the air handling units cooling coils. The warm water is returned to the tank where the heat is absorbed by the ice. Economic analysis using the present electric schedules indicate a favorable return on investment Time of day rates would make the system look even more desirable.","abstract_html":"The electric utilities in the United States have entered a period of slow growth due to a combination of increased capital costs and a staggering rise in the costs for fuel. In addition to this, the rise in peak power demand continues almost at historical levels resulting in lower plant utilization. Current rate schedules do little to improve the utilities&#x27; load factors and,in fact, encourage consumption. Time of day rate structures have been suggested as one load management device. This thesis investigates the impact of commercial cooling systems on the utilities supply picture and describes an off-peak cooling system which would enable a building operator to shift chiller operation to off-peak hours. The chillers draw heat from a water/glycol coolant, cooling it to 20°F. The coolant circulates through a series of coiled pipes inside a water filled storage tank. As heat is drawn from the water, ice forms around the pipe heat exchanger. With a cool ant temperature of 20°F the ice cylinder will form out to a diameter of 3.4&quot; in 10 hours. Optimum pipe spacing is 3.5&quot; on center. Polyethylene pipe is preferred to copper pipe for cost and fabrication reasons. The plastic pipes are grouped in discrete modules which allow flexibility in design. Building cooling loads are managed by circulating the remaining 32°F tank water through a heat exchanger coupled to the air handling units cooling coils. The warm water is returned to the tank where the heat is absorbed by the ice. Economic analysis using the present electric schedules indicate a favorable return on investment Time of day rates would make the system look even more desirable.","abstract_has_math":false,"creators":["Quinlan, Edward Michael"],"institution":"Massachusetts Institute of Technology","degree_name":null,"degree_level":null,"degree_discipline":null,"degree_department":null,"school":null,"contributors":[],"advisors":["Timothy E. Johnson."],"committee_chairs":[],"committee_members":[],"year":1980,"date_issued":"1980","date_published":"1980","updated_at":"2026-11-29T16:52:07Z","subjects":["Architecture","Power resources","Heating","Ventilation","Electric utilities Rates"],"languages":["en"],"rights":["M.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission."],"rights_urls":["http://dspace.mit.edu/handle/1721.1/7582"],"identifier_entries":[{"key":"dc:identifier.oclc","label":"OCLC","values":["07441136"],"render_values":[{"text":"07441136","href":null,"code":true}]}],"person_identifier_entries":[]},"links":{"outbound_url":"https://hdl.handle.net/1721.1/77046","outbound_label":"Handle","outbound_source":"dc:identifier.uri","record_url":"https://hdl.handle.net/1721.1/77046","record_label":"Repository record","record_kind":"handle","record_source":"dc:identifier.uri","access_status":null,"embargo_until":null,"access_note":null},"oai_pmh_record":{"url":"https://union.ndltd.org/oai-pmh/?verb=GetRecord&metadataPrefix=oai_dc&identifier=oai%3Aunion.ndltd.org%3Arepo%3Amit%3Aoai%3Adspace.mit.edu%3A1721.1%2F77046","prefix":"oai_dc"},"source_record":{"url":"https://dspace.mit.edu/oai/request?verb=GetRecord&metadataPrefix=dim&identifier=oai%3Adspace.mit.edu%3A1721.1%2F77046","prefix":"dim"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor.advisor","label":"Advisor","values":["Timothy E. Johnson."]},{"key":"dc:creator","label":"Author","values":["Quinlan, Edward Michael"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:coverage.spatial","label":"Dc Coverage Spatial","values":["n-us---"]},{"key":"dc:date.accessioned","label":"Dc Date Accessioned","values":["2013-02-14T19:12:40Z"]},{"key":"dc:date.available","label":"Dc Date Available","values":["2013-02-14T19:12:40Z"]},{"key":"dc:date.copyright","label":"Dc Date Copyright","values":["1980"]},{"key":"dc:date.issued","label":"Date","values":["1980"]},{"key":"dc:publisher","label":"Institution","values":["Massachusetts Institute of Technology"]},{"key":"dc:type","label":"Dc Type","values":["Thesis"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject","label":"Dc Subject","values":["Architecture"]},{"key":"dc:subject.lcsh","label":"Dc Subject Lcsh","values":["Power resources","Heating","Ventilation","Electric utilities Rates"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:language.iso","label":"Language (ISO)","values":["en"]},{"key":"dc:rights","label":"Dc Rights","values":["M.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission."]},{"key":"dc:rights.uri","label":"Rights URI","values":["http://dspace.mit.edu/handle/1721.1/7582"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier.oclc","label":"OCLC","values":["07441136"]},{"key":"dc:identifier.uri","label":"Identifier URI","values":["http://hdl.handle.net/1721.1/77046"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"cerif:openaire","label":"Cerif Openaire","values":["<Publication xmlns=\"https://www.openaire.eu/cerif-profile/1.1/\" id=\"87823786-04d5-40cb-bb73-49d97eb481cf\"> <Type xmlns=\"https://www.openaire.eu/cerif-profile/vocab/COAR_Publication_Types\">http://purl.org/coar/resource_type/c_1843</Type> <Language>en</Language> <Title>Off peak cooling using an ice storage system</Title> <PublishedIn> <Publication> </Publication> </PublishedIn> <PublicationDate>1980</PublicationDate> <Authors> <Author> <DisplayName>Quinlan, Edward Michael</DisplayName> <Affiliation> <OrgUnit> </OrgUnit> </Affiliation> </Author> </Authors> <Editors> </Editors> <Publishers> <Publisher> <DisplayName>Massachusetts Institute of Technology</DisplayName> <OrgUnit /> </Publisher> </Publishers> <License>http://dspace.mit.edu/handle/1721.1/7582</License> <Keyword>Architecture</Keyword> <Abstract>The electric utilities in the United States have entered a period of slow growth due to a combination of increased capital costs and a staggering rise in the costs for fuel. In addition to this, the rise in peak power demand continues almost at historical levels resulting in lower plant utilization. Current rate schedules do little to improve the utilities' load factors and,in fact, encourage consumption. Time of day rate structures have been suggested as one load management device. This thesis investigates the impact of commercial cooling systems on the utilities supply picture and describes an off-peak cooling system which would enable a building operator to shift chiller operation to off-peak hours. The chillers draw heat from a water/glycol coolant, cooling it to 20°F. The coolant circulates through a series of coiled pipes inside a water filled storage tank. As heat is drawn from the water, ice forms around the pipe heat exchanger. With a cool ant temperature of 20°F the ice cylinder will form out to a diameter of 3.4\" in 10 hours. Optimum pipe spacing is 3.5\" on center. Polyethylene pipe is preferred to copper pipe for cost and fabrication reasons. The plastic pipes are grouped in discrete modules which allow flexibility in design. Building cooling loads are managed by circulating the remaining 32°F tank water through a heat exchanger coupled to the air handling units cooling coils. The warm water is returned to the tank where the heat is absorbed by the ice. Economic analysis using the present electric schedules indicate a favorable return on investment Time of day rates would make the system look even more desirable.</Abstract> <Access xmlns=\"http://purl.org/coar/access_right\" > </Access> </Publication>"]},{"key":"dc:description","label":"Description","values":["Thesis (M.S.)--Massachusetts Institute of Technology, Dept. of Architecture, 1980.","MICROFICHE COPY AVAILABLE IN ARCHIVES AND ROTCH.","Includes bibliographical references."]},{"key":"dc:description.abstract","label":"Abstract","values":["The electric utilities in the United States have entered a period of slow growth due to a combination of increased capital costs and a staggering rise in the costs for fuel. In addition to this, the rise in peak power demand continues almost at historical levels resulting in lower plant utilization. Current rate schedules do little to improve the utilities' load factors and,in fact, encourage consumption. Time of day rate structures have been suggested as one load management device. This thesis investigates the impact of commercial cooling systems on the utilities supply picture and describes an off-peak cooling system which would enable a building operator to shift chiller operation to off-peak hours. The chillers draw heat from a water/glycol coolant, cooling it to 20°F. The coolant circulates through a series of coiled pipes inside a water filled storage tank. As heat is drawn from the water, ice forms around the pipe heat exchanger. With a cool ant temperature of 20°F the ice cylinder will form out to a diameter of 3.4\" in 10 hours. Optimum pipe spacing is 3.5\" on center. Polyethylene pipe is preferred to copper pipe for cost and fabrication reasons. The plastic pipes are grouped in discrete modules which allow flexibility in design. Building cooling loads are managed by circulating the remaining 32°F tank water through a heat exchanger coupled to the air handling units cooling coils. The warm water is returned to the tank where the heat is absorbed by the ice. Economic analysis using the present electric schedules indicate a favorable return on investment Time of day rates would make the system look even more desirable."]},{"key":"dc:description.degree","label":"Dc Description Degree","values":["M.S."]},{"key":"dc:description.statementofresponsibility","label":"Dc Description Statementofresponsibility","values":["by Edward M. Quinlan."]},{"key":"dc:format.extent","label":"Dc Format Extent","values":["131 leaves"]},{"key":"dc:format.mimetype","label":"Dc Format Mimetype","values":["application/pdf"]},{"key":"dc:title","label":"Title","values":["Off peak cooling using an ice storage system"]},{"key":"dspace:entity.type","label":"Dspace Entity Type","values":["Publication"]},{"key":"others:access_status","label":"Others Access Status","values":["unknown"]}]}],"canonical_facts":{"cerif:openaire":["<Publication xmlns=\"https://www.openaire.eu/cerif-profile/1.1/\" id=\"87823786-04d5-40cb-bb73-49d97eb481cf\"> <Type xmlns=\"https://www.openaire.eu/cerif-profile/vocab/COAR_Publication_Types\">http://purl.org/coar/resource_type/c_1843</Type> <Language>en</Language> <Title>Off peak cooling using an ice storage system</Title> <PublishedIn> <Publication> </Publication> </PublishedIn> <PublicationDate>1980</PublicationDate> <Authors> <Author> <DisplayName>Quinlan, Edward Michael</DisplayName> <Affiliation> <OrgUnit> </OrgUnit> </Affiliation> </Author> </Authors> <Editors> </Editors> <Publishers> <Publisher> <DisplayName>Massachusetts Institute of Technology</DisplayName> <OrgUnit /> </Publisher> </Publishers> <License>http://dspace.mit.edu/handle/1721.1/7582</License> <Keyword>Architecture</Keyword> <Abstract>The electric utilities in the United States have entered a period of slow growth due to a combination of increased capital costs and a staggering rise in the costs for fuel. In addition to this, the rise in peak power demand continues almost at historical levels resulting in lower plant utilization. Current rate schedules do little to improve the utilities' load factors and,in fact, encourage consumption. Time of day rate structures have been suggested as one load management device. This thesis investigates the impact of commercial cooling systems on the utilities supply picture and describes an off-peak cooling system which would enable a building operator to shift chiller operation to off-peak hours. The chillers draw heat from a water/glycol coolant, cooling it to 20°F. The coolant circulates through a series of coiled pipes inside a water filled storage tank. As heat is drawn from the water, ice forms around the pipe heat exchanger. With a cool ant temperature of 20°F the ice cylinder will form out to a diameter of 3.4\" in 10 hours. Optimum pipe spacing is 3.5\" on center. Polyethylene pipe is preferred to copper pipe for cost and fabrication reasons. The plastic pipes are grouped in discrete modules which allow flexibility in design. Building cooling loads are managed by circulating the remaining 32°F tank water through a heat exchanger coupled to the air handling units cooling coils. The warm water is returned to the tank where the heat is absorbed by the ice. Economic analysis using the present electric schedules indicate a favorable return on investment Time of day rates would make the system look even more desirable.</Abstract> <Access xmlns=\"http://purl.org/coar/access_right\" > </Access> </Publication>"],"dc:contributor.advisor":["Timothy E. Johnson."],"dc:coverage.spatial":["n-us---"],"dc:creator":["Quinlan, Edward Michael"],"dc:date.accessioned":["2013-02-14T19:12:40Z"],"dc:date.available":["2013-02-14T19:12:40Z"],"dc:date.copyright":["1980"],"dc:date.issued":["1980"],"dc:description":["Thesis (M.S.)--Massachusetts Institute of Technology, Dept. of Architecture, 1980.","MICROFICHE COPY AVAILABLE IN ARCHIVES AND ROTCH.","Includes bibliographical references."],"dc:description.abstract":["The electric utilities in the United States have entered a period of slow growth due to a combination of increased capital costs and a staggering rise in the costs for fuel. In addition to this, the rise in peak power demand continues almost at historical levels resulting in lower plant utilization. Current rate schedules do little to improve the utilities' load factors and,in fact, encourage consumption. Time of day rate structures have been suggested as one load management device. This thesis investigates the impact of commercial cooling systems on the utilities supply picture and describes an off-peak cooling system which would enable a building operator to shift chiller operation to off-peak hours. The chillers draw heat from a water/glycol coolant, cooling it to 20°F. The coolant circulates through a series of coiled pipes inside a water filled storage tank. As heat is drawn from the water, ice forms around the pipe heat exchanger. With a cool ant temperature of 20°F the ice cylinder will form out to a diameter of 3.4\" in 10 hours. Optimum pipe spacing is 3.5\" on center. Polyethylene pipe is preferred to copper pipe for cost and fabrication reasons. The plastic pipes are grouped in discrete modules which allow flexibility in design. Building cooling loads are managed by circulating the remaining 32°F tank water through a heat exchanger coupled to the air handling units cooling coils. The warm water is returned to the tank where the heat is absorbed by the ice. Economic analysis using the present electric schedules indicate a favorable return on investment Time of day rates would make the system look even more desirable."],"dc:description.degree":["M.S."],"dc:description.statementofresponsibility":["by Edward M. Quinlan."],"dc:format.extent":["131 leaves"],"dc:format.mimetype":["application/pdf"],"dc:identifier.oclc":["07441136"],"dc:identifier.uri":["http://hdl.handle.net/1721.1/77046"],"dc:language.iso":["en"],"dc:publisher":["Massachusetts Institute of Technology"],"dc:rights":["M.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission."],"dc:rights.uri":["http://dspace.mit.edu/handle/1721.1/7582"],"dc:subject":["Architecture"],"dc:subject.lcsh":["Power resources","Heating","Ventilation","Electric utilities Rates"],"dc:title":["Off peak cooling using an ice storage system"],"dc:type":["Thesis"],"dspace:entity.type":["Publication"],"others:access_status":["unknown"]},"updated_at":"2026-11-29T16:52:07Z"}