{"id":{"repo_id":"odu","oai_identifier":"oai:digitalcommons.odu.edu:mae_etds-1530"},"canonical_url":"https://search.ndltd.org/etd/odu/oai:digitalcommons.odu.edu:mae_etds-1530","repository":{"repo_id":"odu","name":"Old Dominion University","base_url":"https://digitalcommons.odu.edu/do/oai/"},"display":{"title":"Comparative Heat Load Analysis for a Direct Gain Passive Solar Building","abstract":"A newly erected University Police Safety Building on the campus was constructed with passive solar design features. The slab-on-grade brick building has 3081 square feet of conditioned space, an ample south-facing solar aperture with clerestory and an air-to-air heat pump system. A comparative winter heat load assessment has been made in order to determine the fraction of the heat load which can be met by the winter sun (Norfolk, VA 37°N Latitude), and more importantly to probe differences which result when various heat load estimating methods are employed. Techniques employed included the degree day method·, bin method with and with out credit for solar input, the passive load-collector ratio (LCR) method, a combined LCR-absorbed radiation, degree day method, and finally a customized electrical network modeling analysis. A number of interesting conclusions can be drawn from the study, including the realization that inadequacies exist in the load-modeling process. The thermal mass of the building is low; not more than 29 percent of the winter (January) heat load can be supplied via direct gain through the south-facing windows. It was interesting to learn that horizontal reflectors placed on the roof, south of the clerestory windows, would produce a 15 percent increase in the fraction of load delivered by solar input, and that R-9 night insulation placed on the windows would decrease heat loss from the windows by 60 percent. From the bin method and simulation analysis the installed beat pumps appear to be oversized. It can also be seen that the passive solar building, with the floor as thermal mass, will increase heat loss from the floor as compared with a conventional building. The computer simulation results for January enable a favorable comparison with the other methods.","abstract_html":"A newly erected University Police Safety Building on the campus was constructed with passive solar design features. The slab-on-grade brick building has 3081 square feet of conditioned space, an ample south-facing solar aperture with clerestory and an air-to-air heat pump system. A comparative winter heat load assessment has been made in order to determine the fraction of the heat load which can be met by the winter sun (Norfolk, VA 37°N Latitude), and more importantly to probe differences which result when various heat load estimating methods are employed. Techniques employed included the degree day method·, bin method with and with out credit for solar input, the passive load-collector ratio (LCR) method, a combined LCR-absorbed radiation, degree day method, and finally a customized electrical network modeling analysis. A number of interesting conclusions can be drawn from the study, including the realization that inadequacies exist in the load-modeling process. The thermal mass of the building is low; not more than 29 percent of the winter (January) heat load can be supplied via direct gain through the south-facing windows. It was interesting to learn that horizontal reflectors placed on the roof, south of the clerestory windows, would produce a 15 percent increase in the fraction of load delivered by solar input, and that R-9 night insulation placed on the windows would decrease heat loss from the windows by 60 percent. From the bin method and simulation analysis the installed beat pumps appear to be oversized. It can also be seen that the passive solar building, with the floor as thermal mass, will increase heat loss from the floor as compared with a conventional building. The computer simulation results for January enable a favorable comparison with the other methods.","abstract_has_math":false,"creators":["Hu, Hong"],"institution":null,"degree_name":"Master of Science (MS)","degree_level":"Thesis","degree_discipline":"Mechanical & Aerospace Engineering","degree_department":null,"school":null,"contributors":["A. Sidney Roberts, Jr.","Robert L. Ash","Sushil K. Chaturvedi"],"advisors":[],"committee_chairs":[],"committee_members":[],"year":null,"date_issued":"","date_published":null,"updated_at":"2026-11-27T04:11:26Z","subjects":["Heat","Solar houses","Mechanical Engineering"],"languages":[],"rights":["<p>In Copyright. URI: <a href=\"http://rightsstatements.org/vocab/InC/1.0/\">http://rightsstatements.org/vocab/InC/1.0/</a> This Item is protected by copyright and/or related rights. You are free to use this Item in any way that is permitted by the copyright and related rights legislation that applies to your use. For other uses you need to obtain permission from the rights-holder(s).</p>"],"rights_urls":[],"identifier_entries":[],"person_identifier_entries":[]},"links":{"outbound_url":"https://digitalcommons.odu.edu/mae_etds/535","outbound_label":"Repository record","outbound_source":"dc:identifier","record_url":"https://digitalcommons.odu.edu/mae_etds/535","record_label":"Repository record","record_kind":"record","record_source":"dc:identifier","access_status":null,"embargo_until":null,"access_note":null},"oai_pmh_record":{"url":"https://union.ndltd.org/oai-pmh/?verb=GetRecord&metadataPrefix=oai_dc&identifier=oai%3Aunion.ndltd.org%3Arepo%3Aodu%3Aoai%3Adigitalcommons.odu.edu%3Amae_etds-1530","prefix":"oai_dc"},"source_record":{"url":"https://digitalcommons.odu.edu/do/oai/?verb=GetRecord&metadataPrefix=oai_etdms&identifier=oai%3Adigitalcommons.odu.edu%3Amae_etds-1530","prefix":"oai_etdms"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor","label":"Contributor","values":["A. Sidney Roberts, Jr.","Robert L. Ash","Sushil K. Chaturvedi"]},{"key":"dc:creator","label":"Author","values":["Hu, Hong"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date.available","label":"Dc Date Available","values":["2025-01-15T08:00:00Z"]},{"key":"dc:date.created","label":"Dc Date Created","values":["1984-04-01T08:00:00Z"]},{"key":"thesis:degree_discipline","label":"Discipline","values":["Mechanical & Aerospace Engineering"]},{"key":"thesis:degree_level","label":"Degree Level","values":["Thesis"]},{"key":"thesis:degree_name","label":"Degree Name","values":["Master of Science (MS)"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject","label":"Dc Subject","values":["Heat","Solar houses","Mechanical Engineering"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:rights","label":"Dc Rights","values":["<p>In Copyright. URI: <a href=\"http://rightsstatements.org/vocab/InC/1.0/\">http://rightsstatements.org/vocab/InC/1.0/</a> This Item is protected by copyright and/or related rights. You are free to use this Item in any way that is permitted by the copyright and related rights legislation that applies to your use. For other uses you need to obtain permission from the rights-holder(s).</p>"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier","label":"Identifier","values":["https://digitalcommons.odu.edu/mae_etds/535"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description.abstract","label":"Abstract","values":["A newly erected University Police Safety Building on the campus was constructed with passive solar design features. The slab-on-grade brick building has 3081 square feet of conditioned space, an ample south-facing solar aperture with clerestory and an air-to-air heat pump system. A comparative winter heat load assessment has been made in order to determine the fraction of the heat load which can be met by the winter sun (Norfolk, VA 37°N Latitude), and more importantly to probe differences which result when various heat load estimating methods are employed. Techniques employed included the degree day method·, bin method with and with out credit for solar input, the passive load-collector ratio (LCR) method, a combined LCR-absorbed radiation, degree day method, and finally a customized electrical network modeling analysis. A number of interesting conclusions can be drawn from the study, including the realization that inadequacies exist in the load-modeling process. The thermal mass of the building is low; not more than 29 percent of the winter (January) heat load can be supplied via direct gain through the south-facing windows. It was interesting to learn that horizontal reflectors placed on the roof, south of the clerestory windows, would produce a 15 percent increase in the fraction of load delivered by solar input, and that R-9 night insulation placed on the windows would decrease heat loss from the windows by 60 percent. From the bin method and simulation analysis the installed beat pumps appear to be oversized. It can also be seen that the passive solar building, with the floor as thermal mass, will increase heat loss from the floor as compared with a conventional building. The computer simulation results for January enable a favorable comparison with the other methods."]},{"key":"dc:title","label":"Title","values":["Comparative Heat Load Analysis for a Direct Gain Passive Solar Building"]}]}],"canonical_facts":{"dc:contributor":["A. Sidney Roberts, Jr.","Robert L. Ash","Sushil K. Chaturvedi"],"dc:creator":["Hu, Hong"],"dc:date.available":["2025-01-15T08:00:00Z"],"dc:date.created":["1984-04-01T08:00:00Z"],"dc:description.abstract":["A newly erected University Police Safety Building on the campus was constructed with passive solar design features. The slab-on-grade brick building has 3081 square feet of conditioned space, an ample south-facing solar aperture with clerestory and an air-to-air heat pump system. A comparative winter heat load assessment has been made in order to determine the fraction of the heat load which can be met by the winter sun (Norfolk, VA 37°N Latitude), and more importantly to probe differences which result when various heat load estimating methods are employed. Techniques employed included the degree day method·, bin method with and with out credit for solar input, the passive load-collector ratio (LCR) method, a combined LCR-absorbed radiation, degree day method, and finally a customized electrical network modeling analysis. A number of interesting conclusions can be drawn from the study, including the realization that inadequacies exist in the load-modeling process. The thermal mass of the building is low; not more than 29 percent of the winter (January) heat load can be supplied via direct gain through the south-facing windows. It was interesting to learn that horizontal reflectors placed on the roof, south of the clerestory windows, would produce a 15 percent increase in the fraction of load delivered by solar input, and that R-9 night insulation placed on the windows would decrease heat loss from the windows by 60 percent. From the bin method and simulation analysis the installed beat pumps appear to be oversized. It can also be seen that the passive solar building, with the floor as thermal mass, will increase heat loss from the floor as compared with a conventional building. The computer simulation results for January enable a favorable comparison with the other methods."],"dc:identifier":["https://digitalcommons.odu.edu/mae_etds/535"],"dc:rights":["<p>In Copyright. URI: <a href=\"http://rightsstatements.org/vocab/InC/1.0/\">http://rightsstatements.org/vocab/InC/1.0/</a> This Item is protected by copyright and/or related rights. You are free to use this Item in any way that is permitted by the copyright and related rights legislation that applies to your use. For other uses you need to obtain permission from the rights-holder(s).</p>"],"dc:subject":["Heat","Solar houses","Mechanical Engineering"],"dc:title":["Comparative Heat Load Analysis for a Direct Gain Passive Solar Building"],"thesis:degree_discipline":["Mechanical & Aerospace Engineering"],"thesis:degree_level":["Thesis"],"thesis:degree_name":["Master of Science (MS)"]},"updated_at":"2026-11-27T04:11:26Z"}