{"id":{"repo_id":"sask","oai_identifier":"oai:harvest.usask.ca:10388/8381"},"canonical_url":"https://search.ndltd.org/etd/sask/oai:harvest.usask.ca:10388/8381","repository":{"repo_id":"sask","name":"University of Saskatchewan","base_url":"https://harvest.usask.ca/server/oai/request"},"display":{"title":"REAL-TIME POWER SWING DETECTION USING EQUAL AREA CRITERION","abstract":"Power systems are interconnected for enhancing the availability of power supply to the customers and for reducing the prices charged to them. A natural consequence of the interconnections is that the interconnected power systems are likely to swing following faults and other disturbing events. The systems should be allowed to settle down to a stable state if one exists but should be disconnected from each other if the swing is likely to result in dynamic instability. For maintaining generation-load balance, it becomes necessary to shed load in some cases and shed generation in other cases. During power-system swings, currents and voltages swing in amplitude and phase. The impedances seen by distance relays, which calculate the impedances from the measured voltages and currents, also swing in magnitude and phase. At certain locations in the power system, the impedances calculated from the voltages and currents become so small that they enter the protection zones of distance relays. Power swing relays are traditionally used to block distance relays from tripping line circuit breakers if the swing is not likely to cause dynamic instability but open the interconnecting lines if the systems are likely to become unstable. This is achieved by using delay timers but deciding on the delays is a very difficult and involved issue. Also the needed delay times are different for different operating states of the systems. This thesis presents a new approach for use in out-of-step relays. The technique is based on the well known equal area criterion in the time domain. The basis of the protection technique is described in the thesis. The results from computer simulations show that the technique is able to correctly identify swings that are likely to result in dynamic instability. Based on the information provided by the technique, appropriate decisions for shedding loads or generation can be made with reasonable certainty.","abstract_html":"Power systems are interconnected for enhancing the availability of power supply to the customers and for reducing the prices charged to them. A natural consequence of the interconnections is that the interconnected power systems are likely to swing following faults and other disturbing events. The systems should be allowed to settle down to a stable state if one exists but should be disconnected from each other if the swing is likely to result in dynamic instability. For maintaining generation-load balance, it becomes necessary to shed load in some cases and shed generation in other cases. During power-system swings, currents and voltages swing in amplitude and phase. The impedances seen by distance relays, which calculate the impedances from the measured voltages and currents, also swing in magnitude and phase. At certain locations in the power system, the impedances calculated from the voltages and currents become so small that they enter the protection zones of distance relays. Power swing relays are traditionally used to block distance relays from tripping line circuit breakers if the swing is not likely to cause dynamic instability but open the interconnecting lines if the systems are likely to become unstable. This is achieved by using delay timers but deciding on the delays is a very difficult and involved issue. Also the needed delay times are different for different operating states of the systems. This thesis presents a new approach for use in out-of-step relays. The technique is based on the well known equal area criterion in the time domain. The basis of the protection technique is described in the thesis. The results from computer simulations show that the technique is able to correctly identify swings that are likely to result in dynamic instability. Based on the information provided by the technique, appropriate decisions for shedding loads or generation can be made with reasonable certainty.","abstract_has_math":false,"creators":["Cheng, Shengli"],"institution":"University of Saskatchewan","degree_name":"Master of Science (M.Sc.)","degree_level":"Masters","degree_discipline":"Electrical Engineering","degree_department":"Electrical and Computer Engineering","school":null,"contributors":[],"advisors":["Sachdev, M. S."],"committee_chairs":[],"committee_members":[],"year":2006,"date_issued":"2006-04","date_published":"2006-04","updated_at":"2026-11-19T10:12:18Z","subjects":["Out-of-step","Out-of-step relaying","Power swing","Equal Area Criterion","EAC"],"languages":[],"rights":[],"rights_urls":[],"identifier_entries":[],"person_identifier_entries":[]},"links":{"outbound_url":"https://hdl.handle.net/10388/8381","outbound_label":"Handle","outbound_source":"dc:identifier.uri","record_url":"https://hdl.handle.net/10388/8381","record_label":"Repository record","record_kind":"handle","record_source":"dc:identifier.uri","access_status":null,"embargo_until":null,"access_note":null},"oai_pmh_record":{"url":"https://union.ndltd.org/oai-pmh/?verb=GetRecord&metadataPrefix=oai_dc&identifier=oai%3Aunion.ndltd.org%3Arepo%3Asask%3Aoai%3Aharvest.usask.ca%3A10388%2F8381","prefix":"oai_dc"},"source_record":{"url":"https://harvest.usask.ca/server/oai/request?verb=GetRecord&metadataPrefix=dim&identifier=oai%3Aharvest.usask.ca%3A10388%2F8381","prefix":"dim"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor.advisor","label":"Advisor","values":["Sachdev, M. S."]},{"key":"dc:creator","label":"Author","values":["Cheng, Shengli"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date.accessioned","label":"Dc Date Accessioned","values":["2018-01-30T21:10:13Z"]},{"key":"dc:date.available","label":"Dc Date Available","values":["2018-01-30T21:10:13Z"]},{"key":"dc:date.issued","label":"Date","values":["2006-04"]},{"key":"dc:date.submitted","label":"Dc Date Submitted","values":["April 2006"]},{"key":"dc:type","label":"Dc Type","values":["Thesis"]},{"key":"thesis:degree_department","label":"Department","values":["Electrical and Computer Engineering"]},{"key":"thesis:degree_discipline","label":"Discipline","values":["Electrical Engineering"]},{"key":"thesis:degree_level","label":"Degree Level","values":["Masters"]},{"key":"thesis:degree_name","label":"Degree Name","values":["Master of Science (M.Sc.)"]},{"key":"thesis:institution_name","label":"Thesis Institution Name","values":["University of Saskatchewan"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject","label":"Dc Subject","values":["Out-of-step","Out-of-step relaying","Power swing","Equal Area Criterion","EAC"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier.uri","label":"Identifier URI","values":["https://hdl.handle.net/10388/8381"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description.abstract","label":"Abstract","values":["Power systems are interconnected for enhancing the availability of power supply to the customers and for reducing the prices charged to them. A natural consequence of the interconnections is that the interconnected power systems are likely to swing following faults and other disturbing events. The systems should be allowed to settle down to a stable state if one exists but should be disconnected from each other if the swing is likely to result in dynamic instability. For maintaining generation-load balance, it becomes necessary to shed load in some cases and shed generation in other cases. During power-system swings, currents and voltages swing in amplitude and phase. The impedances seen by distance relays, which calculate the impedances from the measured voltages and currents, also swing in magnitude and phase. At certain locations in the power system, the impedances calculated from the voltages and currents become so small that they enter the protection zones of distance relays. Power swing relays are traditionally used to block distance relays from tripping line circuit breakers if the swing is not likely to cause dynamic instability but open the interconnecting lines if the systems are likely to become unstable. This is achieved by using delay timers but deciding on the delays is a very difficult and involved issue. Also the needed delay times are different for different operating states of the systems. This thesis presents a new approach for use in out-of-step relays. The technique is based on the well known equal area criterion in the time domain. The basis of the protection technique is described in the thesis. The results from computer simulations show that the technique is able to correctly identify swings that are likely to result in dynamic instability. Based on the information provided by the technique, appropriate decisions for shedding loads or generation can be made with reasonable certainty."]},{"key":"dc:title","label":"Title","values":["REAL-TIME POWER SWING DETECTION USING EQUAL AREA CRITERION"]},{"key":"others:access_status","label":"Others Access Status","values":["open.access"]}]}],"canonical_facts":{"dc:contributor.advisor":["Sachdev, M. S."],"dc:creator":["Cheng, Shengli"],"dc:date.accessioned":["2018-01-30T21:10:13Z"],"dc:date.available":["2018-01-30T21:10:13Z"],"dc:date.issued":["2006-04"],"dc:date.submitted":["April 2006"],"dc:description.abstract":["Power systems are interconnected for enhancing the availability of power supply to the customers and for reducing the prices charged to them. A natural consequence of the interconnections is that the interconnected power systems are likely to swing following faults and other disturbing events. The systems should be allowed to settle down to a stable state if one exists but should be disconnected from each other if the swing is likely to result in dynamic instability. For maintaining generation-load balance, it becomes necessary to shed load in some cases and shed generation in other cases. During power-system swings, currents and voltages swing in amplitude and phase. The impedances seen by distance relays, which calculate the impedances from the measured voltages and currents, also swing in magnitude and phase. At certain locations in the power system, the impedances calculated from the voltages and currents become so small that they enter the protection zones of distance relays. Power swing relays are traditionally used to block distance relays from tripping line circuit breakers if the swing is not likely to cause dynamic instability but open the interconnecting lines if the systems are likely to become unstable. This is achieved by using delay timers but deciding on the delays is a very difficult and involved issue. Also the needed delay times are different for different operating states of the systems. This thesis presents a new approach for use in out-of-step relays. The technique is based on the well known equal area criterion in the time domain. The basis of the protection technique is described in the thesis. The results from computer simulations show that the technique is able to correctly identify swings that are likely to result in dynamic instability. Based on the information provided by the technique, appropriate decisions for shedding loads or generation can be made with reasonable certainty."],"dc:identifier.uri":["https://hdl.handle.net/10388/8381"],"dc:subject":["Out-of-step","Out-of-step relaying","Power swing","Equal Area Criterion","EAC"],"dc:title":["REAL-TIME POWER SWING DETECTION USING EQUAL AREA CRITERION"],"dc:type":["Thesis"],"others:access_status":["open.access"],"thesis:degree_department":["Electrical and Computer Engineering"],"thesis:degree_discipline":["Electrical Engineering"],"thesis:degree_level":["Masters"],"thesis:degree_name":["Master of Science (M.Sc.)"],"thesis:institution_name":["University of Saskatchewan"]},"updated_at":"2026-11-19T10:12:18Z"}