{"id":{"repo_id":"star-france","oai_identifier":"2017GREAT060"},"canonical_url":"https://search.ndltd.org/etd/star-france/2017GREAT060","repository":{"repo_id":"star-france","name":"STAR","base_url":"https://staroai.theses.fr/OAIHandler"},"display":{"title":"Full selective protection strategy for multi-terminal cable HVDC grids based on HB-MMC converters","abstract":"Les réseaux multi-terminaux à courant continu sont une solution efficace pour intégrer l’énergie électrique produite en grande quantité par de grands parcs éoliens offshore. Bien que le recours à la technologie HVDC soit maitrisé pour des applications point-à-point, des verrous technologiques sont encore à lever pour permettre une exploitation sûre d’un réseau à courant continu. La protection est le principal domaine technique pour lequel des progrès sont encore attendu. Des stratégies de protection fiables et assurant le meilleur ratio technico-économique sont à l’étude. Ces travaux de thèse ont pour objectif la mise en œuvre d’une philosophie de protection à sélectivité totale, identique à celle utilisée dans les réseaux de transport traditionnels. Cette étude considère l’utilisation de liaison par câbles uniquement, de convertisseurs VSC-MMC composées de sous-modules en demi-pont et de disjoncteurs hybrides à courant continu. Une association de deux algorithmes de détection de défaut a été proposée. Une étude du temps disponible pour l’élimination du défaut a été menée. Enfin, des simulations numériques avec le logiciel EMTP ont permis d’évaluer la fiabilité de la stratégie de protection.","abstract_html":"Les réseaux multi-terminaux à courant continu sont une solution efficace pour intégrer l’énergie électrique produite en grande quantité par de grands parcs éoliens offshore. Bien que le recours à la technologie HVDC soit maitrisé pour des applications point-à-point, des verrous technologiques sont encore à lever pour permettre une exploitation sûre d’un réseau à courant continu. La protection est le principal domaine technique pour lequel des progrès sont encore attendu. Des stratégies de protection fiables et assurant le meilleur ratio technico-économique sont à l’étude. Ces travaux de thèse ont pour objectif la mise en œuvre d’une philosophie de protection à sélectivité totale, identique à celle utilisée dans les réseaux de transport traditionnels. Cette étude considère l’utilisation de liaison par câbles uniquement, de convertisseurs VSC-MMC composées de sous-modules en demi-pont et de disjoncteurs hybrides à courant continu. Une association de deux algorithmes de détection de défaut a été proposée. Une étude du temps disponible pour l’élimination du défaut a été menée. Enfin, des simulations numériques avec le logiciel EMTP ont permis d’évaluer la fiabilité de la stratégie de protection.","abstract_has_math":false,"creators":["Auran, Geoffrey"],"institution":"Université Grenoble Alpes (ComUE)","degree_name":"Docteur es","degree_level":"Doctorat","degree_discipline":"Genie electrique","degree_department":null,"school":null,"contributors":["Université Grenoble Alpes (ComUE)"],"advisors":["Raison, Bertrand"],"committee_chairs":["Tixador, Pascal"],"committee_members":["Descloux, Justine","Nguefeu, Samuel","Curis, Jean-Baptiste","Bertinato, Alberto"],"year":2017,"date_issued":"2017-10-17","date_published":"2017-10-17","updated_at":"2026-11-27T11:16:05Z","subjects":["Courant continu","Réseau multi-Terminaux HVDC","Stratégie de protection","Sélectivité","Câbles","Direct current","Multi-Terminal HVDC grid","Protection strategy","Selectivity","Cables","620"],"languages":["en"],"rights":["Open Access"],"rights_urls":["http://purl.org/eprint/accessRights/OpenAccess"],"identifier_entries":[{"key":"dc:identifier.uri","label":"Identifier URI","values":["https://theses.fr/2017GREAT060","https://theses.hal.science/tel-01719612","http://www.theses.fr/2017GREAT060/abes"],"render_values":[{"text":"https://theses.fr/2017GREAT060","href":"https://theses.fr/2017GREAT060","code":true},{"text":"https://theses.hal.science/tel-01719612","href":"https://theses.hal.science/tel-01719612","code":true},{"text":"http://www.theses.fr/2017GREAT060/abes","href":"http://www.theses.fr/2017GREAT060/abes","code":true}]},{"key":"dc:identifier","label":"Identifier","values":["http://www.theses.fr/2017GREAT060/document"],"render_values":[{"text":"http://www.theses.fr/2017GREAT060/document","href":"http://www.theses.fr/2017GREAT060/document","code":true}]},{"key":"dc:contributor.researchpartner.identifier","label":"Dc Contributor Researchpartner Identifier","values":["35871","https://www.idref.fr/184702941"],"render_values":[{"text":"35871","href":null,"code":true},{"text":"https://www.idref.fr/184702941","href":"https://www.idref.fr/184702941","code":true}]},{"key":"thesis:doctoral_school_identifier","label":"Thesis Doctoral School Identifier","values":["220","https://www.idref.fr/14912449X"],"render_values":[{"text":"220","href":null,"code":true},{"text":"https://www.idref.fr/14912449X","href":"https://www.idref.fr/14912449X","code":true}]},{"key":"thesis:institution_identifier","label":"Thesis Institution Identifier","values":["https://www.idref.fr/184668794"],"render_values":[{"text":"https://www.idref.fr/184668794","href":"https://www.idref.fr/184668794","code":true}]},{"key":"thesis:thesis_identifier","label":"Thesis Thesis Identifier","values":["2017GREAT060"],"render_values":[{"text":"2017GREAT060","href":null,"code":true}]}],"person_identifier_entries":[{"key":"person:identifier.idref","label":"Person Identifier Idref","values":["https://www.idref.fr/224562673","https://www.idref.fr/10359714X","https://www.idref.fr/033275327","https://www.idref.fr/176283285","https://www.idref.fr/103080104","https://www.idref.fr/224562959","https://www.idref.fr/071540156","https://www.idref.fr/224563203","https://www.idref.fr/224563408"],"render_values":[{"text":"https://www.idref.fr/224562673","href":"https://www.idref.fr/224562673","code":true},{"text":"https://www.idref.fr/10359714X","href":"https://www.idref.fr/10359714X","code":true},{"text":"https://www.idref.fr/033275327","href":"https://www.idref.fr/033275327","code":true},{"text":"https://www.idref.fr/176283285","href":"https://www.idref.fr/176283285","code":true},{"text":"https://www.idref.fr/103080104","href":"https://www.idref.fr/103080104","code":true},{"text":"https://www.idref.fr/224562959","href":"https://www.idref.fr/224562959","code":true},{"text":"https://www.idref.fr/071540156","href":"https://www.idref.fr/071540156","code":true},{"text":"https://www.idref.fr/224563203","href":"https://www.idref.fr/224563203","code":true},{"text":"https://www.idref.fr/224563408","href":"https://www.idref.fr/224563408","code":true}]},{"key":"person:identifier.student","label":"Person Identifier Student","values":["1102019381d","63490"],"render_values":[{"text":"1102019381d","href":null,"code":true},{"text":"63490","href":null,"code":true}]}]},"links":{"outbound_url":"https://doi.org/10.70675/1d9e24cbz7f1az4058z9181z82644f5541e8","outbound_label":"DOI","outbound_source":"dc:identifier.doi","record_url":"https://doi.org/10.70675/1d9e24cbz7f1az4058z9181z82644f5541e8","record_label":"Repository record","record_kind":"doi","record_source":"dc:identifier.doi","access_status":"open","embargo_until":null,"access_note":null},"oai_pmh_record":{"url":"https://union.ndltd.org/oai-pmh/?verb=GetRecord&metadataPrefix=oai_dc&identifier=oai%3Aunion.ndltd.org%3Arepo%3Astar-france%3A2017GREAT060","prefix":"oai_dc"},"source_record":{"url":"https://staroai.theses.fr/OAIHandler?verb=GetRecord&metadataPrefix=tef&identifier=2017GREAT060","prefix":"tef"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor","label":"Contributor","values":["Université Grenoble Alpes (ComUE)","Raison, Bertrand"]},{"key":"dc:contributor.advisor","label":"Advisor","values":["Raison, Bertrand"]},{"key":"dc:contributor.committeechair","label":"Committee Chair","values":["Tixador, Pascal"]},{"key":"dc:contributor.committeemember","label":"Committee Member","values":["Descloux, Justine","Nguefeu, Samuel","Curis, Jean-Baptiste","Bertinato, Alberto"]},{"key":"dc:contributor.examiner","label":"Dc Contributor Examiner","values":["Robyns, Benoît","Petit, Marc"]},{"key":"dc:contributor.researchpartner","label":"Dc Contributor Researchpartner","values":["Laboratoire de génie électrique (Grenoble, Isère, France ; 2007-....)"]},{"key":"dc:contributor.researchpartner.identifier","label":"Dc Contributor Researchpartner Identifier","values":["35871","https://www.idref.fr/184702941"]},{"key":"dc:creator","label":"Author","values":["Auran, Geoffrey"]},{"key":"person:birthdate","label":"Person Birthdate","values":["1992-02-09"]},{"key":"person:identifier.idref","label":"Person Identifier Idref","values":["https://www.idref.fr/224562673","https://www.idref.fr/10359714X","https://www.idref.fr/033275327","https://www.idref.fr/176283285","https://www.idref.fr/103080104","https://www.idref.fr/224562959","https://www.idref.fr/071540156","https://www.idref.fr/224563203","https://www.idref.fr/224563408"]},{"key":"person:identifier.student","label":"Person Identifier Student","values":["1102019381d","63490"]},{"key":"person:nationality","label":"Person Nationality","values":["FR"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date","label":"Dc Date","values":["2017-10-17"]},{"key":"dc:date.dateaccepted","label":"Dc Date Dateaccepted","values":["2017-10-17"]},{"key":"dc:type","label":"Dc Type","values":["Electronic Thesis or Dissertation","Text"]},{"key":"dc:type.dcmitype","label":"Dc Type Dcmitype","values":["Text"]},{"key":"thesis:by_published_works","label":"Thesis By Published Works","values":["non"]},{"key":"thesis:degree_discipline","label":"Discipline","values":["Genie electrique"]},{"key":"thesis:degree_level","label":"Degree Level","values":["Doctorat"]},{"key":"thesis:degree_name","label":"Degree Name","values":["Docteur es"]},{"key":"thesis:doctoral_school","label":"Thesis Doctoral School","values":["École doctorale électronique, électrotechnique, automatique, traitement du signal (Grenoble ; 199.-....)"]},{"key":"thesis:doctoral_school_identifier","label":"Thesis Doctoral School Identifier","values":["220","https://www.idref.fr/14912449X"]},{"key":"thesis:institution_identifier","label":"Thesis Institution Identifier","values":["https://www.idref.fr/184668794"]},{"key":"thesis:institution_name","label":"Thesis Institution Name","values":["Université Grenoble Alpes (ComUE)"]},{"key":"thesis:jury_release_opinion","label":"Thesis Jury Release Opinion","values":["oui"]},{"key":"thesis:thesis_identifier","label":"Thesis Thesis Identifier","values":["2017GREAT060"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject","label":"Dc Subject","values":["Courant continu","Réseau multi-Terminaux HVDC","Stratégie de protection","Sélectivité","Câbles","Direct current","Multi-Terminal HVDC grid","Protection strategy","Selectivity","Cables","620"]},{"key":"dc:subject.ddc","label":"Dc Subject Ddc","values":["620"]},{"key":"dc:subject.rameau","label":"Dc Subject Rameau","values":["Haute tension","Câbles électriques","Électricité -- Transport -- Courant continu","Énergie éolienne"]},{"key":"dc:subject.uri","label":"Dc Subject URI","values":["https://www.idref.fr/027233596","https://www.idref.fr/027372413","https://www.idref.fr/027258130","https://www.idref.fr/027270343"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:language","label":"Dc Language","values":["en"]},{"key":"dc:language.rfc3066","label":"Language (RFC 3066)","values":["en"]},{"key":"dc:rights","label":"Dc Rights","values":["Open Access","http://purl.org/eprint/accessRights/OpenAccess"]},{"key":"dc:rights.permissions","label":"Dc Rights Permissions","values":["display, duplicate, print"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier","label":"Identifier","values":["http://www.theses.fr/2017GREAT060/document"]},{"key":"dc:identifier.doi","label":"DOI","values":["https://doi.org/10.70675/1d9e24cbz7f1az4058z9181z82644f5541e8"]},{"key":"dc:identifier.fulltext","label":"Full Text Identifier","values":["GREA/THESE_94591/document/0/0/AURAN_2017_archivage.pdf"]},{"key":"dc:identifier.uri","label":"Identifier URI","values":["https://theses.fr/2017GREAT060","https://theses.hal.science/tel-01719612","http://www.theses.fr/2017GREAT060/abes"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description","label":"Description","values":["Les réseaux multi-terminaux à courant continu sont une solution efficace pour intégrer l’énergie électrique produite en grande quantité par de grands parcs éoliens offshore. Bien que le recours à la technologie HVDC soit maitrisé pour des applications point-à-point, des verrous technologiques sont encore à lever pour permettre une exploitation sûre d’un réseau à courant continu. La protection est le principal domaine technique pour lequel des progrès sont encore attendu. Des stratégies de protection fiables et assurant le meilleur ratio technico-économique sont à l’étude. Ces travaux de thèse ont pour objectif la mise en œuvre d’une philosophie de protection à sélectivité totale, identique à celle utilisée dans les réseaux de transport traditionnels. Cette étude considère l’utilisation de liaison par câbles uniquement, de convertisseurs VSC-MMC composées de sous-modules en demi-pont et de disjoncteurs hybrides à courant continu. Une association de deux algorithmes de détection de défaut a été proposée. Une étude du temps disponible pour l’élimination du défaut a été menée. Enfin, des simulations numériques avec le logiciel EMTP ont permis d’évaluer la fiabilité de la stratégie de protection.","In a near future, multi-terminal High Voltage Direct Current grids (MT-HVDC grids) appear to be a suitable solution for the integration of power electricity produced by remote offshore windfarms into the AC transmission system. Though the recourse to HVDC point-to-point links is well-known, challenges still remain for a safe operation of HVDC grids. Protection is the main technical field still under study and reliable protection strategies ensuring the best technological and economic ratio are investigated. This thesis focused on a full selective protection philosophy similar to the one applied to AC transmission systems. The consideration of cable links, Half-Bridge VSC-MMC converters and hybrid DC circuit breakers defines the frame of the study. An association of two algorithms for the identification of faults is suggested. The time available for the fault clearing process has been investigated. Simulations performed with EMTP software have been used to evaluate the reliability of the suggested strategy."]},{"key":"dc:description.abstract","label":"Abstract","values":["Les réseaux multi-terminaux à courant continu sont une solution efficace pour intégrer l’énergie électrique produite en grande quantité par de grands parcs éoliens offshore. Bien que le recours à la technologie HVDC soit maitrisé pour des applications point-à-point, des verrous technologiques sont encore à lever pour permettre une exploitation sûre d’un réseau à courant continu. La protection est le principal domaine technique pour lequel des progrès sont encore attendu. Des stratégies de protection fiables et assurant le meilleur ratio technico-économique sont à l’étude. Ces travaux de thèse ont pour objectif la mise en œuvre d’une philosophie de protection à sélectivité totale, identique à celle utilisée dans les réseaux de transport traditionnels. Cette étude considère l’utilisation de liaison par câbles uniquement, de convertisseurs VSC-MMC composées de sous-modules en demi-pont et de disjoncteurs hybrides à courant continu. Une association de deux algorithmes de détection de défaut a été proposée. Une étude du temps disponible pour l’élimination du défaut a été menée. Enfin, des simulations numériques avec le logiciel EMTP ont permis d’évaluer la fiabilité de la stratégie de protection.","In a near future, multi-terminal High Voltage Direct Current grids (MT-HVDC grids) appear to be a suitable solution for the integration of power electricity produced by remote offshore windfarms into the AC transmission system. Though the recourse to HVDC point-to-point links is well-known, challenges still remain for a safe operation of HVDC grids. Protection is the main technical field still under study and reliable protection strategies ensuring the best technological and economic ratio are investigated. This thesis focused on a full selective protection philosophy similar to the one applied to AC transmission systems. The consideration of cable links, Half-Bridge VSC-MMC converters and hybrid DC circuit breakers defines the frame of the study. An association of two algorithms for the identification of faults is suggested. The time available for the fault clearing process has been investigated. Simulations performed with EMTP software have been used to evaluate the reliability of the suggested strategy."]},{"key":"dc:format.extent","label":"Dc Format Extent","values":["11528617","11010634"]},{"key":"dc:format.filetype","label":"Dc Format Filetype","values":["PDF"]},{"key":"dc:format.medium","label":"Dc Format Medium","values":["PDF","application/pdf"]},{"key":"dc:title","label":"Title","values":["Full selective protection strategy for multi-terminal cable HVDC grids based on HB-MMC converters","Stratégie de protection à sélectivité totale pour réseaux multi-terminaux à courant continu composés de câbles et de convertisseurs de type hb-mmc"]},{"key":"dc:title.alternative","label":"Alternative Title","values":["Stratégie de protection à sélectivité totale pour réseaux multi-terminaux à courant continu composés de câbles et de convertisseurs de type hb-mmc"]},{"key":"tef:authorizedname","label":"Tef Authorizedname","values":["Raison, Bertrand","Electronique, Electrotechnique, Automatique, Traitement du Signal (EEATS)","Tixador, Pascal","Laboratoire de génie électrique (Grenoble)","Descloux, Justine","Nguefeu, Samuel","Curis, Jean-Baptiste","Bertinato, Alberto","Robyns, Benoît","Petit, Marc"]},{"key":"tef:internalref","label":"Tef Internalref","values":["MADS_DIRECTEUR_DE_THESE_1","MADS_PRESIDENT_DU_JURY","MADS_MEMBRE_DU_JURY_1","MADS_RAPPORTEUR_1","MADS_ECOLE_DOCTORALE_1","MADS_PARTENAIRE_DE_RECHERCHE_1","MADS_MEMBRE_DU_JURY_2","MADS_RAPPORTEUR_2","MADS_MEMBRE_DU_JURY_3","MADS_MEMBRE_DU_JURY_4"]},{"key":"tef:oaisetspec","label":"Tef Oaisetspec","values":["ddc:620"]},{"key":"tef:record.agent","label":"Tef Record Agent","values":["ABES"]},{"key":"tef:record.agentnote","label":"Tef Record Agentnote","values":["Note"]},{"key":"tef:record.created","label":"Tef Record Created","values":["2017-10-03T08:57:07"]},{"key":"tef:record.modified","label":"Tef Record Modified","values":["2025-03-06T03:22:53Z"]},{"key":"tef:record.status","label":"Tef Record Status","values":["valide"]}]}],"canonical_facts":{"dc:contributor":["Université Grenoble Alpes (ComUE)","Raison, Bertrand"],"dc:contributor.advisor":["Raison, Bertrand"],"dc:contributor.committeechair":["Tixador, Pascal"],"dc:contributor.committeemember":["Descloux, Justine","Nguefeu, Samuel","Curis, Jean-Baptiste","Bertinato, Alberto"],"dc:contributor.examiner":["Robyns, Benoît","Petit, Marc"],"dc:contributor.researchpartner":["Laboratoire de génie électrique (Grenoble, Isère, France ; 2007-....)"],"dc:contributor.researchpartner.identifier":["35871","https://www.idref.fr/184702941"],"dc:creator":["Auran, Geoffrey"],"dc:date":["2017-10-17"],"dc:date.dateaccepted":["2017-10-17"],"dc:description":["Les réseaux multi-terminaux à courant continu sont une solution efficace pour intégrer l’énergie électrique produite en grande quantité par de grands parcs éoliens offshore. Bien que le recours à la technologie HVDC soit maitrisé pour des applications point-à-point, des verrous technologiques sont encore à lever pour permettre une exploitation sûre d’un réseau à courant continu. La protection est le principal domaine technique pour lequel des progrès sont encore attendu. Des stratégies de protection fiables et assurant le meilleur ratio technico-économique sont à l’étude. Ces travaux de thèse ont pour objectif la mise en œuvre d’une philosophie de protection à sélectivité totale, identique à celle utilisée dans les réseaux de transport traditionnels. Cette étude considère l’utilisation de liaison par câbles uniquement, de convertisseurs VSC-MMC composées de sous-modules en demi-pont et de disjoncteurs hybrides à courant continu. Une association de deux algorithmes de détection de défaut a été proposée. Une étude du temps disponible pour l’élimination du défaut a été menée. Enfin, des simulations numériques avec le logiciel EMTP ont permis d’évaluer la fiabilité de la stratégie de protection.","In a near future, multi-terminal High Voltage Direct Current grids (MT-HVDC grids) appear to be a suitable solution for the integration of power electricity produced by remote offshore windfarms into the AC transmission system. Though the recourse to HVDC point-to-point links is well-known, challenges still remain for a safe operation of HVDC grids. Protection is the main technical field still under study and reliable protection strategies ensuring the best technological and economic ratio are investigated. This thesis focused on a full selective protection philosophy similar to the one applied to AC transmission systems. The consideration of cable links, Half-Bridge VSC-MMC converters and hybrid DC circuit breakers defines the frame of the study. An association of two algorithms for the identification of faults is suggested. The time available for the fault clearing process has been investigated. Simulations performed with EMTP software have been used to evaluate the reliability of the suggested strategy."],"dc:description.abstract":["Les réseaux multi-terminaux à courant continu sont une solution efficace pour intégrer l’énergie électrique produite en grande quantité par de grands parcs éoliens offshore. Bien que le recours à la technologie HVDC soit maitrisé pour des applications point-à-point, des verrous technologiques sont encore à lever pour permettre une exploitation sûre d’un réseau à courant continu. La protection est le principal domaine technique pour lequel des progrès sont encore attendu. Des stratégies de protection fiables et assurant le meilleur ratio technico-économique sont à l’étude. Ces travaux de thèse ont pour objectif la mise en œuvre d’une philosophie de protection à sélectivité totale, identique à celle utilisée dans les réseaux de transport traditionnels. Cette étude considère l’utilisation de liaison par câbles uniquement, de convertisseurs VSC-MMC composées de sous-modules en demi-pont et de disjoncteurs hybrides à courant continu. Une association de deux algorithmes de détection de défaut a été proposée. Une étude du temps disponible pour l’élimination du défaut a été menée. Enfin, des simulations numériques avec le logiciel EMTP ont permis d’évaluer la fiabilité de la stratégie de protection.","In a near future, multi-terminal High Voltage Direct Current grids (MT-HVDC grids) appear to be a suitable solution for the integration of power electricity produced by remote offshore windfarms into the AC transmission system. Though the recourse to HVDC point-to-point links is well-known, challenges still remain for a safe operation of HVDC grids. Protection is the main technical field still under study and reliable protection strategies ensuring the best technological and economic ratio are investigated. This thesis focused on a full selective protection philosophy similar to the one applied to AC transmission systems. The consideration of cable links, Half-Bridge VSC-MMC converters and hybrid DC circuit breakers defines the frame of the study. An association of two algorithms for the identification of faults is suggested. The time available for the fault clearing process has been investigated. Simulations performed with EMTP software have been used to evaluate the reliability of the suggested strategy."],"dc:format.extent":["11528617","11010634"],"dc:format.filetype":["PDF"],"dc:format.medium":["PDF","application/pdf"],"dc:identifier":["http://www.theses.fr/2017GREAT060/document"],"dc:identifier.doi":["https://doi.org/10.70675/1d9e24cbz7f1az4058z9181z82644f5541e8"],"dc:identifier.fulltext":["GREA/THESE_94591/document/0/0/AURAN_2017_archivage.pdf"],"dc:identifier.uri":["https://theses.fr/2017GREAT060","https://theses.hal.science/tel-01719612","http://www.theses.fr/2017GREAT060/abes"],"dc:language":["en"],"dc:language.rfc3066":["en"],"dc:rights":["Open Access","http://purl.org/eprint/accessRights/OpenAccess"],"dc:rights.permissions":["display, duplicate, print"],"dc:subject":["Courant continu","Réseau multi-Terminaux HVDC","Stratégie de protection","Sélectivité","Câbles","Direct current","Multi-Terminal HVDC grid","Protection strategy","Selectivity","Cables","620"],"dc:subject.ddc":["620"],"dc:subject.rameau":["Haute tension","Câbles électriques","Électricité -- Transport -- Courant continu","Énergie éolienne"],"dc:subject.uri":["https://www.idref.fr/027233596","https://www.idref.fr/027372413","https://www.idref.fr/027258130","https://www.idref.fr/027270343"],"dc:title":["Full selective protection strategy for multi-terminal cable HVDC grids based on HB-MMC converters","Stratégie de protection à sélectivité totale pour réseaux multi-terminaux à courant continu composés de câbles et de convertisseurs de type hb-mmc"],"dc:title.alternative":["Stratégie de protection à sélectivité totale pour réseaux multi-terminaux à courant continu composés de câbles et de convertisseurs de type hb-mmc"],"dc:type":["Electronic Thesis or Dissertation","Text"],"dc:type.dcmitype":["Text"],"person:birthdate":["1992-02-09"],"person:identifier.idref":["https://www.idref.fr/224562673","https://www.idref.fr/10359714X","https://www.idref.fr/033275327","https://www.idref.fr/176283285","https://www.idref.fr/103080104","https://www.idref.fr/224562959","https://www.idref.fr/071540156","https://www.idref.fr/224563203","https://www.idref.fr/224563408"],"person:identifier.student":["1102019381d","63490"],"person:nationality":["FR"],"tef:authorizedname":["Raison, Bertrand","Electronique, Electrotechnique, Automatique, Traitement du Signal (EEATS)","Tixador, Pascal","Laboratoire de génie électrique (Grenoble)","Descloux, Justine","Nguefeu, Samuel","Curis, Jean-Baptiste","Bertinato, Alberto","Robyns, Benoît","Petit, Marc"],"tef:internalref":["MADS_DIRECTEUR_DE_THESE_1","MADS_PRESIDENT_DU_JURY","MADS_MEMBRE_DU_JURY_1","MADS_RAPPORTEUR_1","MADS_ECOLE_DOCTORALE_1","MADS_PARTENAIRE_DE_RECHERCHE_1","MADS_MEMBRE_DU_JURY_2","MADS_RAPPORTEUR_2","MADS_MEMBRE_DU_JURY_3","MADS_MEMBRE_DU_JURY_4"],"tef:oaisetspec":["ddc:620"],"tef:record.agent":["ABES"],"tef:record.agentnote":["Note"],"tef:record.created":["2017-10-03T08:57:07"],"tef:record.modified":["2025-03-06T03:22:53Z"],"tef:record.status":["valide"],"thesis:by_published_works":["non"],"thesis:degree_discipline":["Genie electrique"],"thesis:degree_level":["Doctorat"],"thesis:degree_name":["Docteur es"],"thesis:doctoral_school":["École doctorale électronique, électrotechnique, automatique, traitement du signal (Grenoble ; 199.-....)"],"thesis:doctoral_school_identifier":["220","https://www.idref.fr/14912449X"],"thesis:institution_identifier":["https://www.idref.fr/184668794"],"thesis:institution_name":["Université Grenoble Alpes (ComUE)"],"thesis:jury_release_opinion":["oui"],"thesis:thesis_identifier":["2017GREAT060"]},"updated_at":"2026-11-27T11:16:05Z"}